Schneider LC1D65ABNE - TeSys Deca Green Contactor 3P 65A AC3 24-60VAC/DC
Schneider

LC1D65ABNE - TeSys Deca Green Contactor 3P 65A AC3 24-60VAC/DC

Schneider LC1D65ABNE, TeSys Deca Green Contactor 3P 65A AC3 24-60VAC/DC. Category: TeSys Deca Advanced. Request a quote for price and lead time.

Key Specifications

Range Of Product
TeSys Deca Advanced
Product Or Component Type
Contactor
Device Short Name
LC1D
Contactor Application
Motor control; Resistive load

Product Description

TeSys D contactor, 3 poles (3NO), for motor control applications up to 65A/690V AC-3/3e (30kW@400V). It provides a low consumption 24-60V AC/DC coil with electronic control, 1NO+1NC built-in auxiliary contacts (NC mirror certified), power connection by EverLink BTR screw connectors, control connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability to demanding applications. Compact (55mm width), DIN-rail mounting or screw fixing. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine).

Key Features

  • "Ultra low consumption coil for maximized energy efficiency to meet sustainability needs"
  • "Designed to meet the requirements of industrial and HVAC applications"
  • "Easier to install and operate with multi-standard screws"
  • "With IEC60335-1 compliance, improved fire resistance, and dustproof auxiliaries"
  • "Digital customer experience for technical documents"

Technical Specifications

Main9
Range Of ProductTeSys Deca Advanced
Product Or Component TypeContactor
Device Short NameLC1D
Contactor ApplicationMotor control; Resistive load
Utilisation CategoryAC-3; AC-3e; AC-1; AC-4
Poles Description3P
[Ue] Rated Operational VoltagePower circuit: <= 690 V AC 25...400 Hz
[Ie] Rated Operational Current80 A (at <60 °C) at <= 440 V AC-1 for power circuit; 65 A (at <60 °C) at <= 440 V AC-3 for power circuit; 65 A (at <60 °C) at <= 440 V AC-3e for power circuit
[Uc] Control Circuit Voltage24...60 V AC 50/60 Hz; 24...60 V DC
Complementary39
Motor Power KW18.5 kW at 220/230 V AC 50/60 Hz (AC-3); 30 kW at 380/400 V AC 50/60 Hz (AC-3); 37 kW at 415 V AC 50/60 Hz (AC-3); 37 kW at 440 V AC 50/60 Hz (AC-3); 37 kW at 500 V AC 50/60 Hz (AC-3); 37 kW at 660/690 V AC 50/60 Hz (AC-3); 18.5 kW at 220/230 V AC 50/60 Hz (AC-3e); 30 kW at 380/400 V AC 50/60 Hz (AC-3e); 37 kW at 415 V AC 50/60 Hz (AC-3e); 37 kW at 440 V AC 50/60 Hz (AC-3e); 37 kW at 500 V AC 50/6
Motor Power Hp5 hp at 115 V AC 60 Hz for 1 phase motors; 10 hp at 230/240 V AC 60 Hz for 1 phase motors; 20 hp at 200/208 V AC 60 Hz for 3 phases motors; 20 hp at 230/240 V AC 60 Hz for 3 phases motors; 40 hp at 460/480 V AC 60 Hz for 3 phases motors; 50 hp at 575/600 V AC 60 Hz for 3 phases motors
Compatibility CodeLC1D
Pole Contact Composition3 NO
Protective CoverWith
[Ith] Conventional Free Air Thermal Current80 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signalling circuit
Irms Rated Making Capacity1000 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated Breaking Capacity1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] Rated Short-time Withstand Current110 A 40 °C - 10 min for power circuit; 260 A 40 °C - 1 min for power circuit; 640 A 40 °C - 10 s for power circuit; 900 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit
Associated Fuse Rating125 A gG at <= 690 V coordination type 1 for power circuit; 125 A gG at <= 690 V coordination type 2 for power circuit; 10 A gG for signalling circuit conforming to IEC 60947-5-1
Average Impedance1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power Dissipation Per Pole9.6 W AC-1; 6.3 W AC-3; 6.3 W AC-3e
[Ui] Rated Insulation VoltagePower circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1
Overvoltage CategoryIII
Pollution Degree3
[Uimp] Rated Impulse Withstand Voltage6 kV conforming to IEC 60947
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical Durability10 Mcycles
Electrical Durability1.8 Mcycles 57 A AC-3 at Ue <= 440 V; 0.5 Mcycles 80 A AC-1 at Ue <= 440 V; 1.8 Mcycles 57 A AC-3e at Ue <= 440 V
Control Circuit TypeAC/DC at 50/60 Hz AC/DC electronic
Coil TechnologyBuilt-in bidirectional peak limiting
Control Circuit Voltage Limits<= 0.1 Uc (-40…70 °C):drop-out AC/DC; 0.85...1.1 Uc (-40…60 °C):operational AC; 0.8...1.1 Uc (-40…60 °C):operational DC; 1...1.1 Uc (60…70 °C):operational AC/DC
Inrush Power In VA18 VA 50/60 Hz (at 20 °C)
Inrush Power In W18 W (at 20 °C)
Hold-in Power Consumption In VA1.2 VA 50/60 Hz (at 20 °C)
Hold-in Power Consumption In W0.7 W at 20 °C
Heat Dissipation0.7 W at 50/60 Hz
Operating Time55...65 ms closing; 20...80 ms opening
Maximum Operating Rate3600 cyc/h at 60 °C
Connections - TerminalsControl circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: scr
Tightening TorqueControl circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25…35 mm² hexagonal screw head 4 mm; Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1…25 mm² hexagonal screw head 4 mm; Power circuit: 2.5 N.m - with
Auxiliary Contact Composition1 NO + 1 NC
Auxiliary Contacts Typetype mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling Circuit Frequency25...400 Hz
Minimum Switching Voltage17 V for signalling circuit
Minimum Switching Current5 mA for signalling circuit
Insulation Resistance> 10 MOhm for signalling circuit
Non-overlap Time1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
Mounting SupportRail; Plate
Environment12
StandardsEN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; IEC 60335-1
Product CertificationsCCC; CSA; EAC; UL; KC; DNV-GL; LROS (Lloyds register of shipping); UKCA
IP Degree Of ProtectionIP20 front face conforming to IEC 60529
Climatic Withstandconforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible Ambient Air Temperature Around The Device-40…60 °C; 60…70 °C with derating
Operating Altitude0...3000 m
Fire Resistance850 °C conforming to IEC 60695-2-1
Mechanical RobustnessVibrations contactor open (2 Gn, 5...300 Hz); Vibrations contactor closed (4 Gn, 5...300 Hz); Shocks contactor open (10 Gn for 11 ms); Shocks contactor closed (15 Gn for 11 ms)
Height122 mm
Width55 mm
Depth120 mm
Net Weight1.002 kg
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height6.100 cm
Package 1 Width14.000 cm
Package 1 Length15.500 cm
Package 1 Weight886.000 g
Unit Type Of Package 2S02
Number Of Units In Package 210
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight9.152 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents2

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support