Schneider
METSEION7400A - ION7400A Class A Certified 98 x 112 x 78.5 mm
Schneider METSEION7400A, ION7400A Class A Certified 98 x 112 x 78.5 mm. Category: PowerLogic™ ION7400 Power Quality Meters. Request a quote for price and lead time.
- Reference:METSEION7400A
- Manufacturer / Brand:Schneider
- Availability:On Request / Inquire Stock
- Price:REQUEST A QUOTE
Key Specifications
- Range
- PowerLogic
- Product Name
- PowerLogic ION7400
- Product Or Component Type
- Power meter
- Device Short Name
- ION7400
Product Description
- The PowerLogic ION7400A comes in a flush mount form factor with integrated display.
- It is designed to bring operational awareness and efficiency for your Utility Feeder applications in substation.
- It unlocks energy transparency and provides actionable data from complex power quality conditions.
- With its modular, flexible, and power ION technology, you can build custom applications for each meter.
- It comes with revenue grade accuracy, power quality reporting, multiple communication ports, and a color graphical display.
- Certified by third party labs for Class 0.2S energy accuracy (IEC62052-11, IEC62053-24, IEC62053-22).
- Certified also for Class A Power Quality (IEC61000-4-30 Ed.3, IEC62586-2).
- Cybersecurity features include secure protocols (HTTPs, sFTP, Secure ION), security event logging, Syslog protocol.
- Ability to enable/disable communication ports and support 50 configurable user account to help manage access.
- With 64MB of memory to support up to 10 data logs (160 channels), 50+ user-definable alarms, waveform captures upto 128 samples/cycle, 1/2 cycle RMS logging.
- The storage can also be used for custom web pages, min/max logs, energy trends, and Time of Use.
- The ability to timestamp events to +/-1ms utilizing time synchronization.
- Time synch method that include PTP (IEEE1588), NTP, IRIG-B, GPS ASCII (RS485) and network time set function.
- 3 digital inputs and one digital output, plus the ability to add up to 4 option modules.
- I/O option modules include 2 relays and 6 digital inputs or 2 analog outputs and 4 analog inputs
- Wide control power range of 90-415 VAC / 110-415 VDC.
- Operating environment of -25 to +70°C; Humidity rating of 5% to 95%; Altitude up to 3000 m.
Key Features
- Fast access to timely, critical information for energy, electrical network, and asset management
- More detailed PQ compliance reporting, and expertlevel power quality and rootcause analytics
- Forecasting to help ensure your electrical system avoid overloads, unbalances or high peak demand
- Ensure energy efficiency and optimized costs by understanding how energy is being consumed
- Perform subbilling or allocate cost to encourage energyefficient behavior, reduce PF penalities
Technical Specifications
Main5
| Range | PowerLogic |
|---|---|
| Product Name | PowerLogic ION7400 |
| Product Or Component Type | Power meter |
| Device Short Name | ION7400 |
| Model Type | Advanced |
Complementary39
| Power Quality Analysis | conforming to EN 50160 compliance report; conforming to IEC 61000-4-30: class A power quality measurement; up to the 63rd harmonic; harmonic distortion; waveform capture; conforming to IEC 61000-4-15 voltage sag and swell detection; conforming to IEC 62586 programmablity (logic and math functions); conforming to IEC 62586 power quality monitoring; conforming to IEC 61000-4-15 flicker; conforming t |
|---|---|
| Device Application | Revenue billing; WAGES metering; Data aggregation; Power monitoring |
| Type Of Measurement | Current per phase, rms; Voltage per phase, rms; Frequency; Active and reactive power total; Apparent power total; Power factor total; Active and reactive power per phase, rms; Apparent power per phase, rms; Power factor per phase, rms; Active and reactive energy; Apparent energy |
| Supply Voltage | 90...415 V AC 45...65 Hz +/- 10 %; 110...415 V DC +/- 10 % |
| Network Frequency | 50 Hz; 60 Hz |
| [In] Rated Current | 10 A; 5 A; 1 A |
| Poles Description | 1P + N; 3P; 3P + N |
| Power Consumption In VA | 18 VA at 415 V AC |
| Display Type | Colour TFT LCD |
| Display Resolution | 320 x 240 pixels QVGA |
| Sampling Rate | 512 samples/cycle |
| Measurement Current | 50…10000 mA |
| Analogue Input Type | Voltage (impedance 5 MOhm); Current (impedance 0.3 mOhm) |
| Measurement Voltage | 57…400 V AC 42...69 Hz between phase and neutral; 100…690 V AC 42...69 Hz between phases |
| Frequency Measurement Range | 42…69 Hz |
| Number Of Inputs | 3 digital 30 V AC; 3 digital 60 V DC |
| Measurement Accuracy | Current +/- 0.1 %; Voltage +/- 0.1 %; Active energy +/- 0.2 % |
| Accuracy Class | Class 0.2S active energy conforming to IEC 62053-22; Class 0.2 active energy conforming to ANSI C12.20; Class 0.2 active power conforming to IEC 61557-12; Class 0.5S reactive energy conforming to IEC 62053-24; Class 0.5 power factor conforming to IEC 61557-12; Class 0.2 voltage conforming to IEC 61557-12; Class 0.2 current conforming to IEC 61557-12; Class 0.2 frequency conforming to IEC 61557-12; |
| Number Of Outputs | 1 pulse |
| Information Displayed | Voltage; Current; Frequency; Power; Energy consumption; Harmonic distortion |
| Communication Port Protocol | Modbus RTU at 115 kbauds - 2-wire; ION at 115 kbauds - 2-wire; DNP3; IEC 61850 at 10/100 Mbit/s; Modbus TCP/IP; Ethernet Modbus TCP/IP daisy chain at 10/100 Mbit/s; RSTP 801.1d 2004; Ansi C12.19; DLMS at 115 kbauds - 2-wire |
| Communication Port Support | ETHERNET; Screw terminal block: RS485; Optical probe: fiber optic; Mini B USB: USB |
| Communication Network Type | IPv6 (internet protocol) |
| Data Recording | Alarm logs; Waveform logs; Sequence of event recording; Event logs; Sag and swell logs; Data logs; Harmonics logs; GPS synchronisation; Time stamping; Trending/forecasting; Min/max of instantaneous values; 64 data recorders |
| Memory Capacity | 512 MB |
| Web Services | Customizable home page; File upload/download via FTP; File upload/download via SFTP; Web server; Alarm notification by e-mail; Viewing of captured waveform (FTP); Viewing of captured waveform (web); HTTPS server |
| Communication Service | DHCP; RSTP support; NTP time synchronization; SMTP e-mail notification; PTP time synchronization |
| Cybersecurity | Syslog protocol support; Robust security logs; Enable/disable communication ports; Password protection; Port hardening |
| Mounting Mode | Flush-mounted |
| Mounting Support | Framework |
| Type Of Installation | Indoor installation |
| Installation Category | III |
| Safety Construction | III400…690 V conforming to IEC 61010-1:ed. 3; III400…690 V conforming to EN 61010-1:ed. 3; III347…600 V conforming to UL 61010-1:ed. 3; III347…600 V conforming to CSA C22.2 No 61010-1:ed. 3 |
| Standards | IEC 62053-22; IEC 62052-11; IEC 62053-24; IEC 61557-12; IEC 61326-1; IEEE 1588; IEC 62586 |
| Product Certifications | CE; CULus; N998 |
| Width | 98 mm |
| Depth | 78.5 mm |
| Height | 112 mm |
| Net Weight | 706 g |
Environment6
| Electromagnetic Compatibility | Electrostatic discharge conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test conforming to IEC 61000-4-4; Surge immunity test conforming to IEC 61000-4-5; Conducted RF disturbances conforming to IEC 61000-4-6; Magnetic field at power frequency conforming to IEC 61000-4-8; Voltage dips an |
|---|---|
| IP Degree Of Protection | IP54 front: conforming to IEC 60529; IP30 body: conforming to IEC 60529 |
| Relative Humidity | 5…95 % |
| Ambient Air Temperature For Operation | -25…70 °C |
| Ambient Air Temperature For Storage | -40…85 °C |
| Operating Altitude | 3000 m |
Packing Units12
| Unit Type Of Package 1 | PCE |
|---|---|
| Number Of Units In Package 1 | 1 |
| Package 1 Height | 14.0 cm |
| Package 1 Width | 14.0 cm |
| Package 1 Length | 18.5 cm |
| Package 1 Weight | 954 g |
| Unit Type Of Package 2 | S03 |
| Number Of Units In Package 2 | 8 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 8.186 kg |
Contractual warranty1
| Warranty (in Months) | 18 |
|---|
Documents and Downloads
Documents are published by the manufacturer and open in a new tab.