Schneider C63W32D630 - NSX630 HB2 ML2.3 100kA 690V 3P
Schneider

C63W32D630 - NSX630 HB2 ML2.3 100kA 690V 3P

Schneider C63W32D630, NSX630 HB2 ML2.3 100kA 690V 3P. Category: ComPacT NSX, new generation. Request a quote for price and lead time.

Key Specifications

Range
ComPacT
Product Name
ComPacT NSX
Device Short Name
NSX630HB2
Product Or Component Type
Circuit breaker

Product Description

This ComPacT NSX630HB2 is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 85kA rms at 500VAC 50/60Hz and 100kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic MicroLogic 2.3 trip unit, with 630A rating. MicroLogic 2.3 trip unit provides adjustable long time and short time protections, and a fixed instantaneous protection. This 3 poles version (140mm x 255mm x 110mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX630HB2 is part of Schneider Electric EcoStruxure Power architecture.

Key Features

  • "Schneider Electric green signature style for the entire ComPacT range"
  • "Estimated 40% reduction of wiring time for panel builders"
  • "Experience easier installation thanks to a new ergonomic front-plate design"
  • "Gain the confidence that all auxiliaries are on the right spot, and check that you have the right coil rating"
  • "Ergonomic new toggle for easier breaker manual operation"

Technical Specifications

Main20
RangeComPacT
Product NameComPacT NSX
Device Short NameNSX630HB2
Product Or Component TypeCircuit breaker
Device ApplicationDistribution
Poles Description3P
Protected Poles Description3D
[In] Rated Current630 A at 40 °C
[Ue] Rated Operational Voltage690 V AC 50/60 Hz
Network TypeAC
Network Frequency50/60 Hz
Suitability For IsolationYes conforming to EN/IEC 60947-2
Utilisation CategoryCategory A
Breaking Capacity100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking Capacity CodeHB2 100 kA 690 V AC
Trip Unit NameMicroLogic 2.3
Trip Unit TechnologyElectronic
Trip Unit Protection FunctionsLSoI
Control TypeToggle
Circuit Breaker Mounting ModeFixed
Complementary31
[Ui] Rated Insulation Voltage800 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage8 kV
[Ics] Rated Service Breaking Capacity100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical Durability15000 cycles
Electrical Durability8000 cycles at 440 V In/2; 4000 cycles at 440 V In; 6000 cycles at 690 V In/2; 2000 cycles at 690 V In
Power Dissipation Per Pole39.7 W
Mounting SupportBackplate
Mounting PositionHorizontal and vertical; Flat on the back
Upside ConnectionFront
Downside ConnectionFront
Connection Pitch45 mm
Protection TypeL : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection
Trip Unit Rating630 A at 40 °C
Long-time Pick-up Adjustment Type Ir (thermal Protection)Adjustable 9 settings
[Ir] Long-time Protection Pick-up Adjustment Range250...630 A
Long-time Protection Delay Adjustment Type TrFixed
[tr] Long-time Delay Adjustment Range400 s at 1.5 x Ir; 16 s at 6 x Ir; 11 s at 7.2 x Ir
Thermal Memory20 minutes before and after tripping
Short-time Protection Pick-up Adjustment Type IsdAdjustable 9 settings
[Isd] Short-time Protection Pick-up Adjustment Range1.5...10 x Ir
Short-time Protection Delay Adjustment Type TsdFixed
Instantaneous Protection Pick-up Adjustment Type IiFixed
[Ii] Instantaneous Protection Pick-up Adjustment Range6900 A
Earth-leakage ProtectionWithout
Zone Selective Interlocking ZSIWithout
Number Of Slots6 slot(s)
Local SignallingFlashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
Width (W)140 mm
Height (H)255 mm
Depth (D)110 mm
Net Weight6.2 kg
Environment10
StandardsEN/IEC 60947-2
Overvoltage CategoryIII
Electrical Shock Protection ClassClass II on front face
Pollution Degree3 conforming to IEC 60664-1
IP Degree Of ProtectionIP40 conforming to IEC 60529
IK Degree Of ProtectionIK07 conforming to IEC 62262
Ambient Air Temperature For Operation-25…70 °C
Ambient Air Temperature For Storage-50…85 °C
Relative Humidity0…95 %
Operating Altitude0...2000 m without derating; 2000 m...5000 m with derating
Packing Units6
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height15.2 cm
Package 1 Width15.2 cm
Package 1 Length29.2 cm
Package 1 Weight5.751 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.