Schneider LRD350 - TeSys LRD Thermal Overload Relay 37-50A Class 10A
Schneider

LRD350 - TeSys LRD Thermal Overload Relay 37-50A Class 10A

Schneider LRD350, TeSys LRD Thermal Overload Relay 37-50A Class 10A. Category: TeSys Deca overload relays. Request a quote for price and lead time.

Key Specifications

Range
TeSys; TeSys Deca
Product Name
TeSys LRD; TeSys Deca
Product Or Component Type
Differential thermal overload relay
Device Short Name
LRD

Product Description

TeSys LRD thermal overload relay, 50A/690V, thermal setting range 37-50A, tripping class 10A, for protection of 3-phase motors 22kW@400V. Differential device with phase failure (loss). It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by EverLink BTR screw terminals , it connects directly to the bottom terminals of 3-pole contactors LC1D40A-D80A. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD96560 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine).

Key Features

  • "Tesys Deca thermal overload relays are designed to protect a.c. circuits and motors against overloads."
  • "New modern look & feel of all machines"
  • "Easier to install and operate with multi-standard screws"
  • "Digital customer experience for technical documents"
  • "Maintenance guide via EcoStruxureTM Facility Expert"

Technical Specifications

Main10
RangeTeSys; TeSys Deca
Product NameTeSys LRD; TeSys Deca
Product Or Component TypeDifferential thermal overload relay
Device Short NameLRD
Relay ApplicationMotor protection
Product CompatibilityLC1D65A; LC1D50A; LC1D40A
Network TypeDC; AC
Thermal Overload ClassClass 10A conforming to IEC 60947-4-1
Thermal Protection Adjustment Range37…50 A
[Ui] Rated Insulation VoltagePower circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL; Power circuit: 690 V conforming to IEC 60947-4-1
Complementary18
Network Frequency0...400 Hz
Mounting SupportPlate, with specific accessories; Rail, with specific accessories; Under contactor
Tripping Threshold1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Auxiliary Contact Composition1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current5 A for signalling circuit
Permissible Current0.95 A at 380 V AC-15 for signalling circuit; 0.06 A at 440 V DC-13 for signalling circuit
[Ue] Rated Operational Voltage690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated Fuse Rating4 A gG for signalling circuit; 4 A BS for signalling circuit
[Uimp] Rated Impulse Withstand Voltage6 kV
Phase Failure SensitivityTripping current 130 % of Ir on two phase, the last one at 0
Control TypeRed push-button: stop; Blue push-button: reset
Temperature Compensation-20…60 °C
Connections - TerminalsControl circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end; Power circuit: EverLink BTR screw connectors 1 cable(s) 1…35 mm² flexible without cable end; Power circuit: EverLink BTR screw connectors 1 ca
Tightening TorqueControl circuit: 1.7 N.m - on screw clamp terminals; Power circuit: 5 N.m - on EverLink BTR screw connectors
Height70 mm
Width55 mm
Depth123 mm
Net Weight0.375 kg
Environment9
Climatic Withstandconforming to IACS E10
IP Degree Of ProtectionIP20 conforming to IEC 60529
Ambient Air Temperature For Operation-20…60 °C without derating conforming to IEC 60947-4-1
Ambient Air Temperature For Storage-60…70 °C
Flame RetardanceV1 conforming to UL 94
Mechanical RobustnessShocks: 15 Gn for 11 ms conforming to IEC 60068-2-7; Vibrations: 4 gn conforming to IEC 60068-2-6
Dielectric Strength1.89 kV at 50 Hz conforming to IEC 60947-1
StandardsEN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; EN 50495
Product CertificationsIEC; UL; CSA; CCC; EAC; DNV-GL; RMRS; EU-RO MR; LROS (Lloyds register of shipping); ATEX INERIS; UKCA
Packing Units18
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height6.400 cm
Package 1 Width10.500 cm
Package 1 Length13.700 cm
Package 1 Weight394.000 g
Unit Type Of Package 2S02
Number Of Units In Package 213
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight5.504 kg
Unit Type Of Package 3P06
Number Of Units In Package 3208
Package 3 Height77.000 cm
Package 3 Width80.000 cm
Package 3 Length60.000 cm
Package 3 Weight96.564 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents3

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support