Schneider
Motor breaker; 0.09kW; 230÷690VAC; for DIN rail mounting; IP20
Schneider GV2P03, Motor breaker; 0.09kW; 230÷690VAC; for DIN rail mounting; IP20. Category: TeSys Deca - frame 2. Request a quote for price and lead time.
- Reference:GV2P03
- Manufacturer / Brand:Schneider
- Availability:On Request / Inquire Stock
- Price:76.30 EUR (Request a quote)
Key Specifications
- Range
- TeSys Deca
- Product Name
- TeSys GV2
- Product Or Component Type
- Motor circuit breaker
- Device Short Name
- GV2P
Product Description
- TeSys GV motor circuit breaker, 3 poles (3P), 0.4A/690V, for 3-phase motor applications 0.09kW@400V.
- It provides a thermal-magnetic protection with a thermal setting range 0.25-0.4A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V.
- Connection by screw clamp terminals.
- Start-stop control by rotary knob guaranteed for 100 000 cycles AC-3.
- Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX),
Key Features
- "New modern look & feel of all machines"
- "Wide range of GVs: Magnetic, thermal magnetic, different sizes (GV2,GV3,GV4)"
- "Easier to install and operate with multi-standard screws"
- "Sturdy and long-lasting power connection with EverLink terminals"
- "Digital customer experience for technical documents"
Technical Specifications
Main6
| Range | TeSys Deca |
|---|---|
| Product Name | TeSys GV2 |
| Product Or Component Type | Motor circuit breaker |
| Device Short Name | GV2P |
| Device Application | Motor protection |
| Trip Unit Technology | Thermal-magnetic |
Complementary29
| Poles Description | 3P |
|---|---|
| Network Type | AC |
| Utilisation Category | Category A conforming to IEC 60947-2; AC-3 conforming to IEC 60947-4-1; AC-3e conforming to IEC 60947-4-1 |
| Network Frequency | 50/60 Hz conforming to IEC 60947-2 |
| Motor Power KW | 0.09 kW at 400/415 V AC 50/60 Hz |
| Breaking Capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ics] Rated Service Short-circuit Breaking Capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2; 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Control Type | Rotary handle |
| [In] Rated Current | 0.4 A |
| Thermal Protection Adjustment Range | 0.25…0.4 A conforming to IEC 60947-2 |
| Magnetic Tripping Current | 5.8 A |
| [Ith] Conventional Free Air Thermal Current | 0.4 A conforming to IEC 60947-2 |
| [Ue] Rated Operational Voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Ui] Rated Insulation Voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947-2 |
| Phase Failure Sensitivity | Yes conforming to IEC 60947-4-1 |
| Suitability For Isolation | Yes conforming to IEC 60947-1 |
| Power Dissipation Per Pole | 2.5 W |
| Mechanical Durability | 100000 cycles |
| Electrical Durability | 100000 cycles for AC-3 at 415 V In; 100000 cycles for AC-3e at 415 V In |
| Rated Duty | Uninterrupted conforming to IEC 60947-4-1 |
| Connections - Terminals | Power circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid; Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end; Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end |
| Tightening Torque | 1.7 N.m - on screw clamp terminal |
| Fixing Mode | 35 mm symmetrical DIN rail: clipped; Panel: screwed (with 2 x M4 screws) |
| Mounting Position | Horizontal; Vertical |
| Width | 45 mm |
| Height | 89 mm |
| Depth | 97 mm |
| Colour | Dark grey |
Environment10
| Standards | EN/IEC 60947-2; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC/EN 60335-2-40:Annex JJ; IEC/EN 60335-1:Clause 30.2 |
|---|---|
| Product Certifications | CB Scheme; CE; UKCA; CCC; cULus; EAC; ATEX; LROS (Lloyds register of shipping); BV; RINA; DNV-GL |
| IK Degree Of Protection | IK04 |
| IP Degree Of Protection | IP20 conforming to IEC 60529 |
| Climatic Withstand | conforming to IACS E10 |
| Ambient Air Temperature For Storage | -40…80 °C |
| Fire Resistance | 960 °C conforming to IEC 60695-2-11 |
| Ambient Air Temperature For Operation | -20…60 °C |
| Mechanical Robustness | Shocks: 30 Gn for 11 ms; Vibrations: 5 Gn, 5...150 Hz |
| Operating Altitude | <= 2000 m |
Packing Units18
| Unit Type Of Package 1 | PCE |
|---|---|
| Number Of Units In Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 9.000 cm |
| Package 1 Length | 10.000 cm |
| Package 1 Weight | 255.000 g |
| Unit Type Of Package 2 | S02 |
| Number Of Units In Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.500 kg |
| Unit Type Of Package 3 | P06 |
| Number Of Units In Package 3 | 320 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 94.308 kg |
Logistical informations1
| Country Of Origin | FR |
|---|
Contractual warranty1
| Warranty (in Months) | 18 |
|---|
Documents and Downloads