Schneider LV430991
Schneider

LV430991

Not for sale

Schneider LV430991. Category: Low-voltage products. Not for sale; no price or quote is offered for this product.

Key Specifications

Series
Compact
Product Name
Compact NSX
Product Or Component Type
Circuit breaker
Device Short Name
Compact NSX160H

Product Description

Schneider LV430991 (LV430991).

Technical Specifications

SeriesCompact
Product NameCompact NSX
Product Or Component TypeCircuit breaker
Device Short NameCompact NSX160H
Device ApplicationMotor
Poles Description3P
Protected Poles Description3t
Network TypeAC
Network Frequency50/60 Hz
[In] Rated Current150 A ( 65 °C ), 160 A ( 40 °C )
[Ui] Rated Insulation Voltage800 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage8 kV
[Ue] Rated Operational Voltage690 V AC 50/60 Hz
Compatibility CodeH
Breaking Capacity10 kA at 600 V AC 50/60 Hz compliance standard UL 508, at 240 V AC 50/60 Hz compliance standard NEMA AB1, at 600 V AC 50/60 Hz compliance standard NEMA AB1, at 480 V AC 50/60 Hz compliance standard NEMA AB1, 65 kA at 480 V AC 50/60 Hz compliance standard UL 508, 85 kA at 240 V AC 50/60 Hz compliance standard UL 508, 50 kA Icu at 500 V AC 50/60 Hz compliance standard IEC 60947-2, 10 kA Icu at
[Ics] Rated Service Breaking CapacityIcs 10 kA 660/690 V AC 50/60 Hz compliance standard IEC 60947-2, Ics 100 kA 220/240 V AC 50/60 Hz compliance standard IEC 60947-2, Ics 35 kA 525 V AC 50/60 Hz compliance standard IEC 60947-2, Ics 50 kA 500 V AC 50/60 Hz compliance standard IEC 60947-2, Ics 65 kA 440 V AC 50/60 Hz compliance standard IEC 60947-2, Ics 70 kA 380/415 V AC 50/60 Hz compliance standard IEC 60947-2
Suitability For IsolationYes compliance standard EN 60947-2, Yes compliance standard IEC 60947-2
Utilization CategoryCategory A
Trip Unit NameMicrologic 2.2 M
Trip Unit TechnologyElectronic
Trip Unit Protection FunctionsLSoI
Trip Unit Rating150 A ( 65 °C )
Protection TypeInstantaneous short-circuit protection, Overload protection (long time), Short-time short-circuit protection
Pollution Degree3 compliance standard IEC 60664-1
Control TypeToggle
Mounting ModeFixed
Mounting SupportBackplate
Top ConnectionFront
Down ConnectionFront
Mechanical Durability40000 cycles
Electrical Durability10000 cycles 440 V In/2 compliance standard IEC 60947-2, 15000 cycles 690 V In/2 compliance standard IEC 60947-2, 20000 cycles 440 V In compliance standard IEC 60947-2, 7500 cycles 690 V In compliance standard IEC 60947-2
Connection Pitch35 mm
Local SignallingLED 95% Ith, LED ready
Motor Trip Class10, 20, 5
Complementary Motor ProtectionPhase unbalance
Long-time Pick-up Adjustment Type LrAdjustable 9 settings
Long-time Pick-up Adjustment Range70...150 A
Long-time Delay Adjustment TypeFixed
[tr] Long-time Delay Adjustment10 s 7.2 x Ir 10, 120 s 1.5 x Ir 5, 20 s 7.2 x Ir 20, 240 s 1.5 x Ir 10, 26 s 6 x Ir 20, 480 s 1.5 x Ir 20, 5 s 7.2 x Ir 5, 13.5 s 6 x Ir 10, 6.5 s 6 x Ir 5
Thermal Memory20 minutes before and after tripping
Short-time Pick-up Adjustment Type IsdAdjustable 9 settings
[Isd] Short-time Pick-up Adjustment Range5...13 x Ir
Short-time Delay Adjustment TypeFixed
Instantaneous Pick-up Adjustment Type LiFixed
Instantaneous Pick-up Adjustment Range2250 A
Height161 mm
Width105 mm
Depth86 mm
Product Weight2.2 kg
Electric Shock Protection ClassClass II
StandardsEN 60947-2, IEC 60947-2, NEMA AB1, UL 508
Product CertificationsCSA, UL
IP Degree Of ProtectionIP40 compliance standard IEC 60529
IK Degree Of ProtectionIK07 compliance standard IEC 62262
Ambient Air Temperature For Operation-35...70 °C
Ambient Air Temperature For Storage-55...85 °C
Sustainable Offer StatusGreen Premium product
ROHSCompliant - since 0819 - Schneider Electric declaration of conformity
REACHReference not containing SVHC above the threshold
Product Environmental ProfileAvailable
WhatsApp Direct Support