Schneider ATV630U07N4 - Automation module: Inverter; 0.75kW; 3x400VAC; 3x380÷480VAC; IP20
Schneider

Automation module: Inverter; 0.75kW; 3x400VAC; 3x380÷480VAC; IP20

Schneider ATV630U07N4, Automation module: Inverter; 0.75kW; 3x400VAC; 3x380÷480VAC; IP20. Category: Altivar Process ATV600. Request a quote for price and lead time.

Key Specifications

Range Of Product
Altivar Process ATV600
Product Specific Application
Process and utilities
Product Or Component Type
Variable speed drive
Variant
Standard version

Product Description

This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 380V to 480V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 0.75kW / 1hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 0.37kW / 0.5hp for applications requiring significant overload (up to 150%). It weighs 4.5kg and its dimensions are, 144mm wide, 350mm high, 203mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.

Key Features

  • Embedded power measurement and energy dashboard
  • Embedded process monitoring and control
  • Stop and Go function to reduce energy consumption
  • Asset monitoring and protection
  • Drift monitoring

Technical Specifications

Main24
Range Of ProductAltivar Process ATV600
Product Specific ApplicationProcess and utilities
Product Or Component TypeVariable speed drive
VariantStandard version
Device Short NameATV630
Mounting ModeWall mount
Communication Port ProtocolModbus TCP; Ethernet; Modbus serial
[Us] Rated Supply Voltage380...480 V - 15...10 %
Relative Symmetric Mains Voltage Tolerance10 %
Relative Symmetric Network Frequency Tolerance5 %
Nominal Output Current2.2 A
IP Degree Of ProtectionIP21
Product DestinationAsynchronous motors; Synchronous motors
EMC FilterIntegrated with 50 m conforming to IEC 61800-3 category C2; Integrated with 150 m conforming to IEC 61800-3 category C3
Degree Of ProtectionUL type 1 conforming to UL 508C
Type Of CoolingForced convection
Supply Frequency50...60 Hz - 5...5 %
Motor Power KW0.75 kW (normal duty); 0.37 kW (heavy duty)
Motor Power Hp1 hp normal duty; 0.5 hp heavy duty
Line Current1.5 A at 380 V (normal duty); 1.3 A at 480 V (normal duty); 0.9 A at 380 V (heavy duty); 0.8 A at 480 V (heavy duty)
Continuous Output Current2.2 A at 4 kHz for normal duty; 1.5 A at 4 kHz for heavy duty
Speed Drive Output Frequency0.1…500 Hz
Safety FunctionSTO (safe torque off) SIL 3
Option CardSlot A: communication module, Profibus DP V1; Slot A: communication module, PROFINET; Slot A: communication module, DeviceNet; Slot A: communication module, Modbus TCP/EtherNet/IP; Slot A: communication module, CANopen daisy chain RJ45; Slot A: communication module, CANopen SUB-D 9; Slot A: communication module, CANopen screw terminals; Slot A/slot B: digital and analog I/O extension module; Slot
Complementary74
Discrete Input Number8
Discrete Input TypeDI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V)
Discrete Input Logic16 preset speeds
Discrete Output Number0
Discrete Output TypeRelay outputs R1A, R1B, R1C 250 V AC 3000 mA; Relay outputs R1A, R1B, R1C 30 V DC 3000 mA; Relay outputs R2A, R2C 250 V AC 5000 mA; Relay outputs R2A, R2C 30 V DC 5000 mA; Relay outputs R3A, R3C 250 V AC 5000 mA; Relay outputs R3A, R3C 30 V DC 5000 mA
Analogue Input Number3
Analogue Input TypeAI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits; AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits; AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits
Analogue Output Number2
Analogue Output TypeSoftware-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits; Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits; Software-configurable current DQ-, DQ+: 30 V DC; Software-configurable current DQ-, DQ+: 100 mA
Relay Output Number3
Relay Output TypeConfigurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles; Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles; Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles
Maximum Switching CurrentRelay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC; Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC; Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC; Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC
Minimum Switching CurrentRelay output R1, R2, R3: 5 mA at 24 V DC
Network Number Of Phases3 phases
Physical InterfaceEthernet; 2-wire RS 485
Method Of AccessSlave Modbus TCP
Transmission Rate10, 100 Mbits; 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Transmission FrameRTU
Output Voltage<= power supply voltage
Permissible Temporary Current Boost1.1 x In during 60 s (normal duty); 1.5 x In during 60 s (heavy duty)
Data Format8 bits, configurable odd, even or no parity
Type Of PolarizationNo impedance
Frequency ResolutionDisplay unit: 0.1 Hz; Analog input: 0.012/50 Hz
Electrical ConnectionControl: removable screw terminals 0.5...1.5 mm²/20 AWG...16 AWG; Motor: screw terminal 2.5...6 mm²/14 AWG...10 AWG; Line side: screw terminal 2.5...6 mm²/14 AWG...10 AWG
Connector TypeRJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP; RJ45 (on the remote graphic terminal) for Modbus serial
Exchange ModeHalf duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Number Of Addresses1…247 for Modbus serial
SupplyExternal supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection; Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection; Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection
Local Signalling3 LEDs for local diagnostic; 3 LEDs (dual colour) for embedded communication status; 4 LEDs (dual colour) for communication module status; 1 LED (red) for presence of voltage
Input CompatibilityDI1...DI6: discrete input level 1 PLC conforming to IEC 61131-2; DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68; STOA, STOB: discrete input level 1 PLC conforming to IEC 61131-2
Sampling Duration2 ms +/- 0.5 ms (DI1...DI4) - discrete input; 5 ms +/- 1 ms (DI5, DI6) - discrete input; 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input; 10 ms +/- 1 ms (AO1) - analog output
Accuracy+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input; +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Linearity ErrorAI1, AI2, AI3: +/- 0.15 % of maximum value for analog input; AO1, AO2: +/- 0.2 % for analog output
Refresh TimeRelay output (R1, R2, R3): 5 ms (+/- 0.5 ms)
IsolationBetween power and control terminals
Discrete And Process ManufacturingBuilding - HVAC compressor centrifugal; Food and beverage processing other application; Mining mineral and metal fan; Mining mineral and metal pump; Oil and gas fan; Water and waste water other application; Building - HVAC screw compressor; Food and beverage processing pump; Food and beverage processing fan; Food and beverage processing atomization; Oil and gas electro submersible pump (ESP); Oil
Power Range0.55…1 kW at 380…440 V 3 phases; 0.55…1 kW at 480…500 V 3 phases
Enclosure MountingWall mounted
4 Quadrant Operation PossibleFalse
Asynchronous Motor Control ProfileConstant torque standard; Optimized torque mode; Variable torque standard
Synchronous Motor Control ProfilePermanent magnet motor; Synchronous reluctance motor
Maximum Output Frequency500 kHz
Acceleration And Deceleration RampsLinear adjustable separately from 0.01...9999 s
Motor Slip CompensationAdjustable; Can be suppressed; Not available in permanent magnet motor law; Automatic whatever the load
Switching Frequency2...12 kHz adjustable; 4...12 kHz with derating factor
Nominal Switching Frequency4 kHz
Braking To StandstillBy DC injection
Brake Chopper IntegratedFalse
Maximum Input Current1.5 A
Maximum Output Voltage480.0 V
Apparent Power1.1 kVA at 480 V (normal duty); 0.7 kVA at 480 V (heavy duty)
Maximum Transient Current2.4 A during 60 s (normal duty); 2.3 A during 60 s (heavy duty)
Network Frequency50...60 Hz
Prospective Line Isc50 kA
Base Load Current At High Overload1.5 A
Base Load Current At Low Overload2.2 A
Power Dissipation In WNatural convection: 26 W at 380 V, switching frequency 4 kHz; Forced convection: 21 W at 380 V, switching frequency 4 kHz
With Safety Function Safely Limited Speed (SLS)False
With Safety Function Safe Brake Management (SBC/SBT)False
With Safety Function Safe Operating Stop (SOS)False
With Safety Function Safe Position (SP)False
With Safety Function Safe Programmable LogicFalse
With Safety Function Safe Speed Monitor (SSM)False
With Safety Function Safe Stop 1 (SS1)False
With Sft Fct Safe Stop 2 (SS2)False
With Safety Function Safe Torque Off (STO)True
With Safety Function Safely Limited Position (SLP)False
With Safety Function Safe Direction (SDI)False
Protection TypeThermal protection: motor; Safe torque off: motor; Motor phase break: motor; Thermal protection: drive; Safe torque off: drive; Overheating: drive; Overcurrent between output phases and earth: drive; Overload of output voltage: drive; Short-circuit protection: drive; Motor phase break: drive; Overvoltages on the DC bus: drive; Line supply overvoltage: drive; Line supply undervoltage: drive; Line s
Quantity Per Set1
Width144 mm
Height350 mm
Depth203 mm
Net Weight4.5 kg
Environment24
Insulation Resistance> 1 MOhm 500 V DC for 1 minute to earth
Noise Level54.5 dB conforming to 86/188/EEC
Pollution Degree2 conforming to IEC 61800-5-1
Vibration Resistance1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Shock Resistance15 gn for 11 ms conforming to IEC 60068-2-27
Relative Humidity5…95 % without condensation conforming to IEC 60068-2-3
Ambient Air Temperature For Operation-15…50 °C (without derating); 50…60 °C (with derating factor)
Operating Altitude<= 1000 m without derating; 1000...4800 m with current derating 1 % per 100 m
Operating PositionVertical +/- 10 degree
Product CertificationsTÜV; ATEX zone 2/22; CSA; DNV-GL; UL; ATEX INERIS
MarkingCE
StandardsUL 508C; IEC 61800-3; IEC 61800-3 environment 1 category C2; EN/IEC 61800-3 environment 2 category C3; IEC 61800-5-1; IEC 61000-3-12; IEC 60721-3; IEC 61508; IEC 13849-1
Maximum THDI<48 % full load conforming to IEC 61000-3-12
Electromagnetic CompatibilityElectrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 6
Environmental Class (during Operation)Class 3C3 according to IEC 60721-3-3; Class 3S3 according to IEC 60721-3-3
Maximum Acceleration Under Shock Impact (during Operation)150 m/s² at 11 ms
Maximum Acceleration Under Vibrational Stress (during Operation)10 m/s² at 13...200 Hz
Maximum Deflection Under Vibratory Load (during Operation)1.5 mm at 2...13 Hz
Permitted Relative Humidity (during Operation)Class 3K5 according to EN 60721-3
Volume Of Cooling Air38 m3/h
Overvoltage CategoryIII
Regulation LoopAdjustable PID regulator
Ambient Air Transport Temperature-40…70 °C
Ambient Air Temperature For Storage-40…70 °C
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height31.500 cm
Package 1 Width17.600 cm
Package 1 Length40.500 cm
Package 1 Weight5.756 kg
Unit Type Of Package 2S06
Number Of Units In Package 26
Package 2 Height75.000 cm
Package 2 Width60.000 cm
Package 2 Length80.000 cm
Package 2 Weight47.536 kg
Logistical informations1
Country Of OriginID
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents4

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support