Product Description
Schneider CAD50V7 (CAD50V7).
Technical Specifications
| Series | TeSys |
|---|---|
| Product Name | TeSys CAD |
| Product Or Component Type | Control relay |
| Device Short Name | CAD |
| Contactor Application | Control circuit |
| Utilization Category | AC-14, AC-15, DC-13 |
| Pole Contact Composition | 5 NO |
| Control Circuit Type | AC 50/60 Hz |
| Control Circuit Voltage | 400 V AC 50/60 Hz |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
| [Ith] Conventional Free Air Thermal Current | 10 A at <= 60 °C |
| Irms Rated Making Capacity | 140 A AC conforming to IEC 60947-5-1, 250 A DC conforming to IEC 60947-5-1 |
| [Icw] Rated Short-time Withstand Current | 100 A 1 s, 120 A 500 ms, 140 A 100 ms |
| Associated Fuse Rating | 10 A gG conforming to IEC 60947-5-1 |
| [Ui] Rated Insulation Voltage | 690 V conforming to IEC 60947-5-1, 600 V certifications UL, 600 V certifications CSA |
| Mounting Support | Plate, Rail |
| Connections - Terminals | Screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end, Screw clamp terminals 2 cable(s) 1...4 mm² - cable stiffness: flexible - without cable end, Screw clamp terminals 1 cable(s) 1...4 mm² - cable stiffness: flexible - with cable end, Screw clamp terminals 2 cable(s) 1...2.5 mm² - cable stiffness: flexible - with cable end, Screw clamp termina |
| Tightening Torque | 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2, 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm |
| Control Circuit Voltage Limits | 0.3...0.6 Uc drop-out, 0.8...1.1 Uc operational 50 Hz, 0.85...1.1 Uc operational 60 Hz |
| Operating Time | 12...22 ms coil energisation and NO closing, 4...12 ms coil de-energisation and NO opening |
| Mechanical Durability | 30 Mcycles |
| Maximum Operating Rate | 180 cyc/mn |
| Inrush Power In VA | 70 VA at 20 °C 50 Hz |
| Hold-in Power Consumption In VA | 8 VA at 20 °C 50 Hz |
| Minimum Switching Voltage | 17 V |
| Minimum Switching Current | 5 mA |
| Non-overlap Time | 1.5 ms on de-energisation (between NC and NO contact), 1.5 ms on energisation (between NC and NO contact) |
| Insulation Resistance | > 10 MOhm |
| Height | 77 mm |
| Width | 45 mm |
| Depth | 84 mm |
| Product Weight | 0.58 kg |
| Standards | BS 4794, EN 60947-5, IEC 60947-5-1, NF C 63-140, VDE 0660 |
| Product Certifications | CSA, UL |
| IP Degree Of Protection | IP2x front face conforming to VDE 0106 |
| Protective Treatment | TH conforming to IEC 60068 |
| Ambient Air Temperature For Operation | -40...70 °C |
| Ambient Air Temperature For Storage | -60...80 °C |
| Operating Altitude | 3000 m without derating |
| Mechanical Robustness | Shocks control relay open 10 Gn for 11 ms IEC 60068-2-27, Shocks control relay closed 15 Gn for 11 ms IEC 60068-2-27, Vibrations control relay open 2 Gn, 5...300 Hz IEC 60068-2-6, Vibrations control relay closed 4 Gn, 5...300 Hz IEC 60068-2-6 |
| Sustainable Offer Status | Green Premium product |
| ROHS | Compliant - since 0627 - Schneider Electric declaration of conformity |
| REACH | Reference not containing SVHC above the threshold |
| Product Environmental Profile | Available |
| End Of Life Instructions | Available |