Schneider A9N61650, Circuit breaker; 800VDC; Inom: 10A; Poles: 2; Charact: B; 1.5kA. Category: C60 H-DC Circuit Breaker. Request a quote for price and lead time.

Key Specifications

Range Of Product
C60
Product Or Component Type
Miniature circuit-breaker
Device Short Name
C60PV-DC
Poles Description
2P

Product Description

This Acti9 C60PV-DC is a low voltage miniature circuit breaker (MCB) dedicated to multi string photovoltaic installations. It is a 2P circuit breaker with 2 protected poles, 10A rated current and B tripping curve. It can be mounted on DIN rail for modular installation. Its width is 8 modules of 9mm. As circuit breaker, its breaking capacity, according to IEC/EN 60947-2, is 1.5kA at 800VDC and 3kA at 650VDC. It is designed to protect the cables located between each string of photovoltaic modules and the photovoltaic inverter against overloads and short circuits. It has an IP40 degree of protection (as per IEC/EN 60529) on its terminals in modular enclosure. Its fast closing mechanism, independent of the speed of actuation of the toggle, improves its service life. The tripping or position indication functions are remotely provided by adding electrical auxiliaries. The presence of the green strip guarantees physical opening of the contacts and allows operations to be performed on the downstream circuit in complete safety.

Technical Specifications

Main9
Range Of ProductC60
Product Or Component TypeMiniature circuit-breaker
Device Short NameC60PV-DC
Poles Description2P
Number Of Protected Poles2
Network TypeDC
Curve CodeB
Utilisation CategoryCategory A conforming to EN/IEC 60947-2
Suitability For IsolationYes conforming to EN/IEC 60947-2
Complementary27
[In] Rated Current10 A
Voltage Drop680 mV 68 mOhm 6.8 W 10 A
[Ue] Rated Operational Voltage800 V DC
Magnetic Tripping Limit5.5 x In
Breaking Capacity3 kA Icu at 650 V DC; 1.5 kA Icu at 800 V DC
[Ics] Rated Service Breaking Capacity1.5 kA 100 % - 800 V DC; 3 kA 100 % - 650 V DC
[Ui] Rated Insulation Voltage1000 V DC
[Uimp] Rated Impulse Withstand Voltage6 kV
Polarity SensitivityNo (can protect against bi-directional current)
Contact Position IndicatorYes
Control TypeToggle
Mounting ModeFixed
Mounting Support35 mm symmetrical DIN rail
9 Mm Pitches8
Height132.7 mm
Width72 mm
Depth77.4 mm
Net Weight0.545 kg
ColourWhite
Mechanical Durability20000 cycles
Electrical Durability1500 cycles L/R = 2 ms
Locking Options DescriptionPadlocking in OFF position
Connections - TerminalsTunnel terminal (downside) 1…25 mm² rigid; Tunnel terminal (downside) 1…16 mm² flexible; Pre-wired cable (upside)
Wire Stripping Length14 mm
Tightening Torque2.5 N.m
Market SegmentResidential; Small commercial
Compatibility CodeC60PV-DC
Environment5
StandardsEN/IEC 60947-2
Pollution Degree2
Relative Humidity95 % at 55 °C
Ambient Air Temperature For Operation-25…70 °C
Ambient Air Temperature For Storage-40…85 °C
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height8.200 cm
Package 1 Width7.500 cm
Package 1 Length13.500 cm
Package 1 Weight522.000 g
Unit Type Of Package 2S03
Number Of Units In Package 230
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight16.230 kg
Logistical informations1
Country Of OriginCN
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents1