Schneider LR2K0316 - Thermal relay; NO + NC; screw terminals; 8÷11.5A; -20÷55°C
Schneider

Thermal relay; NO + NC; screw terminals; 8÷11.5A; -20÷55°C

Schneider LR2K0316, Thermal relay; NO + NC; screw terminals; 8÷11.5A; -20÷55°C. Category: TeSys LR2 k. In stock.

Key Specifications

Range
TeSys
Product Name
TeSys LRK
Product Or Component Type
Differential thermal overload relay
Device Short Name
LR2K

Product Description

  • TeSys LRK thermal overload relay, 11.5A/690V, thermal setting range 8-11.5A, tripping class 10A, for protection of 3-phase motors 4kW@400V.
  • Differential device with phase failure and load unbalance detection.
  • It provides a thermal adjustement dial, a manual-automatic reset selector, a test slide switch for simulation of a tripping, reset/stop button, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling.
  • Settings are protected by a transparent cover lockable by sealing.
  • Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1K09-K16.
  • Mounting on DIN rail, separated from the contactor, with use of a terminal block LA7K0064 (to be ordered separately).
  • Multi standards certified (IEC, UL, CSA, CCC, EAC),

Key Features

  • "Tesys K thermal overload relays are designed to protect a.c. circuits and motors against overloads."
  • "Simple to select and install at optimized budget"
  • "The range delivers strong performance for its compact size and promises seamless integration in all applications."
  • "Widely used for industry, infrastructure and building applications."
  • "Designed for simple control systems"

Technical Specifications

Main10
RangeTeSys
Product NameTeSys LRK
Product Or Component TypeDifferential thermal overload relay
Device Short NameLR2K
Relay ApplicationMotor protection
Product CompatibilityLC7K; LP1K; LC1K; LP4K
Network TypeDC; AC
Thermal Overload ClassClass 10A conforming to IEC 60947-4-1
Thermal Protection Adjustment Range8…11.5 A
[Ui] Rated Insulation VoltagePower circuit: 690 V conforming to BS 4941; Power circuit: 690 V conforming to IEC 60947; Power circuit: 750 V conforming to VDE 0110 group C; Power circuit: 600 V conforming to CSA C22.2 No 14
Complementary17
Network Frequency<= 400 Hz
Mounting SupportUnder contactor; Plate, with specific accessories; Rail, with specific accessories
Auxiliary Contact Composition1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current6 A for signalling circuit
[Ue] Rated Operational Voltage<= 690 V for power circuit; 690 V AC AC-15 for signalling circuit; 250 V DC DC-13 for signalling circuit
Associated Fuse Rating6 A gG for signalling circuit conforming to VDE 0660; 6 A gG for signalling circuit conforming to IEC 60947
[Uimp] Rated Impulse Withstand Voltage6 kV
Power Dissipation Per Pole2 W
Phase Failure SensitivityYes conforming to IEC 60947-4-1
Local SignallingTrip indicator (yellow)
Control TypeRed push-button: trip test function; Blue push-button: stop and manual reset; selector switch: manual or automatic reset
Connections - TerminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
Tightening Torque1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2; 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; 1.3 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Height58 mm
Width45 mm
Depth65 mm
Net Weight0.145 kg
Environment10
StandardsIEC 60947; VDE 0660; BS 4941; NF C 63-650
Product CertificationsUL; CSA; UKCA
Protective TreatmentTC conforming to IEC 60068; TC conforming to DIN 50016
IP Degree Of ProtectionIP2X conforming to IEC 60529
Ambient Air Temperature For Operation-20…55 °C without derating conforming to IEC 60947; -30…60 °C with derating conforming to IEC 60947
Ambient Air Temperature For Storage-40…70 °C
Operating Altitude2000 m without derating
Fire Resistance850 °C conforming to IEC 60695-2-1
Flame RetardanceV1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102
Mechanical RobustnessShocks NO contact: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks NC contact: 10 Gn for 11 ms conforming to IEC 60068-2-27; Vibrations NO contact: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations NC contact: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height7.200 cm
Package 1 Width4.800 cm
Package 1 Length8.500 cm
Package 1 Weight157.000 g
Unit Type Of Package 2S02
Number Of Units In Package 241
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight6.855 kg
Logistical informations1
Country Of OriginCZ
Contractual warranty1
Warranty (in Months)18

Documents and Downloads