Schneider MVS08H3MW5L
Schneider

MVS08H3MW5L

Not for sale

Schneider MVS08H3MW5L. Category: Open-type circuit breakers with electronic trip unit. Not for sale; no price or quote is offered for this product.

Key Specifications

Product Range
EasyPact MVS
Series
EasyPact
Product Name
MVS08H
Device Short Name
MVS08H

Product Description

Schneider MVS08H3MW5L (MVS08H3MW5L).

Technical Specifications

Product RangeEasyPact MVS
SeriesEasyPact
Product NameMVS08H
Device Short NameMVS08H
Product Or Component TypeCircuit breaker
Device ApplicationDistribution
Poles Description3P
Protected Poles Description3P 3d
Network TypeAC
Unit Rating CodeH
Suitability For IsolationYes conforming to IEC 60947-2
Utilization CategoryCategory B
Trip Unit NameET5S
Trip Unit TechnologyElectronic
Trip Unit Rating800 A (-5...70 °C)
Network Frequency50/60 Hz
Control TypeManual operation
Mounting ModeWithdrawable
Mounting SupportBase plate, Rail
Connection PositionHorizontal, Vertical
Location Of ConnectionRear
[In] Rated Current800 A (40 °C)
[Ui] Rated Insulation Voltage1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage12 kV conforming to IEC 60947-2
[Ue] Rated Operational Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Circuit Breaker CT Value800 A
Breaking Capacity65 kA (Icu) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] Rated Service Breaking Capacity65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical Durability20000 cycles (with maintenance) conforming to IEC 60947-2, 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical Durability6000 cycles (without maintenance), category B at 440 V AC 50/60 Hz, conforming to IEC 60947-2, 4000 cycles (without maintenance), category B at 690 V AC 50/60 Hz, conforming to IEC 60947-2
Connection Pitch115 mm (without spreader)
Contact Position IndicatorYes
[Icm] Rated Short-circuit Making Capacity143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] Rated Short-time Withstand Current65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Trip Unit Protection FunctionsLSI
Protection TypeInstantaneous short-circuit protection, Overload protection (long time), Short time short-circuit protection
Fault IndicationOverload, Short-circuit, Internal fault
Long-time Pick-up Adjustment Type LrAdjustable 9 settings
Long-time Pick-up Adjustment Range0.4...1 x In
Long-time Delay Adjustment TypeAdjustable 9 settings
[tr] Long-time Delay Adjustment0.5...24 s (6 x Ir)
Short-time Pick-up Adjustment Type IsdAdjustable 9 settings
[Isd] Short-time Pick-up Adjustment Range1.5...10 x Ir
Short-time Delay Adjustment TypeAdjustable 5 settings
[tsd] Short-time Delay Adjustment Range100...400 ms
Instantaneous Pick-up Adjustment Type LiAdjustable 9 settings
Instantaneous Pick-up Adjustment Range2...15 x In, Off
Zone Selective Interlocking ZSIWith
Current Sensor Rating Range400/2000 A
Maximum Breaking Time25 ms
Closing Response Time< 70 ms
Height439 mm
Width441 mm
Depth395 mm
Product Weight70 kg
StandardsIEC 60947-2
Product CertificationsCCC, GOST, IEC, CCS
IP Degree Of ProtectionIP40
Pollution Degree4 conforming to IEC 60664-1
Ambient Air Temperature For Operation-5...70 °C