Schneider
LR9D01 - TeSys LR9D Electronic Thermal Overload Relay 0.1-0.5A
Schneider LR9D01, TeSys LR9D Electronic Thermal Overload Relay 0.1-0.5A. Category: TeSys LR9. Request a quote for price and lead time.
- Reference:LR9D01
- Manufacturer / Brand:Schneider
- Availability:On Request / Inquire Stock
- Price:164.85 EUR (Request a quote)
Key Specifications
- Range
- TeSys
- Product Name
- TeSys LRD
- Device Short Name
- LR9D
- Product Or Component Type
- Electronic thermal overload relay
Product Description
- TeSys LR9D electronic overload relay, 0.5A/690V, thermal setting range 0.1-0.5A, selectable tripping class 5-10-20-30, for protection of 3-phase motors up to 0.12kW@400V.
- Differential device with phase failure and load unbalance detection.
- It provides a thermal adjustement dial, buttons for test, stop and reset as well as manual-automatic reset selector, dipswitches for tripping class selection, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling.
- Settings are protected by a transparent cover lockable by sealing.
- Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D09-D38.
- Mounting on DIN rail or screw fixing, separated from contactor, with use of the terminal block LAD7B205 (to be ordered separately).
- Multi-standards certified (IEC, UL, CSA, CCC),
Key Features
- Easy for selection
- Simple to install
- Trip indication
- Efficiency maintenance
- Class 10 A and 20
Technical Specifications
Main10
| Range | TeSys |
|---|---|
| Product Name | TeSys LRD |
| Device Short Name | LR9D |
| Product Or Component Type | Electronic thermal overload relay |
| Relay Application | Motor protection |
| Product Compatibility | LC1D09; LC1D25; LC1D32; LC1D12; LC1D38; LC1D18 |
| Thermal Overload Class | Class 5…30 |
| Thermal Protection Adjustment Range | 0.1…0.5 A |
| Power Consumption In W | 300 mW |
| Mounting Support | Under contactor; Plate, with specific accessories; Rail, with specific accessories |
Complementary16
| [Ue] Rated Operational Voltage | 690 V for power circuit; 660 V for signalling circuit |
|---|---|
| [Ui] Rated Insulation Voltage | Power circuit: 1000 V; Signalling circuit: 690 V |
| Tripping Threshold | 1.25 In conforming to IEC 60947-4-1 |
| Control Type | Red push-button: stop and manual reset; White 2 microswitches: adjustable trip class; Red knob: automatic reset; White dial: full-load current adjustment |
| Time Range | 1.5...4 min - automatic reset time |
| [Ith] Conventional Free Air Thermal Current | 5 A for signalling circuit |
| Associated Fuse Rating | 5 A gG for signalling circuit; 5 A BS for signalling circuit |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV |
| Phase Failure Sensitivity | Phase difference > 40% 3 s conforming to IEC 60947-4-1 |
| Electromagnetic Compatibility | Surge withstand: 2 kV common mode conforming to IEC 61000-4-5; Resistance to electrostatic discharge: 8 kV conforming to IEC 61000-4-2; Immunity to radiated radio-electrical interference: 10 V/m conforming to IEC 61000-4-3; Immunity to fast transients: 2 kV conforming to IEC 61000-4-4 |
| Connections - Terminals | Control circuit: screw clamp terminals 1 cable 2.5 mm² - cable stiffness: solid or flexible - without cable end; Power circuit: screw clamp terminals 1 cable 16 mm² - cable stiffness: solid or flexible - without cable end |
| Tightening Torque | Control circuit: 0.8 N.m on screw clamp terminals; Power circuit: 3.1 N.m on screw clamp terminals |
| Height | 72.5 mm |
| Width | 45 mm |
| Depth | 79.9 mm |
| Net Weight | 0.18 kg |
Environment8
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; GB/T 14048.4; GB/T 14048.5 |
|---|---|
| Product Certifications | IECEE CB Scheme; UL; CSA; CCC |
| IP Degree Of Protection | IP20 front face conforming to IEC 60529 |
| Ambient Air Temperature For Operation | -25…70 °C conforming to IEC 60255-8 |
| Ambient Air Temperature For Storage | -55…80 °C |
| Operating Altitude | 2000 m without derating |
| Mechanical Robustness | Vibrations 10...150 Hz: 6 Gn conforming to IEC 60068-2-6; Shocks 11 ms: 15 gn conforming to IEC 60068-2-7 |
| Dielectric Strength | 6 kV 50 Hz conforming to IEC 60255-5 |
Packing Units12
| Unit Type Of Package 1 | PCE |
|---|---|
| Number Of Units In Package 1 | 1 |
| Package 1 Height | 5.500 cm |
| Package 1 Width | 7.500 cm |
| Package 1 Length | 9.100 cm |
| Package 1 Weight | 209.000 g |
| Unit Type Of Package 2 | S02 |
| Number Of Units In Package 2 | 30 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.649 kg |
Logistical informations1
| Country Of Origin | CN |
|---|
Contractual warranty1
| Warranty (in Months) | 18 |
|---|
Documents and Downloads
Documents are published by the manufacturer and open in a new tab.