Schneider C40V35E400 - NSX400 HB1 ML5.3 75kA 690V 3P
Schneider

C40V35E400 - NSX400 HB1 ML5.3 75kA 690V 3P

Schneider C40V35E400, NSX400 HB1 ML5.3 75kA 690V 3P. Category: ComPacT NSX, new generation. Request a quote for price and lead time.

Key Specifications

Range
ComPacT
Product Name
ComPacT NSX
Device Short Name
NSX400HB1
Product Or Component Type
Circuit breaker

Product Description

This ComPacT NSX400HB1 is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 85kA rms at 500VAC 50/60Hz and 75kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic MicroLogic 5.3 E trip unit, with 400A rating. MicroLogic 5.3 E trip unit provides adjustable long time, short time and instantaneous protection. MicroLogic 5.3 E has an embedded display unit for fine settings adjustment and display of the energy (energy meter). This 3 poles version (140mm x 255mm x 110mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX400HB1 is part of Schneider Electric EcoStruxure Power architecture.

Key Features

  • "Schneider Electric green signature style for the entire ComPacT range"
  • "Estimated 40% reduction of wiring time for panel builders"
  • "Experience easier installation thanks to a new ergonomic front-plate design"
  • "Gain the confidence that all auxiliaries are on the right spot, and check that you have the right coil rating"
  • "Ergonomic new toggle for easier breaker manual operation"

Technical Specifications

Main20
RangeComPacT
Product NameComPacT NSX
Device Short NameNSX400HB1
Product Or Component TypeCircuit breaker
Device ApplicationDistribution
Poles Description3P
Protected Poles Description3D
[In] Rated Current400 A at 40 °C
[Ue] Rated Operational Voltage690 V AC 50/60 Hz
Network TypeAC
Network Frequency50/60 Hz
Suitability For IsolationYes conforming to EN/IEC 60947-2
Utilisation CategoryCategory A
Breaking Capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity CodeHB1 75 kA 690 V AC
Trip Unit NameMicroLogic 5.3 E
Trip Unit TechnologyElectronic
Trip Unit Protection FunctionsLSI
Control TypeToggle
Circuit Breaker Mounting ModeFixed
Complementary35
[Ui] Rated Insulation Voltage800 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage8 kV
[Ics] Rated Service Breaking Capacity85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical Durability15000 cycles
Electrical Durability12000 cycles at 440 V In/2; 6000 cycles at 440 V In; 6000 cycles at 690 V In/2; 3000 cycles at 690 V In
Power Dissipation Per Pole19.2 W
Mounting SupportBackplate
Mounting PositionHorizontal and vertical; Flat on the back
Upside ConnectionFront
Downside ConnectionFront
Connection Pitch45 mm
Protection TypeL : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection
Trip Unit Rating400 A at 40 °C
Long-time Pick-up Adjustment Type Ir (thermal Protection)Adjustable 9 settings
[Ir] Long-time Protection Pick-up Adjustment Range160...400 A
Long-time Protection Delay Adjustment Type TrAdjustable
[tr] Long-time Delay Adjustment Range15…400 s at 1.5 x Ir; 0.5…16 s at 6 x Ir; 0.35…11 s at 7.2 x Ir
Thermal Memory20 minutes before and after tripping
Short-time Protection Pick-up Adjustment Type IsdAdjustable 9 settings
[Isd] Short-time Protection Pick-up Adjustment Range1.5...10 x Ir
Short-time Protection Delay Adjustment Type TsdAdjustable 5 settings
[tsd] Short-time Delay Adjustment Range0…0.4 s I²t=off; 0.1…0.4 s I²t=on
Instantaneous Protection Pick-up Adjustment Type IiAdjustable
[Ii] Instantaneous Protection Pick-up Adjustment Range1.5...12 x In
Earth-leakage ProtectionWithout
Zone Selective Interlocking ZSIWith
Number Of Slots6 slot(s)
Local SignallingFlashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
Display TypeLCD display
Type Of MeasurementEnergy meter
Communication Of DataProtection and alarm settings; Energy metering; Time-stamped histories and event tables; Power quality; Instantaneous and demand values; Demand current and power; Maintenance indicators; Maximeters/minimeters
Width (W)140 mm
Height (H)255 mm
Depth (D)110 mm
Net Weight6.05 kg
Environment10
StandardsEN/IEC 60947-2
Overvoltage CategoryIII
Electrical Shock Protection ClassClass II on front face
Pollution Degree3 conforming to IEC 60664-1
IP Degree Of ProtectionIP40 conforming to IEC 60529
IK Degree Of ProtectionIK07 conforming to IEC 62262
Ambient Air Temperature For Operation-25…70 °C
Ambient Air Temperature For Storage-40…85 °C
Relative Humidity0…95 %
Operating Altitude0...2000 m without derating; 2000 m...5000 m with derating
Packing Units18
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height15.200 cm
Package 1 Width15.200 cm
Package 1 Length29.200 cm
Package 1 Weight5.860 kg
Unit Type Of Package 2S04
Number Of Units In Package 23
Package 2 Height30 cm
Package 2 Width40 cm
Package 2 Length60 cm
Package 2 Weight18.230 kg
Unit Type Of Package 3P12
Number Of Units In Package 312
Package 3 Height45.000 cm
Package 3 Width80.000 cm
Package 3 Length120.000 cm
Package 3 Weight84.920 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents3

Tags

See products with the same tag in the catalogue.