Schneider
A9F73150

Not for sale
Schneider A9F73150. Category: Low-voltage products. Not for sale; no price or quote is offered for this product.
- Reference:A9F73150
- Manufacturer / Brand:Schneider
Key Specifications
- Device Application
- Distribution
- Range
- Acti 9
- Product Or Component Type
- Miniature circuit breaker
- Product Name
- IC60
Product Description
Schneider A9F73150 (A9F73150).
Technical Specifications
| Device Application | Distribution |
|---|---|
| Range | Acti 9 |
| Product Or Component Type | Miniature circuit breaker |
| Product Name | IC60 |
| Device Short Name | IC60N |
| Poles Description | 1P |
| Number Of Protected Poles | 1 |
| [In] Rated Current | 50 A |
| Network Type | AC, DC |
| Trip Unit Technology | Thermal-magnetic |
| Curve Code | B |
| Breaking Capacity | 6000 A Icn conforming to EN 60898-1 - 230 V AC 50/60 Hz, 10 kA Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz, 10 kA Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz, 36 kA Icu conforming to EN 60947-2 - 12...60 V AC 50/60 Hz, 36 kA Icu conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz, 6000 A Icn conforming to IEC 60898-1 - 230 V AC 50/60 Hz, 20 kA Icu |
| Utilization Category | Category A EN 60947-2 EN 60947-2 EN 60947-2 EN 60947-2 EN 60947-2 EN 60947-2 EN 60947-2 EN 60947-2 EN 60947-2 EN 60947-2 EN 60947-2 EN 60947-2 EN 60947-2 EN 60947-2, Category A conforming to IEC 60947-2 |
| Suitability For Isolation | Yes conforming to EN 60947-2, Yes conforming to IEC 60947-2, Yes conforming to EN 60898-1, Yes conforming to IEC 60898-1 |
| Standards | EN 60898-1, EN 60947-2, IEC 60898-1, IEC 60947-2 |
| Network Frequency | 50/60 Hz |
| Magnetic Tripping Limit | 4 x In +/- 20 % |
| [Ics] Rated Service Breaking Capacity | 6000 A 100 % x Icu conforming to EN 60898-1 - 230 V AC 50/60 Hz, 27 kA 75 % x Icu conforming to EN 60947-2 - 12...60 V AC 50/60 Hz, 7,5 kA 75 % x Icu conforming to EN 60947-2 - 220...240 V AC 50/60 Hz, 27 kA 75 % x Icu conforming to IEC 60947-2 - 12...60 V AC 50/60 Hz, 7,5 kA 75 % x Icu conforming to IEC 60947-2 - 220...240 V AC 50/60 Hz, 15 kA 75 % x Icu conforming st |
| [Ui] Rated Insulation Voltage | 500 V AC 50/60 Hz conforming to IEC 60947-2, 500 V AC 50/60 Hz conforming to EN 60947-2 |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to EN 60947-2, 6 kV conforming to IEC 60947-2 |
| Contact Position Indicator | Yes |
| Control Type | Toggle |
| Local Signalling | Trip indicator |
| Mounting Mode | Fixed |
| Mounting Support | DIN rail |
| Comb Busbar Distribution Block Compatibility | YES top or bottom |
| 9 Mm Pitches | 2 |
| Height | 85 mm |
| Width | 18 mm |
| Depth | 78.5 mm |
| Product Weight | 0.215 kg |
| Color | White |
| Mechanical Durability | 20000 cycles |
| Electrical Durability | 10000 cycles |
| Connections - Terminals | Single terminal, top or bottom rigid wire(s) 1...35 mm² max, Single terminal, top or bottom flexible wire(s) 1...25 mm² max |
| Wire Stripping Length | 14 mm top or bottom |
| Tightening Torque | 3.5 N.m top or bottom |
| Earth-leakage Protection | None |
| IP Degree Of Protection | IP20 conforming to EN 60529, IP20 conforming to IEC 60529 |
| Pollution Degree | 3 conforming to EN 60947-2, 3 conforming to IEC 60947-2 |
| Overvoltage Category | IV |
| Tropicalisation | 2 conforming to IEC 60068-1 |
| Relative Humidity | 95 % ( 55 °C ) |
| Operating Altitude | 0...2000 m |
| Ambient Air Temperature For Operation | -35...70 °C |
| Ambient Air Temperature For Storage | -40...85 °C |
| Sustainable Offer Status | Green Premium product |
| ROHS | Compliant - since 1001 - Schneider Electric declaration of conformity |
| REACH | Reference not containing SVHC above the threshold |
| Product Environmental Profile | Available |
| End Of Life Instructions | No specific recycling operations required |