Key Specifications

Range
TeSys
Range Of Product
TeSys Giga
Product Or Component Type
Contactor
Device Short Name
LC1G

Product Description

  • TeSys Giga high power contactor, 4 poles (4 NO) for category AC-1 applications up to 700A @440V.
  • It's equipped with 200-500V AC/DC wide band low consumption electronic coil, PLC output control and embedded with highly reliable 1NO+1NC auxiliary contact block (17V 1mA).
  • Designed for demanding applications with maximum operating rates up to 300 cycles per hour and environments up to 60°C.
  • It’s built with high reliability delivering mechanical durability up to 8 million cycles.
  • Contact Wear Diagnosis (CWD) is a standard function, which continuously monitors and provide feedback through healthy and alarm conditions by an LED indicator
  • Remote signaling of wear diagnosis is enabled by an optional Remote Wear Diagnosis (RWD) module.
  • It is possible to replace switching module (main contacts) and control module.
  • Enhancing contactor life and maintenance possible without removing main power cables/busbars, thanks to cable-memory connection blocks.
  • Front accessible main power connections are with bolted connection and control connections by push-in terminals and easy and quick assembly.
  • It provides IP2x protection from front face with optional terminal shrouds conforming to IEC 60529 and VDE 0106.
  • It can cover -25°C to 60°C operation ambient air temperature and directly mounted on plate, with no derating up to 3000m altitude.
  • Contactor can be installed in three quadrants of vertical plane, and OLR could be directly mounted below contactor.
  • The dimensions are 290 mm x 185 mm x 226 mm (H x W x D), compact size enables panel space savings.
  • Multi standards certified (CB, CCC, cULcs, CE, UKCA marking).
  • Unique QR code provides quick access to complete product data.

Key Features

  • "Designed to meet needs of demanding applications built-in with advanced features and functionalities"
  • "Fewer references covering wider applications means simpler to select and less inventory to carry"
  • "Coil designed for less energy consumption and wider voltage band-width"
  • "Modular design and compact size for easy maintenance, short down times and less installation space consumption"
  • "Advanced Local & Remote Contact Wear Diagnostic feature for predictive maintenance"

Technical Specifications

Main11
RangeTeSys
Range Of ProductTeSys Giga
Product Or Component TypeContactor
Device Short NameLC1G
Contactor ApplicationPower switching
Utilisation CategoryAC-3; AC-3e; AC-1; AC-5a; AC-5b; AC-6a; AC-6b; DC-1; DC-3; DC-5
Poles Description4P
[Ue] Rated Operational Voltage<= 1000 V AC 50/60 Hz; <= 460 V DC
[Ie] Rated Operational Current500 A (at <60 °C) at <= 440 V AC-3; 700 A (at <40 °C) at <= 1000 V AC-1
[Uc] Control Circuit Voltage200...500 V AC 50/60 Hz; 200...500 V DC
Control Circuit Voltage LimitsOperational: 0.8 Uc Min...1.1 Uc Max (at <60 °C); Drop-out: 0.1 Uc Max...0.45 Uc Min (at <60 °C)
Complementary32
[Uimp] Rated Impulse Withstand Voltage8 kV
Overvoltage CategoryIII
[Ith] Conventional Free Air Thermal Current700 A (at 40 °C)
Rated Breaking Capacity4600 A at 440 V
[Icw] Rated Short-time Withstand Current4.0 kA - 10 s; 2.8 kA - 30 s; 2.2 kA - 1 min; 1.5 kA - 3 min; 1.2 kA - 10 min
Associated Fuse Rating500 A aM at <= 440 V for motor; 400 A aM at <= 690 V for motor; 800 A gG at <= 690 V; 600 A UL Type L at <= 600 V
Average Impedance0.00008 Ohm
[Ui] Rated Insulation Voltage1000 V
Power Dissipation Per Pole40 W AC-1 - Ith 700 A; 20 W AC-3 - Ith 500 A
Compatibility CodeLC1G
Pole Contact Composition4 NO
Auxiliary Contact Composition1 NO + 1 NC
Irms Rated Making Capacity5090 A at 440 V
Coil TechnologyBuilt-in bidirectional peak limiting
Safety Reliability LevelB10d = 400000 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 3000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical Durability8 Mcycles
Inrush Power In VA (50/60 Hz, AC)535 VA
Inrush Power In W (DC)300 W
Hold-in Power Consumption In VA (50/60 Hz, AC)15.4 VA
Hold-in Power Consumption In W (DC)8.6 W
Operating Time40...70 ms closing; 15...50 ms opening
Maximum Operating Rate600 cyc/h AC-3; 600 cyc/h AC-3e; 300 cyc/h AC-1
Connections - TerminalsPower circuit: bar 2 - busbar cross section: 32 x 10 mm; Power circuit: lugs-ring terminals 1 185 mm²; Power circuit: bolted connection; Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable end; Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: push-in 2 0.5…1.0 mm² with cable end; Control circuit: push-in 0.75…2.
Connection Pitch45 mm
Mounting SupportPlate
StandardsEN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; JIS C8201-5-1; UL 60335-1; UL 60335-2-40:Annex JJ
Product CertificationsCB Scheme; CCC; cULus; EAC; CE; UKCA; EU-RO-MR by DNV-GL
Tightening Torque35 N.m
Height290 mm
Width185 mm
Depth226 mm
Net Weight8.9 kg
Environment7
IP Degree Of ProtectionIP2X front face with shrouds conforming to IEC 60529; IP2X front face with shrouds conforming to VDE 0106
Ambient Air Temperature For Operation-25…60 °C
Ambient Air Temperature For Storage-60…80 °C
Mechanical RobustnessVibrations 5…300 Hz 2 gn contactor open; Vibrations 5…300 Hz 4 gn contactor closed; Shocks 10 gn 11 ms contactor open; Shocks 15 gn 11 ms contactor closed
ColourDark grey
Protective TreatmentTH
Permissible Ambient Air Temperature Around The Device-40…70 °C at Uc
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height32 cm
Package 1 Width28 cm
Package 1 Length37 cm
Package 1 Weight11.247 kg
Unit Type Of Package 2P06
Number Of Units In Package 28
Package 2 Height75 cm
Package 2 Width60 cm
Package 2 Length80 cm
Package 2 Weight98.476 kg
Contractual warranty1
Warranty (in Months)18