Schneider LV432950 - circuit breaker Compact NSX630H, 70 kA at 415 VAC, Micrologic 1.3 M trip unit 500 A, 3 poles 3d
Schneider

circuit breaker Compact NSX630H, 70 kA at 415 VAC, Micrologic 1.3 M trip unit 500 A, 3 poles 3d

Not for sale

Schneider LV432950, circuit breaker Compact NSX630H, 70 kA at 415 VAC, Micrologic 1.3 M trip unit 500 A, 3 poles 3d. Category: ComPact NSX <630A. Not for sale; no price or quote is offered for this product.

Key Specifications

Range
ComPact
Product Name
ComPact NSX
Range Of Product
ComPact NSX400...630
Device Short Name
NSX630H

Product Description

This Compact NSX630H is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for motor protection applications. The breaking capacity (Icu) is 70kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic Micrologic 1.3 M trip unit, with 500A rating. Micrologic 1.3 M trip unit provides an adjustable short time protection and a fixed instantaneous protection. This 3 poles version (140mm x 255mm x 110mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX630H is part of Schneider Electric EcoStruxure Power architecture.

Technical Specifications

Main21
RangeComPact
Product NameComPact NSX
Range Of ProductComPact NSX400...630
Device Short NameNSX630H
Product Or Component TypeCircuit breaker
Device ApplicationMotor
Number Of Poles3P
Protected Poles Description3t
[In] Rated Current500 A at 65 °C
[Ue] Rated Operational Voltage690 V AC 50/60 Hz
Network TypeAC
Network Frequency50/60 Hz
Suitability For IsolationYes conforming to EN/IEC 60947-2
Utilisation CategoryCategory A
[Icu] Rated Ultimate Short-circuit Breaking Capacity85 kA at 240 V AC 50/60 Hz conforming to UL 508; 65 kA at 480 V AC 50/60 Hz conforming to UL 508; 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 20
Performance LevelH 70 kA 415 V AC
Trip Unit NameMicroLogic 1.3 M
Trip Unit TechnologyElectronic
Trip Unit Protection FunctionsI
Control TypeToggle
Circuit Breaker Mounting ModeFixed
Complementary24
[Ui] Rated Insulation Voltage800 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage8 kV
[Ics] Rated Service Short-circuit Breaking Capacity11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical Durability15000 cycles
Electrical Durability2000 cycles at 690 V In; 6000 cycles at 690 V In/2; 4000 cycles at 440 V In; 8000 cycles at 440 V In/2
Mounting SupportBackplate
Upside ConnectionFront
Downside ConnectionFront
Connection Pitch45 mm
Protection TypeI : for short-circuit protection (magnetic)
Trip Unit Rating500 A at 65 °C
Short-time Protection Pick-up Adjustment Type IsdAdjustable 9 settings
[Isd] Short-time Protection Pick-up Adjustment Range3000 A; 6500 A; 5000 A; 6000 A; 3500 A; 5500 A; 4500 A; 4000 A; 2500 A
Short-time Protection Delay Adjustment Type TsdFixed
Instantaneous Protection Pick-up Adjustment Type IiFixed
[Ii] Instantaneous Protection Pick-up Adjustment Range6500 A
Earth-leakage ProtectionWithout
Zone Selective Interlocking ZSIWithout
Number Of Slots For Electrical Auxiliaries6 slot(s)
Local SignallingFlashing LED (green) for ready to operate
Width (W)140 mm
Height (H)255 mm
Depth (D)110 mm
Net Weight6.2 kg
Environment11
StandardsEN/IEC 60947
Product CertificationsCCC; EAC; Marine
Overvoltage CategoryClass II
Electrical Shock Protection ClassClass II
Pollution Degree3 conforming to IEC 60664-1
IP Degree Of ProtectionIP40 conforming to IEC 60529
IK Degree Of ProtectionIK07 conforming to IEC 62262
Ambient Air Temperature For Operation-25…70 °C
Ambient Air Temperature For Storage-50…85 °C
Relative Humidity0…95 %
Operating Altitude0...2000 m without derating; 2000 m...5000 m with derating
Packing Units18
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height15.000 cm
Package 1 Width15.500 cm
Package 1 Length29.000 cm
Package 1 Weight5.716 kg
Unit Type Of Package 2S04
Number Of Units In Package 23
Package 2 Height30.000 cm
Package 2 Width40.000 cm
Package 2 Length60.000 cm
Package 2 Weight17.798 kg
Unit Type Of Package 3P12
Number Of Units In Package 312
Package 3 Height45.000 cm
Package 3 Width80.000 cm
Package 3 Length120.000 cm
Package 3 Weight83.192 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents3

Tags

See products with the same tag in the catalogue.