The Schneider Harmony K series cam switch with reference K1D004QLH is manufactured for industrial automation applications. Featuring a 12 A conventional free air thermal current rating, this step switch includes 5 stable positions. You can request a price quote for this product from ÜÇ-EL Elektrik.
Technical Specifications
Main16
| Range Of Product | Harmony K |
|---|---|
| Product Or Component Type | Complete cam switch |
| Component Name | K1 |
| [Ith] Conventional Free Air Thermal Current | 12 A |
| Mounting Location | Front |
| Fixing Mode | Multifixing |
| Cam Switch Head Type | With front plate 45 x 45 mm |
| Type Of Operator | Black handle, length = 35 mm |
| Rotary Handle Padlocking | Without |
| Presentation Of Legend | With metallic legend, 0 - 1 - 2 - 3 - 4 black marking |
| Cam Switch Function | Stepping switch |
| Return | Without |
| Off Position | With Off position |
| Poles Description | 1P |
| Switching Positions | Right: 0° - 45° - 90° - 135° - 180° |
| IP Degree Of Protection | IP40 conforming to IEC 60529 |
Complementary19
| Number Of Steps | 4 |
|---|---|
| Switching Angle | 45 ° |
| [Ui] Rated Insulation Voltage | 690 V (pollution degree 3) conforming to IEC 60947-1 |
| [Ithe] Conventional Enclosed Thermal Current | 10 A |
| Rated Operational Power In W | 10500 W AC-21, 500...660 V 3 phases conforming to IEC 947-3; 1100 W AC-3, 230 V 3 phases conforming to IEC 947-3; 1500 W AC-23A, 230 V 3 phases conforming to IEC 947-3; 1500 W AC-3, 400 V 1 phase conforming to IEC 947-3; 1500 W AC-3, 400 V 3 phases conforming to IEC 947-3; 1500 W AC-3, 500 V 3 phases conforming to IEC 947-3; 1500 W AC-3, 690 V 3 phases conforming to IEC 947-3; 2200 W AC-23A, 400 V |
| [Ie] Rated Operational Current AC | 1.8 A at 690 V AC-3 3 phases conforming to IEC 947-3; 2.8 A at 500 V AC-3 3 phases conforming to IEC 947-3; 2.8 A at 690 V AC-23A 3 phases conforming to IEC 947-3; 3.3 A at 400 V AC-3 3 phases conforming to IEC 947-3; 3.8 A at 500 V AC-23A 3 phases conforming to IEC 947-3; 4.6 A at 230 V AC-3 3 phases conforming to IEC 947-3; 4.8 A at 400 V AC-23A 3 phases conforming to IEC 947-3; 5.6 A at 230 V A |
| Electrical Durability | 1000000 cycles AC-15; 1000000 cycles AC-21; 500000 cycles AC-23; 500000 cycles AC-3 |
| Maximum Operating Rate | 2.5 cyc/mn AC-21; 2.5 cyc/mn AC-23; 2.5 cyc/mn AC-3; 8.333 cyc/mn AC-15 |
| Short-circuit Current | 10000 A |
| Short-circuit Protection | 16 A cartridge fuse, type gG |
| [Uimp] Rated Impulse Withstand Voltage | 4 kV in isolating function; 6 kV conforming to IEC 947-1 |
| Contact Operation | Slow-break |
| Positive Opening | With |
| Electrical Connection | Captive screw clamp terminals flexible, clamping capacity: 2 x 1.5 mm²; Captive screw clamp terminals solid, clamping capacity: 1 x 2.5 mm² |
| Mechanical Durability | 1000000 cycles |
| CAD Overall Width | 45 mm |
| CAD Overall Height | 45 mm |
| CAD Overall Depth | 87 mm |
| Net Weight | 0.14 kg |
Environment8
| Standards | IEC 60947-3 for power circuit; IEC 60947-5-1 for control circuit; CENELEC EN 50013 |
|---|---|
| Product Certifications | CSA 240 V 3 hp 3 phases 2 -pole(s); UL 240 V 0.33 hp 1 phase 2 -pole(s); CSA 240 V 1 hp 1 phase; UL 240 V 1 hp 3 phases |
| Protective Treatment | TC |
| Ambient Air Temperature For Operation | -25…55 °C |
| Ambient Air Temperature For Storage | -40…70 °C |
| Shock Resistance | 30 gn conforming to IEC 68-2-27 |
| Vibration Resistance | 5 gn conforming to IEC 68-2-6 (f = 10…150 Hz) |
| Overvoltage Category | Class II conforming to IEC 536; Class II conforming to NF C 20-030 |
Packing Units12
| Unit Type Of Package 1 | PCE |
|---|---|
| Number Of Units In Package 1 | 1 |
| Package 1 Height | 6.500 cm |
| Package 1 Width | 6.500 cm |
| Package 1 Length | 11.000 cm |
| Package 1 Weight | 153.000 g |
| Unit Type Of Package 2 | S01 |
| Number Of Units In Package 2 | 10 |
| Package 2 Height | 15 cm |
| Package 2 Width | 15 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 1.730 kg |
Logistical informations1
| Country Of Origin | CZ |
|---|
Contractual warranty1
| Warranty (in Months) | 18 |
|---|
Documents and Downloads
Documents are published by the manufacturer and open in a new tab.