LR97D38M7 - TeSys LR97D Electronic Thermal Overload Relay 20-38A 220VAC
Schneider LR97D38M7, TeSys LR97D Electronic Thermal Overload Relay 20-38A 220VAC. Category: TeSys Deca electronic relays. Request a quote for price and lead time.
- Reference:LR97D38M7
- Manufacturer / Brand:Schneider
- Availability:On Request / Inquire Stock
- Price:185.85 EUR (Request a quote)
Key Specifications
- Range
- TeSys
- Product Name
- TeSys D
- Device Short Name
- LR97
- Product Or Component Type
- Electronic overcurrent relay
Product Description
TeSys LR97D electronic overcurrent relay, 38A/690V, to be supplied with 200-240V AC, for protection of motors with a rated current 20-34A. It provides 3 dials to adjust the protection, LOAD (20-38A) for the overcurrent level, O-TIME (0.3-10sec) for the acceptable duration of the overcurrent, D-TIME (0.5-30sec) for the starting duration. In addition, the device trips when the current is higher than 3 x LOAD during more than 0.5sec in steady state and if there is a missing phase during more than 3sec. The settings include selectors for 1-phase/3-phase motors and manual/automatic reset, and the device has a reset button, a test/stop button, 2 LED indicators (Run/Trip), 2 auxiliary contacts 1NO/NC for fault signalling. Settings can be locked by sealing the transparent cover. For direct attachement to the bottom terminals of a 3-pole contactor LC1D25-D38, with screw clamp terminals on bottom, the separate mounting from the contactor is possible using the terminal block LAD7B106 (to be ordered separately). Multi-standards certified (IEC, UL, CSA, CCC, EAC), compliant RoHs/Reach.
Key Features
- Settings can be locked by sealing the transparent cover
- It provides 3 dials to adjust the protection
- Compact (45 mm wide) for easy integration into motor starter functions
- Reduces production loss and associated downtime
- Simple setting and signaling features
Technical Specifications
Main11
| Range | TeSys |
|---|---|
| Product Name | TeSys D |
| Device Short Name | LR97 |
| Product Or Component Type | Electronic overcurrent relay |
| Relay Application | Overload Imax > Isetting; Sensitivity to phase failure; Locked rotor, mechanical jamming I > 3 x Isetting |
| Product Compatibility | LC1D25...D38 |
| Network Type | AC |
| [Us] Rated Supply Voltage | 200...240 V AC |
| Thermal Protection Adjustment Range | 20…38 A |
| [Ue] Rated Operational Voltage | 600 V AC 50/60 Hz for power circuit conforming to CSA; 600 V AC 50/60 Hz for power circuit conforming to UL; 690 V AC 50/60 Hz for power circuit conforming to IEC 60947-4-1 |
| Quantity Per Set | Set of 10 |
Complementary20
| Network Frequency | 50...60 Hz |
|---|---|
| Mounting Support | Direct on contactor; Rail |
| Tripping Threshold | 20...34 A |
| Surge Withstand | 6 kV conforming to IEC 61000-4-5 |
| Contacts Type And Composition | 1 C/O |
| [Ith] Conventional Free Air Thermal Current | 3 A for control circuit |
| Protection Type | BS fuse 3 A - for control circuit; GB2 circuit breaker 3 A - for control circuit; GG fuse 3 A - for control circuit |
| Maximum Power | 28 W at 110 V DC conforming to IEC 60947; 28 W at 220 V DC conforming to IEC 60947; 55 W at 24 V DC conforming to IEC 60947; 55 W at 48 V DC conforming to IEC 60947; 140 VA at 48 V AC conforming to IEC 60947; 360 VA at 110 V AC conforming to IEC 60947; 360 VA at 220 V AC conforming to IEC 60947; 70 VA at 24 V AC conforming to IEC 60947 |
| [Ui] Rated Insulation Voltage | Power circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL; Power circuit: 690 V conforming to IEC 60947-4-1 |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV |
| Phase Failure Sensitivity | < 3 s |
| Reset | Automatic reset 120 s fixed; Electrical by interruption of power supply for minimum 0.1 s; Manual reset |
| Time Range | 0.2...10 s - O-time knob; 0.3...10 s - O-time knob; 0.5..30 s - D-time knob |
| Signalling Function | 2 LEDs |
| Connections - Terminals | Control circuit: cable 1 x 1…25 mm²flexible with cable end; Control circuit: cable 1 x 1…25 mm²flexible without cable end; Control circuit: cable 2 x 1…25 mm²flexible without cable end; Control circuit: lug-clamp 1 x 1…25 mm²flexible with cable end; Control circuit: lug-clamp 1 x 1…25 mm²flexible without cable end; Control circuit: lug-clamp 2 x 1…25 mm²flexible with cable end; Control circuit: lu |
| Tightening Torque | Control circuit: 0.6...1.2 N.m on lug-clamp; Power circuit: 2 N.m on cable |
| Height | 67.5 mm |
| Width | 45 mm |
| Depth | 67.5 mm |
| Net Weight | 0.172 kg |
Environment15
| Standards | IEC 60947; IEC 60255-6 |
|---|---|
| Product Certifications | CSA; GOST; UL |
| Protective Treatment | TH conforming to IEC 60068 |
| IP Degree Of Protection | IP20 conforming to IEC 60529 |
| Ambient Air Temperature For Operation | -25…60 °C conforming to IEC 60947-4-1 |
| Ambient Air Temperature For Storage | -30…80 °C |
| Operating Altitude | 2000 m |
| Fire Resistance | 850 °C conforming to IEC 60695-2-1 |
| Shock Resistance | 15 gn 11 ms conforming to IEC 60068-2-7 |
| Vibration Resistance | 4 gn conforming to IEC 60068-2-6 |
| Dielectric Strength | 2 V 50 Hz conforming to IEC 60255-5 |
| Resistance To Electrostatic Discharge | 6 kV in indirect mode; 8 kV in air |
| Resistance To Radiated Fields | 10 V/m level 3 |
| Resistance To Fast Transients | 2 kV |
| Disturbance Radiated/conducted | 10 V conforming to EN 61000-4-6; Class A conforming to EN 55011 |
Packing Units18
| Unit Type Of Package 1 | PCE |
|---|---|
| Number Of Units In Package 1 | 1 |
| Package 1 Height | 5.500 cm |
| Package 1 Width | 7.500 cm |
| Package 1 Length | 8.000 cm |
| Package 1 Weight | 190.000 g |
| Unit Type Of Package 2 | S02 |
| Number Of Units In Package 2 | 24 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.820 kg |
| Unit Type Of Package 3 | P06 |
| Number Of Units In Package 3 | 384 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 85.120 kg |
Logistical informations1
| Country Of Origin | KR |
|---|
Contractual warranty1
| Warranty (in Months) | 18 |
|---|
Documents and Downloads