Schneider A9L40601 - iPRD40r 3P+N
Schneider

A9L40601 - iPRD40r 3P+N

Schneider A9L40601, iPRD40r 3P+N. Category: iPF & iPRD. Request a quote for price and lead time.

Key Specifications

Range Of Product
IPRD
Range Of Product
Acti9
Product Name
Acti9 iPRD
Product Or Component Type
Surge arrester with pluggable cartridge

Product Description

This Acti9 iPRD40r surge arrester protects 3P+N installations. It allows quick replacement of damaged cartridges. This Type 2 device is recommended for high risk level in incoming panel board. It offers remote reporting of the "cartridge must be changed" message. It can be turned over to allow the phase/neutral/earth cables to enter through either the top or the bottom. The associated circuit breaker Isc breaking capacity can go up to 50kA. It is compatible with TT and TN-S earthing system. The Imax rated discharge current is 40kA. The In nominal discharge current is 15kA. The Uc maximum continuous operating voltage in common mode is 260VAC between neutral and earth, and 350VAC between phase and earth. The Uc maximum continuous operating voltage in differential mode (between phase and neutral) is 350VAC. The Up Voltage protection level is 1.4kV in common mode (N/PE) and in differential mode (L/N). The Un rated service voltage is 230VAC or 400VAC. The operating frequency is 50Hz or 60Hz. The dimensions are (W) 72mm x (H) 85mm x (D) 69mm. The width in 9mm pitches is 8. The weight is 450g. The degree of protection is IP20 and IP40 in modular enclosure. The operating temperature is -25°C to 60°C. The storage temperature is -40°C to 85°C. This product is compliant with EN 61643-11 and IEC 61643-11 standards.

Key Features

  • Recommended for a high risk level in incoming panel board
  • Type 2 40kA surge arrester according to IEC 61643-11:2011 and EN 61643-11:2012 standards
  • Suitable for TT and TN-S networks with high prospective short-circuit fault currents
  • Fitted with a remote transfer contact to send cartridge must be replaced indication information
  • Easy to replace withdrawable cartridges, and pluggable with anti-vibration lock

Technical Specifications

Main14
Range Of ProductIPRD
Range Of ProductActi9
Product NameActi9 iPRD
Product Or Component TypeSurge arrester with pluggable cartridge
Device Short NameiPRD40r
Device ApplicationDistribution
StandardsEN 61643-11:2012; IEC 61643-11:2011
Product CertificationsCE
Quality LabelsNF; KEMA-KEUR
Poles Description3P + N
Remote SignallingWith
Signal Contacts Composition1 SD (1 C/O)
Surge Arrester TypeElectrical distribution network
Earthing SystemTT; TN-S
Complementary21
Surge Arrester Class TypeType 2
Surge Arrester TechnologyMOV + GDT
[Ue] Rated Operational Voltage230/400 V AC (+/- 10 %) at 50/60 Hz
Nominal Discharge CurrentCommon mode: 15 kA (L/PE); Common mode: 15 kA (N/PE); Differential mode: 15 kA (L/N)
Maximum Discharge CurrentCommon mode: 40 kA L/PE; Common mode: 40 kA N/PE; Differential mode: 40 kA L/N
[Uc] Maximum Continuous Operating VoltageCommon mode: 260 V N/PE; Common mode: 350 V L/PE; Differential mode: 350 V L/N
Maximum [Up] Voltage Protection LevelCommon mode 1.4 kV type 2 N/PE; Differential mode 1.4 kV type 2 L/N
[Ut] Temporary Overvoltage337 V L/N 5 s withstand; 1200 V N/PE 200 ms safe failure mode; 442 V L/PE 5 s withstand; 1453 V L/PE 200 ms safe failure mode
Disconnector Device TypeAssociated circuit breaker iC60H 40 A curve C - Icu 15 kA; Associated circuit breaker IC60N 40 A curve C - Icu 10 kA; Associated circuit breaker NG125H 40 A curve C - Icu 36 kA; Associated circuit breaker NG125L 40 A curve C - Icu 50 kA; Associated circuit breaker NG125N 40 A curve C - Icu 25 kA; Associated fuse gG 63 A - Icu 15 kA; Associated fuse gG 80 A - Icu 50 kA
Signalling Circuit Voltage0.25 A/250 V AC 50/60 Hz
Mounting ModeClip-on (DIN rail)
9 Mm Pitches8
Height85 mm
Width72 mm
Depth69 mm
Net Weight0.421 kg
ColourWhite (RAL 9003)
[Ipe] Ground Residual Current0.6 mA; 0.003 mA
Connections - TerminalsTunnel type terminal (downside) 2.5…35 mm²; Tunnel type terminal (upside) 2.5…35 mm²
Tightening Torque2.5 N.m
Compatibility CodeIPRD40r
Environment5
IK Degree Of ProtectionIK03 conforming to IEC 62262
Relative Humidity5…95 %
Operating Altitude2000 m
Ambient Air Temperature For Operation-25…60 °C
Ambient Air Temperature For Storage-40…85 °C
Packing Units18
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height8 cm
Package 1 Width8.3 cm
Package 1 Length9.3 cm
Package 1 Weight452 g
Unit Type Of Package 2BB1
Number Of Units In Package 23
Package 2 Height9 cm
Package 2 Width10 cm
Package 2 Length28 cm
Package 2 Weight1.424 kg
Unit Type Of Package 3S03
Number Of Units In Package 327
Package 3 Height30 cm
Package 3 Width30 cm
Package 3 Length40 cm
Package 3 Weight13.363 kg
Logistical informations1
Country Of OriginCN
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents3

Tags

See products with the same tag in the catalogue.