Schneider LADN02 - Auxiliary contacts; screw terminals; front; Contacts: NC x2
Schneider

Auxiliary contacts; screw terminals; front; Contacts: NC x2

Schneider LADN02, Auxiliary contacts; screw terminals; front; Contacts: NC x2. Category: TeSys Deca Advanced. In stock.

Key Specifications

Range
TeSys; TeSys Deca
Product Name
TeSys Deca
Product Or Component Type
Auxiliary contact block
Device Short Name
LADN

Product Description

TeSys D instantaneous auxiliary contact block, for contactors LC1D, LC1F and control relays CAD. It provides 2NC contacts (NC mirror certified) rated up to 10A/690V AC, connection by screw clamp terminals. Clip-on front mounting, it procures high reliability and durability. Multi standards certified (IEC, UL, CSA, CCC, EAC), Sustainability compliant.

Key Features

  • "New modern look & feel of all machines"
  • "Designed to meet the requirements of industrial and HVAC applications"
  • "Easier to install and operate with multi-standard screws"
  • "With IEC60335-1 compliance, improved fire resistance, and dustproof auxiliaries"
  • "Digital customer experience for technical documents"

Technical Specifications

Main14
RangeTeSys; TeSys Deca
Product NameTeSys Deca
Product Or Component TypeAuxiliary contact block
Device Short NameLADN
Range CompatibilityTeSys D CAD; TeSys D LC1D; TeSys F LC1F; TeSys F CR1F; TeSys Deca CAD; TeSys Deca LC1D
Mounting LocationFront
Pole Contact Composition2 NC
Contacts OperationInstantaneous
[Ue] Rated Operational Voltage690 V AC 25...400 Hz
[Ie] Rated Operational Current6 A at 120 V AC-15; 1.04 A at 690 V AC-15; 0.55 A at 125 V DC-13; 0.1 A at 600 V DC-13
[Ui] Rated Insulation Voltage690 V conforming to IEC 60947-5-1; 600 V conforming to UL; 600 V conforming to CSA
[Ith] Conventional Free Air Thermal Current10 A (at 60 °C)
StandardsEN/IEC 60947-5-1; GB/T 14048.5; EN 50012; UL 60947-5-1; CSA C22.2 No 60947-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ
Product CertificationsCB Scheme; UL; CSA; CCC; EAC; UKCA
Complementary14
Irms Rated Making Capacity140 A AC conforming to IEC 60947-5-1; 250 A DC conforming to IEC 60947-5-1
Permissible Short-time Rating100 A 1 s; 120 A 500 ms; 140 A 100 ms
Protection TypeGG fuse 10 A
Mechanical Durability30 Mcycles
Minimum Switching Current5 mA
Minimum Switching Voltage17 V
Non-overlap Time1.5 ms on de-energisation no overlap between NC and NO contact; 1.5 ms on energisation no overlap between NC and NO contact
Insulation Resistance> 10 MOhm
Connections - TerminalsScrew clamp terminals 1 cable(s) 1…4 mm²flexible with cable end; Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 1…4 mm²rigid without cable end; Screw clamp terminals 2 cable(s) 1…4 mm²rigid without cable end
Tightening Torque1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2; 1.7 N.m - with screwdriver pozidriv No 2
Height48 mm
Width26 mm
Depth42 mm
ColourDark grey
Environment6
Environmental CharacteristicNormal environment
IP Degree Of ProtectionIP20 conforming to IEC 60529
Protective TreatmentTH conforming to IEC 60068
Ambient Air Temperature For Storage-60…80 °C
Ambient Air Temperature For Operation-5…60 °C
Operating Altitude3000 m
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height5 cm
Package 1 Width2.8 cm
Package 1 Length4.3 cm
Package 1 Weight34 g
Unit Type Of Package 2S03
Number Of Units In Package 2320
Package 2 Height30 cm
Package 2 Width30 cm
Package 2 Length40 cm
Package 2 Weight11.55 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads