Schneider LV429753
Schneider

LV429753

Not for sale

Schneider LV429753. Category: Compact-type circuit breakers with magnetic trip (motor protection). Not for sale; no price or quote is offered for this product.

Key Specifications

Series
Compact
Product Name
Compact NSX
Product Or Component Type
Circuit breaker
Device Short Name
Compact NSX100N

Product Description

Schneider LV429753 (LV429753).

Technical Specifications

SeriesCompact
Product NameCompact NSX
Product Or Component TypeCircuit breaker
Device Short NameCompact NSX100N
Device ApplicationMotor
Poles Description3P
Protected Poles Description3t
Network TypeAC
Network Frequency50/60 Hz
[In] Rated Current100 A ( 40 °C ), 100 A ( 65 °C )
[Ui] Rated Insulation Voltage800 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage8 kV
[Ue] Rated Operational Voltage690 V AC 50/60 Hz
Grade CodeN
Breaking Capacity-de 600 V AC 50/60 Hz uyumluluk standardı NEMA AB1, -de 600 V AC 50/60 Hz uyumluluk standardı UL 508, -de 480 V AC 50/60 Hz uyumluluk standardı NEMA AB1, 50 kA -de 480 V AC 50/60 Hz uyumluluk standardı UL 508, 85 kA -de 240 V AC 50/60 Hz uyumluluk standardı UL 508, -de 240 V AC 50/60 Hz uyumluluk standardı NEMA AB1, 50 kA Icu -de 440 V AC 50/60 Hzuyumluluk standardı IEC 60947-2, 10 kA Icu -de 660/
[Ics] Rated Service Breaking CapacityIcs 10 kA 660/690 V AC 50/60 Hz uyumluluk standardı IEC 60947-2, Ics 35 kA 525 V AC 50/60 Hzuyumluluk standardı IEC 60947-2, Ics 36 kA 500 V AC 50/60 Hz uyumluluk standardı IEC 60947-2, Ics 50 kA 380/415 V AC 50/60 Hz uyumluluk standardı IEC 60947-2, Ics 50 kA 440 V AC 50/60 Hzuyumluluk standardı IEC 60947-2, Ics 90 kA 220/240 V AC 50/60 Hz uyumluluk standardı IEC 60947-2
Suitability For IsolationEvetuyumluluk standardı EN 60947-2, Evetuyumluluk standardı IEC 60947-2
Utilization CategoryCategory A
Trip Unit NameMA
Trip Unit TechnologyMagnetic
Trip Unit Protection FunctionsI
Trip Unit Rating12.5 A ( 65 °C )
Protection TypeShort-circuit protection (magnetic)
Pollution Degree3uyumluluk standardı IEC 60664-1
Control TypeToggle
Mounting ModeFixed
Mounting SupportBackplate
Upper ConnectionFront
Downward ConnectionFront
Mechanical Durability50000 cycles
Electrical Durability10000 cycles 690 V In uyumluluk standardı IEC 60947-2, 20000 cycles 690 V In/2 uyumluluk standardı IEC 60947-2, 30000 cycles 440 V In uyumluluk standardı IEC 60947-2, 50000 cycles 440 V In/2 uyumluluk standardı IEC 60947-2
Connection Pitch35 mm
Local SignallingPositive contact indication
Short-time Pick-up Adjustment Type IsdAdjustable 9 settings
[Isd] Short-time Pick-up Adjustment Range6...14 x In
Height161 mm
Width105 mm
Depth86 mm
Product Weight2.05 kg
Electric Shock Protection ClassClass II
StandardsEN 60947-2, IEC 60947-2, NEMA AB1, UL 508
Product CertificationsCSA, UL
IP Degree Of ProtectionIP40uyumluluk standardı IEC 60529
IK Degree Of ProtectionIK07uyumluluk standardı IEC 62262
Ambient Air Temperature For Operation-35...70 °C
Ambient Air Temperature For Storage-55...85 °C
Sustainable Offer StatusGreen Premium product
ROHSCompliant - since 0819 - Schneider Electric declaration of conformity
REACHReference not containing SVHC above the threshold
Product Environmental ProfileAvailable
Circularity ProfileAvailable
WhatsApp Direct Support