Schneider MVS32H3NW5L
Schneider

MVS32H3NW5L

Not for sale

Schneider MVS32H3NW5L. Category: Open-type circuit breakers with electronic trip unit. Not for sale; no price or quote is offered for this product.

Key Specifications

Product Range
EasyPact MVS
Series
EasyPact
Product Name
MVS32H
Device Short Name
MVS32H

Product Description

Schneider MVS32H3NW5L (MVS32H3NW5L).

Technical Specifications

Product RangeEasyPact MVS
SeriesEasyPact
Product NameMVS32H
Device Short NameMVS32H
Product Or Component TypeCircuit breaker
Device ApplicationDistribution
Poles Description3P
Protected Poles Description3P 3d
Network TypeAC
Trip Unit Rating CodeH
Suitability For IsolationYes conforming to IEC 60947-2
Utilisation CategoryCategory B
Trip Unit NameET5S
Trip Unit TechnologyElectronic
Trip Unit Rating3200 A (-5...70 °C)
Network Frequency50/60 Hz
Control TypeElectrically operated
Mounting ModeWithdrawable
Mounting SupportBase plate, Rail
Connection PositionHorizontal, Vertical
Location Of ConnectionRear
[In] Rated Current3200 A (40 °C)
[Ui] Rated Insulation Voltage1000 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] Rated Impulse Withstand Voltage12 kV conforming to IEC 60947-2
[Ue] Rated Operational Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Circuit Breaker CT Rating3200 A
Breaking Capacity65 kA (Icu) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] Rated Service Breaking Capacity65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical Durability20000 cycles (with maintenance) conforming to IEC 60947-2, 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical Durability5000 cycles (without maintenance), category B at 440 V AC 50/60 Hz, conforming to IEC 60947-2, 2500 cycles (without maintenance), category B at 690 V AC 50/60 Hz, conforming to IEC 60947-2
Connection Pitch115 mm (without spreader)
Contact Position IndicatorYes
[Icm] Rated Short-circuit Making Capacity143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] Rated Short-time Withstand Current65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2, 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2, 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Trip Unit Protection FunctionsLSI
Protection TypeInstantaneous short-circuit protection, Overload protection (long time), Short-time short-circuit protection
Fault IndicationOverload, Short-circuit, Internal fault
Long-time Pick-up Adjustment Type LrAdjustable 9 settings
Long-time Pick-up Adjustment Range0.4...1 x In
Long-time Delay Adjustment TypeAdjustable 9 settings
[tr] Long-time Delay Adjustment0.5...24 s (6 x Ir)
Short-time Pick-up Adjustment Type IsdAdjustable 9 settings
[Isd] Short-time Pick-up Adjustment Range1.5...10 x Ir
Short-time Delay Adjustment TypeAdjustable 5 settings
[tsd] Short-time Delay Adjustment Range100...400 ms
Instantaneous Pick-up Adjustment Type LiAdjustable 9 settings
Instantaneous Pick-up Adjustment Range2...15 x In, Off
Zone Selective Interlocking ZSIWith
Current Sensor Rating Range1000/4000 A
Maximum Breaking Time25 ms
Closing Response Time< 70 ms
Height439 mm
Width441 mm
Depth395 mm
Product Weight90 kg
StandardsIEC 60947-2
Product CertificationsCCC, GOST, IEC, CCS
IP Degree Of ProtectionIP40
Pollution Degree4 conforming to IEC 60664-1
Ambient Air Temperature For Operation-5...70 °C