Key Specifications

Product Series
EasyPact MVS
Range
EasyPact
Product Name
MVS16H
Device Short Name
MVS16H

Product Description

Schneider MVS16H3NF5L (MVS16H3NF5L).

Technical Specifications

Product SeriesEasyPact MVS
RangeEasyPact
Product NameMVS16H
Device Short NameMVS16H
Product Or Component TypeCircuit breaker
Device ApplicationDistribution
Poles Description3P
Protected Poles Description3P 3d
Network TypeAC
Breaking Capacity CodeH
Suitability For IsolationYes compliance standard IEC 60947-2
Utilisation CategoryCategory B
Trip Unit NameET5S
Trip Unit TechnologyElectronic
Trip Unit Rating1600 A (-5...70 °C)
Network Frequency50/60 Hz
Control TypeElectrically operated
Mounting ModeFixed
Mounting SupportBase plate, Rail
Connection PositionHorizontal, Vertical
Location Of ConnectionBack
[In] Rated Current1600 A (40 °C)
[Ui] Rated Insulation Voltage1000 V AC 50/60 Hz compliance standard IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage12 kV compliance standard IEC 60947-2
[Ue] Rated Operational Voltage690 V AC 50/60 Hz compliance standard IEC 60947-2
Circuit Breaker CT Value1600 A
Breaking Capacity65 kA (Icu) at 220...440 V AC 50/60 Hz compliance standard IEC 60947-2
[Ics] Rated Service Breaking Capacity65 kA (Ics) at 220...440 V AC 50/60 Hz compliance standard IEC 60947-2, 50 kA (Ics) at 690 V AC 50/60 Hz compliance standard IEC 60947-2
Mechanical Durability20000 cycles (with maintenance) compliance standard IEC 60947-2, 10000 cycles (without maintenance) compliance standard IEC 60947-2
Electrical Durability6000 cycles (without maintenance), category B at 440 V AC 50/60 Hz, compliance standard IEC 60947-2, 4000 cycles (without maintenance), category B at 690 V AC 50/60 Hz, compliance standard IEC 60947-2
Connection Pitch115 mm (without spreader)
Contact Position IndicatorYes
[Icm] Rated Short-circuit Making Capacity143 kA (Icm) at 220...440 V AC 50/60 Hz compliance standard IEC 60947-2
[Icw] Rated Short-time Withstand Current65 kA (1 s) at 220...440 V AC 50/60 Hz compliance standard IEC 60947-2, 50 kA (1 s) at 690 V AC 50/60 Hz compliance standard IEC 60947-2, 36 kA (3 s) at 440/690 V AC 50/60 Hz compliance standard IEC 60947-2
Trip Unit Protection FunctionsLSI
Protection TypeInstantaneous short-circuit protection, Overload protection (long time), Short-time short-circuit protection
Fault IndicationOverload, Short-circuit, Internal fault
Long-time Pick-up Adjustment Type LrAdjustable 9 settings
Long-time Pick-up Adjustment Range0.4...1 x In
Long-time Delay Adjustment TypeAdjustable 9 settings
[tr] Long-time Delay Adjustment0.5...24 s (6 x Ir)
Short-time Pick-up Adjustment Type IsdAdjustable 9 settings
[Isd] Short-time Pick-up Adjustment Range1.5...10 x Ir
Short-time Delay Adjustment TypeAdjustable 5 settings
[tsd] Short-time Delay Adjustment Range100...400 ms
Instantaneous Pick-up Adjustment Type LiAdjustable 9 settings
Instantaneous Pick-up Adjustment Range2...15 x In, OFF
Zone Selective Interlocking ZSIWith
Current Sensor Rating Range400/2000 A
Maximum Breaking Time25 ms
Closing Response Time< 70 ms
Height352 mm
Width422 mm
Depth297 mm
Product Weight40 kg
StandardsIEC 60947-2
Product CertificationsCCC, GOST, IEC, CCS
IP Degree Of ProtectionIP40
Pollution Degree4 compliance standard IEC 60664-1
Ambient Air Temperature For Operation-5...70 °C