Schneider LR97D25B - TeSys LR97D Electronic Thermal Overload Relay 5-25A 24VAC/DC
Schneider

LR97D25B - TeSys LR97D Electronic Thermal Overload Relay 5-25A 24VAC/DC

Schneider LR97D25B, TeSys LR97D Electronic Thermal Overload Relay 5-25A 24VAC/DC. Category: TeSys Deca electronic relays. Request a quote for price and lead time.

Key Specifications

Device Short Name
LR97
Product Or Component Type
Electronic overcurrent relay
Device Application
Protection
Product Compatibility
LC1D09...D38

Product Description

TeSys LR97D electronic overcurrent relay, 25A/690V, to be supplied with 24V AC/DC, for protection of motors with a rated current 5-21A. It provides 3 dials to adjust the protection, LOAD (5-25A) for the overcurrent level, O-TIME (0.3-10sec) for the acceptable duration of the overcurrent, D-TIME (0.5-30sec) for the starting duration. In addition, the device trips when the current is higher than 3 x LOAD during more than 0.5sec in steady state and if there is a missing phase during more than 3sec. Settings also include selectors for 1-phase/3-phase motors and manual/automatic reset, the device has a reset button, a test/stop button, 2 LED indicators (Run/Trip), 2 auxiliary contacts 1NO/NC for fault signaling. Settings can be locked by sealing the transparent cover. For direct attachment to the bottom terminals of a 3-phase contactor LC1D09-D38, with screw clamp terminals on bottom, the separate mounting from the contactor is possible using the terminal block LAD7B106 (to be ordered separately). Multi-standards certified (IEC, UL, CSA, CCC, EAC), compliant RoHs/Reach.

Key Features

  • "Settings can be locked by sealing the transparent cover"
  • "It provides 3 dials to adjust the protection"
  • "Compact (45 mm wide) for easy integration into motor starter functions"
  • "Reduces production loss and associated downtime"
  • "Simple setting and signaling features"

Technical Specifications

Main10
Device Short NameLR97
Product Or Component TypeElectronic overcurrent relay
Device ApplicationProtection
Relay ApplicationOverload Imax > Isetting; Locked rotor, mechanical jamming I > 3 x Isetting; Sensitivity to phase failure
Product CompatibilityLC1D09...D38
Network TypeAC; DC
[Us] Rated Supply Voltage24 V AC/DC
Thermal Protection Adjustment Range5…25 A
[Ue] Rated Operational Voltage600 V AC 50/60 Hz for power circuit conforming to CSA; 600 V AC 50/60 Hz for power circuit conforming to UL; 690 V AC 50/60 Hz for power circuit conforming to IEC 60947-4-1
Quantity Per SetSet of 10
Complementary20
Network Frequency50...60 Hz
Mounting SupportDirect on contactor; Rail
Tripping Threshold5...21 A
Surge Withstand6 kV conforming to IEC 61000-4-5
Contacts Type And Composition1 C/O
[Ith] Conventional Free Air Thermal Current3 A for control circuit
Protection TypeBS fuse 3 A - for control circuit; GB2 circuit breaker 3 A - for control circuit; GG fuse 3 A - for control circuit
Maximum Power28 W at 110 V DC conforming to IEC 60947; 28 W at 220 V DC conforming to IEC 60947; 55 W at 24 V DC conforming to IEC 60947; 55 W at 48 V DC conforming to IEC 60947; 140 VA at 48 V AC conforming to IEC 60947; 360 VA at 110 V AC conforming to IEC 60947; 360 VA at 220 V AC conforming to IEC 60947; 70 VA at 24 V AC conforming to IEC 60947
[Ui] Rated Insulation VoltagePower circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL; Power circuit: 690 V conforming to IEC 60947-4-1
[Uimp] Rated Impulse Withstand Voltage6 kV
Phase Failure Sensitivity< 3 s
ResetAutomatic reset 120 s fixed; Electrical by interruption of power supply for minimum 0.1 s; Manual reset
Time Range0.2...10 s - O-time knob; 0.3...10 s - O-time knob; 0.5..30 s - D-time knob
Signalling Function2 LEDs
Connections - TerminalsControl circuit: cable 1 x 1…25 mm²flexible with cable end; Control circuit: cable 1 x 1…25 mm²flexible without cable end; Power circuit: cable 1 x 1…4 mm²flexible with cable end; Power circuit: cable 1 x 1.5…10 mm²flexible without cable end; Power circuit: lug-clamp 1 x 1…4 mm²flexible with cable end; Power circuit: lug-clamp 1 x 1.5…10 mm²flexible without cable end; Control circuit: cable 2 x 1…
Tightening TorqueControl circuit: 0.6...1.2 N.m on lug-clamp; Power circuit: 2 N.m on cable
Height67.5 mm
Width45 mm
Depth67.5 mm
Net Weight0.172 kg
Environment15
StandardsIEC 60947; IEC 60255-6
Product CertificationsUL; GOST; CSA
Protective TreatmentTH conforming to IEC 60068
IP Degree Of ProtectionIP20 conforming to IEC 60529
Ambient Air Temperature For Operation-25…60 °C conforming to IEC 60947-4-1
Ambient Air Temperature For Storage-30…80 °C
Operating Altitude2000 m
Fire Resistance850 °C conforming to IEC 60695-2-1
Shock Resistance15 gn 11 ms conforming to IEC 60068-2-7
Vibration Resistance4 gn conforming to IEC 60068-2-6
Dielectric Strength2 V 50 Hz conforming to IEC 60255-5
Resistance To Electrostatic Discharge6 kV in indirect mode; 8 kV in air
Resistance To Radiated Fields10 V/m level 3
Resistance To Fast Transients2 kV
Disturbance Radiated/conducted10 V conforming to EN 61000-4-6; Class A conforming to EN 55011
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height5.200 cm
Package 1 Width7.200 cm
Package 1 Length7.700 cm
Package 1 Weight176.000 g
Unit Type Of Package 2S02
Number Of Units In Package 224
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight4.680 kg
Logistical informations1
Country Of OriginKR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents2

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support