Schneider METSEION95030 - ION9000T DIN Rail Mount Without Display High-Speed Transient Capture
Schneider

METSEION95030 - ION9000T DIN Rail Mount Without Display High-Speed Transient Capture

Schneider METSEION95030, ION9000T DIN Rail Mount Without Display High-Speed Transient Capture. Category: NEW! PowerLogic ION9000. Request a quote for price and lead time.

Key Specifications

Range
PowerLogic
Product Or Component Type
Energy and power quality meter
Device Short Name
ION95030
Product Name
PowerLogic ION9000

Product Description

The PowerLogic ION9000 is your 24/7 power quality expert, providing information, not just data. A comprehensive, industry-leading Power Quality Instrument (PQI-A) certified to IEC 62586-1/-2 ensures reliable, precision performance that is perfect for both supply and demand side applications. Third-party lab verified accuracy to Class 0.1S (ANSI C12.20, IEC 62053-22). Highly customizable and modular, ION technology programmability and field installable option modules can satisfy any solution, protecting your investment now and into the future. Providing power quality analysis according to both EN 50160 and IEEE 519, and patented Disturbance Direction Detection, you become a PQ expert and will be able to respond rapidly to system events. Cybersecurity features include secure protocols (HTTPS, SFTP), security event logging, Syslog protocol, ability to enable/disable communication ports, and 50 user configurable accounts. With 2GB of memory to support 50 data logs, 50+ user-definable alarms, disturbance and transient waveforms. 1/2 cycle RMS logging, custom web pages, min/max logs, energy trends, and Time of Use. The ability to timestamp events to +/-1 ms utilizing time synchronization method that include PTP (IEEE1588), NTP, IRIG-B, GPS ASCII (RS485) and network time set function. 8 digital inputs, 4 digital outputs and 2 relay outputs, plus the ability to add up to 4 option modules. Option modules include 2 relays and 6 digital inputs or 2 analog outputs and 4 analog inputs. Ability to capture high-speed impulsive and oscillatory transients as short as 100 ns and record both waveforms and 1/2-cycle RMS concurrently on any event. Voltage inputs of 100 to 690 V between phases; Current inputs of 1 A, 5 A; current class 2, 10, 20 A; Frequency of 20-450 Hz. Wide control power range of 90 to 480 VAC or 110 to 480 VDC. DIN rail mounting or panel mounting (with back to back adapter) transducer, plus 2 display options, further enhance the flexibility and adaptability of the ION9000.

Key Features

  • "Fast access to timely, critical information for energy, electrical network, and asset management"
  • "Help operations personnel avoid downtime by making power quality understandable"
  • "Makes energy and power quality actionable to support your op and sustainability goals"
  • "More detailed PQ compliance reporting, and expertlevel power quality and rootcause analytics"
  • "High Speed Transient Capture unmasks hidden PQ phenomenon"

Technical Specifications

Main6
RangePowerLogic
Product Or Component TypeEnergy and power quality meter
Device Short NameION95030
Product NamePowerLogic ION9000
Device ApplicationPower monitoring; WAGES metering; Net metering; Medium voltage; High voltage
Metering TypeDemand current I1, I2, I3, I4, I5; Peak demand currents; Demand power P, Q, S; Peak demand power PM, QM, SM; Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Complementary39
Power Quality AnalysisEN 50160 compliance checking; conforming to IEEE 519 harmonic limit; conforming to IEC 61000-4-30: class A compliance reporting; conforming to IEEE 519 compliance reporting; waveform capture; total demand distortion; total harmonic distortion; up to the 63rd harmonic; up to the 127th harmonic with software; disturbance direction detection; dip, swell and transient; half cycle data acquisition; hig
Type Of MeasurementVoltage sags and swells; Current sags and swells; Voltage; Current; Frequency; Active and reactive power total; Apparent power total; Active and reactive power per phase; Apparent power per phase; Power factor total; Power factor per phase; Active and reactive energy; Apparent energy; Harmonic distortion (I THD & U THD)
[Us] Rated Supply Voltage90...480 V AC 45...66 Hz +/- 10 %; 90...120 V AC 400 Hz +/- 10 %; 110...480 V DC +/- 10 %
Network Frequency50 Hz; 60 Hz
Ride-through Time100 ms 6 cycles at 60 Hz 120 V AC typical; 400 ms 24 cycles at 60 Hz 240 V AC typical; 1200 ms 72 cycles at 60 Hz 480 V AC typical
[In] Rated Current1 A; 5 A
Type Of Network3P + N + E
Power Consumption In VA38 VA at 480 V AC
Maximum Power Consumption In VA80 VA at 480 V AC
Display TypeWithout display
Sampling Rate1024 samples/cycle
Measurement Current0.01…20 A
Input TypeVoltage (impedance 5 MOhm); External CT (impedance 0.3 mOhm)5 x
Measurement Voltage57…400 V AC 42...69 Hz between phase and neutral; 100…690 V AC 42...69 Hz between phases; 10 kV AC transient
Frequency Measurement Range20…450 Hz
Number Of Inputs8 digital 30 V AC/60 V DC
Measurement AccuracyVoltage +/- 0.1 %; Current +/- 0.1 %
Accuracy ClassClass 0.1S active energy conforming to IEC 62053-22; Class 0.1 active energy conforming to IEC 61557-12; Class 0.1 active energy conforming to ANSI C12.20; Class 0.5S reactive energy conforming to IEC 62053-24; Class 0.1 current conforming to IEC 61557-12; Class 0.1 voltage conforming to IEC 61557-12; Class 0.1 active power conforming to IEC 61557-12; Class 0.5 power factor conforming to IEC 61557
Number Of Outputs4 digital; 2 form C relay
Communication Port ProtocolModbus RTU at 2400...115200 bps - 2-wire; ION at 2400...115200 bps - 2-wire; DNP3 at 2400...115200 bps - 2-wire; Modbus TCP at 10/100 Mbit/s; ION TCP at 10/100 Mbit/s; DNP3 TCP at 10/100 Mbit/s; IEC 61850; Ethernet Modbus TCP/IP daisy chain at 10/100 Mbit/s; DHCP; DNS; DLMS
Communication Port SupportRS485 2 removable screw terminal block
Port Ethernet10/100BASE-TX 2 RJ45
Communication GatewayEthernet/serial
Time Synchronisation ProtocolGPS; IRIG-B; NTP; SNTP; PTP
Data RecordingTime stamping; Min/max of instantaneous values; User-definable data logs; Continuous logging or snapshot; Trending/forecasting; Event logs; Alarm logs; Configuration change; Power outage; User login/logout; Data logs; GPS synchronisation; Sequence of event recording
Memory Capacity2 GB
CybersecuritySyslog protocol support; Robust security logs; Port hardening; Enable/disable communication ports; Hardware metrology lock
Web ServicesViewing of captured waveform; Web page; Pass/fail report for IEEE 519; Pass/fail report for EN 50160; ITIC (CBEMA) curve; SEMI curve; NEMA motor derating curve; Alarm notification by e-mail; TLS 1.2; Push historical data via mail
Ethernet ServiceDHCP client; Device Profile Web Services (DPWS); Rapid Scanning Tree Protocol (RSTP); FTP/HTTP/HTTPS
Communication ServiceCompliant reports; Power quality summary; Energy report; EcoStruxure Power Events Analysis; SMTP e-mail notification; SNMP
Tamperproof Of SettingsProtected by sealable cover
Mounting SupportDIN rail
Electrical Insulation ClassClass III conforming to EN/IEC 62052-11
Isolation VoltageIII400…690 V conforming to EN 61010-1:ed. 3; III347…600 V conforming to UL 61010-1:ed. 3; III347…600 V conforming to CSA C22.2 No 61010-1:ed. 3
Width160 mm
Depth135.3 mm
Height160 mm
Net Weight1.5 kg
Market SegmentData center; Healthcare; Semiconductor; Pharmaceutical; Chemical; Energy; Mining
Environment10
Electromagnetic CompatibilityEMC immunity conforming to IEC 62052-11; EMC immunity conforming to IEC 61326-1; EMC immunity conforming to IEC 61000-6-5; Electrostatic discharge immunity test conforming to IEC 61000-4-2; Immunity to radiated fields conforming to IEC 61000-4-3; Immunity to fast transients conforming to IEC 61000-4-4; Surge immunity test conforming to IEC 61000-4-5; Immunity to conducted disturbances conforming t
IP Degree Of ProtectionIP65 front:; IP30 rear:
Degree Of ProtectionUL type 12, front
Relative Humidity5…95 %
Ambient Air Temperature For Operation-25…70 °C
Ambient Air Temperature For Storage-40…85 °C
Installation CategoryIII
Operating Altitude0...3000 m
StandardsANSI C12.20; ANSI C37.90.1; IEC 61000-4-15; IEC 61000-4-30; IEC 61010-1; IEC 61326-1; IEC 61557-12; IEC 61850; IEC 62052-11; IEC 62052-31; IEC 62053-22; IEC 62053-23; IEC 62053-24; IEC 62586; UL 61010-1
Quality LabelsISO 9001; ISO 14000
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height29.5 cm
Package 1 Width26.4 cm
Package 1 Length37.8 cm
Package 1 Weight2.5 kg
Unit Type Of Package 2P06
Number Of Units In Package 28
Package 2 Height45.0 cm
Package 2 Width80.0 cm
Package 2 Length60.0 cm
Package 2 Weight32.028 kg
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents2

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support