| Apparent Power | 61.9 kVA at 380 V |
|---|
| Continuous Output Current | 94 A at 380 V; 94 A at 460 V |
|---|
| Maximum Transient Current | 103.4 A for 60 s |
|---|
| Speed Drive Output Frequency | 0.5…200 Hz |
|---|
| Speed Range | 1…10 |
|---|
| Speed Accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn |
|---|
| Local Signalling | 1 LED (red) for DC bus energized |
|---|
| Output Voltage | <= power supply voltage |
|---|
| Isolation | Electrical between power and control |
|---|
| Type Of Cable | Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR; Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC; With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC |
|---|
| Electrical Connection | VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / 14 AWG; L1/R, L2/S, L3/T: terminal 50 mm² / 1/0 AWG |
|---|
| Tightening Torque | 0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES); 24 N.m, 212 lb.in (L1/R, L2/S, L3/T) |
|---|
| Supply | Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection; Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection |
|---|
| Sampling Duration | 2 ms +/- 0.5 ms F discrete; 2 ms +/- 0.5 ms R discrete; 2 ms +/- 0.5 ms RES discrete; 3.5 ms +/- 0.5 ms VIA analog; 22 ms +/- 0.5 ms VIB analog |
|---|
| Response Time | FM 2 ms, tolerance +/- 0.5 ms for analog output(s); FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s); FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s); RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s) |
|---|
| Accuracy | +/- 0.6 % (VIA) for a temperature variation 60 °C; +/- 0.6 % (VIB) for a temperature variation 60 °C; +/- 1 % (FM) for a temperature variation 60 °C |
|---|
| Linearity Error | VIA: +/- 0.15 % of maximum value for input; VIB: +/- 0.15 % of maximum value for input; FM: +/- 0.2 % for output |
|---|
| Analogue Output Type | FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits; FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits |
|---|
| Discrete Output Type | Configurable relay logic: (FLA, FLC) NO - 100000 cycles; Configurable relay logic: (FLB, FLC) NC - 100000 cycles; Configurable relay logic: (RY, RC) NO - 100000 cycles |
|---|
| Minimum Switching Current | 3 mA at 24 V DC for configurable relay logic |
|---|
| Maximum Switching Current | 5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R); 5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R); 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R); 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R) |
|---|
| Discrete Input Type | F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm; R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm; RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm |
|---|
| Discrete Input Logic | Positive logic (source) (F, R, RES), = 11 V (state 1); Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1) |
|---|
| Dielectric Strength | 3535 V DC between earth and power terminals; 5092 V DC between control and power terminals |
|---|
| Insulation Resistance | >= 1 mOhm 500 V DC for 1 minute |
|---|
| Frequency Resolution | Display unit: 0.1 Hz; Analog input: 0.024/50 Hz |
|---|
| Communication Service | Read device identification (43); Write multiple registers (16) 2 words maximum; Time out setting from 0.1 to 100 s; Read holding registers (03) 2 words maximum; Monitoring inhibitable; Write single register (06) |
|---|
| Option Card | Communication card for LonWorks |
|---|
| Power Dissipation In W | 1253 W |
|---|
| Air Flow | 429 m3/h |
|---|
| Functionality | Mid |
|---|
| Specific Application | HVAC |
|---|
| Variable Speed Drive Application Selection | Building - HVAC compressor for scroll; Building - HVAC fan; Building - HVAC pump |
|---|
| Motor Power Range AC-3 | 30…50 kW at 380…440 V 3 phases; 30…50 kW at 480…500 V 3 phases |
|---|
| Motor Starter Type | Variable speed drive |
|---|
| Discrete Output Number | 2 |
|---|
| Analogue Input Number | 2 |
|---|
| Analogue Input Type | VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits; VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits; VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm; VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits |
|---|
| Analogue Output Number | 1 |
|---|
| Physical Interface | 2-wire RS 485 |
|---|
| Connector Type | 1 RJ45; 1 open style |
|---|
| Transmission Rate | 9600 bps or 19200 bps |
|---|
| Transmission Frame | RTU |
|---|
| Number Of Addresses | 1…247 |
|---|
| Data Format | 8 bits, 1 stop, odd even or no configurable parity |
|---|
| Type Of Polarization | No impedance |
|---|
| Asynchronous Motor Control Profile | Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo); Voltage/frequency ratio - Energy Saving, quadratic U/f; Voltage/frequency ratio, 2 points; Voltage/frequency ratio, 5 points; Flux vector control without sensor, standard |
|---|
| Torque Accuracy | +/- 15 % |
|---|
| Transient Overtorque | 120 % of nominal motor torque +/- 10 % for 60 s |
|---|
| Acceleration And Deceleration Ramps | Linear adjustable separately from 0.01 to 3200 s; Automatic based on the load |
|---|
| Motor Slip Compensation | Adjustable; Not available in voltage/frequency ratio motor control; Automatic whatever the load |
|---|
| Switching Frequency | 6...16 kHz adjustable; 8...16 kHz with derating factor |
|---|
| Nominal Switching Frequency | 8 kHz |
|---|
| Braking To Standstill | By DC injection |
|---|
| Network Frequency | 47.5...63 Hz |
|---|
| Prospective Line Isc | 22 kA |
|---|
| Protection Type | Overheating protection: drive; Thermal power stage: drive; Short-circuit between motor phases: drive; Input phase breaks: drive; Overcurrent between output phases and earth: drive; Overvoltages on the DC bus: drive; Break on the control circuit: drive; Against exceeding limit speed: drive; Line supply overvoltage and undervoltage: drive; Line supply undervoltage: drive; Against input phase loss: d |
|---|
| Width | 240 mm |
|---|
| Height | 550 mm |
|---|
| Depth | 244 mm |
|---|