Schneider GV2ME16 - Motor breaker; 5.5kW; 230÷690VAC; for DIN rail mounting; IP20
Schneider

Motor breaker; 5.5kW; 230÷690VAC; for DIN rail mounting; IP20

Schneider GV2ME16, Motor breaker; 5.5kW; 230÷690VAC; for DIN rail mounting; IP20. Category: TeSys Deca - frame 2. In stock.

Key Specifications

Range
TeSys Deca
Product Name
TeSys GV2
Product Or Component Type
Motor circuit breaker
Device Short Name
GV2ME

Product Description

  • TeSys GV motor circuit breaker, 3 poles (3P), 14A/690V, for 3-phase motor applications 5.5kW@400V.
  • It provides a thermal-magnetic protection with a thermal setting range 9-14A, magnetic tripping at 13xIn, high breaking capacity Icu 15kA@400V.
  • Connection by screw clamp terminals.
  • Start-stop control by push-button guaranteed for 100 000 cycles AC-3.
  • Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX),

Key Features

  • "New modern look & feel of all machines"
  • "Wide range of GVs: Magnetic, thermal magnetic, different sizes (GV2,GV3,GV4)"
  • "Easier to install and operate with multi-standard screws"
  • "Sturdy and long-lasting power connection with EverLink terminals"
  • "Digital customer experience for technical documents"

Technical Specifications

Main6
RangeTeSys Deca
Product NameTeSys GV2
Product Or Component TypeMotor circuit breaker
Device Short NameGV2ME
Device ApplicationMotor protection
Trip Unit TechnologyThermal-magnetic
Complementary30
Poles Description3P
Network TypeAC
Utilisation CategoryCategory A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1; AC-3e conforming to IEC 60947-4-1
Network Frequency50/60 Hz conforming to IEC 60947-2
Motor Power KW5.5 kW at 400/415 V AC 50/60 Hz; 7.5 kW at 500 V AC 50/60 Hz; 9 kW at 690 V AC 50/60 Hz; 11 kW at 690 V AC 50/60 Hz
Breaking Capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 6 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] Rated Service Short-circuit Breaking Capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control TypePush-button
[In] Rated Current14 A
Thermal Protection Adjustment Range9…14 A conforming to IEC 60947-2
Magnetic Tripping Current253.4 A
[Ith] Conventional Free Air Thermal Current14 A conforming to IEC 60947-2
[Ue] Rated Operational Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] Rated Insulation Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage6 kV conforming to IEC 60947-2
Phase Failure SensitivityYes conforming to IEC 60947-4-1
Suitability For IsolationYes conforming to IEC 60947-1
Power Dissipation Per Pole2.5 W
Mechanical Durability100000 cycles
Electrical Durability100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In
Rated DutyUninterrupted conforming to IEC 60947-4-1
Connections - TerminalsPower circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid; Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end; Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end
Tightening Torque1.7 N.m - on screw clamp terminal
Fixing Mode35 mm symmetrical DIN rail: clipped; Panel: screwed (with adaptor plate)
Mounting PositionHorizontal; Vertical
Width45 mm
Height89 mm
Depth78.5 mm
Net Weight0.26 kg
ColourDark grey
Environment10
StandardsEN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-2-40:Annex JJ; IEC/EN 60335-1:Clause 30.2
Product CertificationsCB Scheme; CE; UKCA; CCC; cULus; EAC; ATEX; LROS (Lloyds register of shipping); BV; RINA; DNV-GL
IK Degree Of ProtectionIK04
IP Degree Of ProtectionIP20 conforming to IEC 60529
Climatic Withstandconforming to IACS E10
Ambient Air Temperature For Storage-40…80 °C
Fire Resistance960 °C conforming to IEC 60695-2-11
Ambient Air Temperature For Operation-20…60 °C
Mechanical RobustnessShocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz
Operating Altitude<= 2000 m
Packing Units18
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height4.700 cm
Package 1 Width8.500 cm
Package 1 Length9.200 cm
Package 1 Weight280.000 g
Unit Type Of Package 2S02
Number Of Units In Package 224
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight6.997 kg
Unit Type Of Package 3P06
Number Of Units In Package 3384
Package 3 Height75.000 cm
Package 3 Width60.000 cm
Package 3 Length80.000 cm
Package 3 Weight117.000 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18