| Utilisation Category | AC-3; AC-3e; AC-1; AC-4 |
|---|
| Poles Description | 3P |
|---|
| Power Pole Contact Composition | 3 NO |
|---|
| [Ue] Rated Operational Voltage | Power circuit: <= 690 V AC <= 400 Hz; Signalling circuit: <= 690 V AC <= 400 Hz |
|---|
| [Ie] Rated Operational Current | 12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 12 A (at <60 °C) at <= 440 V AC AC-3e for power circuit; 20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit |
|---|
| Control Circuit Type | AC at 50/60 Hz |
|---|
| [Uc] Control Circuit Voltage | 48 V AC 50/60 Hz |
|---|
| Motor Power KW | 3 kW at 220...230 V AC 50/60 Hz AC-3; 5.5 kW at 380...415 V AC 50/60 Hz AC-3; 5.5 kW at 440 V AC 50/60 Hz AC-3; 4 kW at 690 V AC 50/60 Hz AC-3; 3 kW at 220...230 V AC 50/60 Hz AC-3e; 5.5 kW at 380...415 V AC 50/60 Hz AC-3e; 5.5 kW at 440 V AC 50/60 Hz AC-3e; 4 kW at 690 V AC 50/60 Hz AC-3e; 3 kW at 220...230 V AC 50/60 Hz AC-4; 5.5 kW at 380...415 V AC 50/60 Hz AC-4; 5.5 kW at 440 V AC 50/60 Hz AC |
|---|
| Auxiliary Contact Composition | 1 NO |
|---|
| [Uimp] Rated Impulse Withstand Voltage | 8 kV |
|---|
| Overvoltage Category | III |
|---|
| [Ith] Conventional Free Air Thermal Current | 20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit |
|---|
| Irms Rated Making Capacity | 144 A AC for power circuit conforming to IEC 60947; 110 A AC for signalling circuit conforming to IEC 60947 |
|---|
| Rated Breaking Capacity | 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947 |
|---|
| [Icw] Rated Short-time Withstand Current | 115 A 50 °C - 1 s for power circuit; 105 A 50 °C - 5 s for power circuit; 100 A 50 °C - 10 s for power circuit; 75 A 50 °C - 30 s for power circuit; 55 A 50 °C - 1 min for power circuit; 50 A 50 °C - 3 min for power circuit; 25 A 50 °C - >= 15 min for power circuit; 80 A - 1 s for signalling circuit; 90 A - 500 ms for signalling circuit; 110 A - 100 ms for signalling circuit |
|---|
| Associated Fuse Rating | 25 A gG at <= 440 V for power circuit; 25 A aM for power circuit; 10 A gG for signalling circuit conforming to IEC 60947; 10 A gG for signalling circuit conforming to VDE 0660 |
|---|
| Average Impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
|---|
| [Ui] Rated Insulation Voltage | Power circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V conforming to UL 508; Power circuit: 600 V conforming to CSA C22.2 No 14; Signalling circuit: 600 V conforming to CSA C22.2 No 14 |
|---|
| Insulation Resistance | > 10 MOhm for signalling circuit |
|---|
| Inrush Power In VA | 30 VA (at 20 °C) |
|---|
| Hold-in Power Consumption In VA | 4.5 VA (at 20 °C) |
|---|
| Heat Dissipation | 1.3 W |
|---|
| Control Circuit Voltage Limits | Operational: 0.8...1.15 Uc (at <50 °C); Drop-out: >= 0.20 Uc (at <50 °C) |
|---|
| Connections - Terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
|---|
| Maximum Operating Rate | 3600 cyc/h |
|---|
| Coil Technology | Without built-in suppressor module |
|---|
| Auxiliary Contacts Type | type instantaneous 1 NO |
|---|
| Signalling Circuit Frequency | <= 400 Hz |
|---|
| Minimum Switching Current | 5 mA for signalling circuit |
|---|
| Minimum Switching Voltage | 17 V for signalling circuit |
|---|
| Mounting Support | Plate; Rail |
|---|
| Tightening Torque | 0.8…1.3 N.m - on screw clamp terminals Philips No 2; 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm; 0.8…1.3 N.m - on screw clamp terminals pozidriv No 2 |
|---|
| Operating Time | 10...20 ms coil de-energisation and NO opening; 10...20 ms coil energisation and NO closing |
|---|
| Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
|---|
| Non Overlap Distance | 0.5 mm |
|---|
| Mechanical Durability | 10 Mcycles |
|---|
| Electrical Durability | 1.3 Mcycles 12 A AC-3 at Ue <= 440 V; 1.3 Mcycles 12 A AC-3e at Ue <= 440 V; 0.3 Mcycles 20 A AC-1 at Ue <= 690 V; 0.02 Mcycles 72 A AC-4 at Ue <= 440 V |
|---|
| Mechanical Robustness | Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27; Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 600 |
|---|
| Height | 58 mm |
|---|
| Width | 45 mm |
|---|
| Depth | 57 mm |
|---|
| Net Weight | 0.18 kg |
|---|