Schneider NSYCVF300M24DPF - Fan + Filter 300m3/h 24VDC IP54 - 223x223
Schneider

NSYCVF300M24DPF - Fan + Filter 300m3/h 24VDC IP54 - 223x223

Schneider NSYCVF300M24DPF, Fan + Filter 300m3/h 24VDC IP54 - 223x223. Category: ClimaSys CV. Request a quote for price and lead time.

Key Specifications

Range
ClimaSys
Product Name
ClimaSys CV
Product Or Component Type
Fan
Type Of Filter
Standard

Product Description

ClimaSys CV Axial motor ventilator. 24V DC. 13 W 50 Hz. Free flow rate with standard filter of 262 m3/h at 50 Hz. 268 x 248 x 104 mm. Cut-out dimensions of 223 x 223 mm. Outlet grille injected thermoplastic (ASA PC), Grey RAL 7035. Connections terminals by faston connector. 2 protective grille on the front and rear surfaces. Protection IP54.

Key Features

  • "Efficiently cools with a power range of 13 W."
  • "Made of durable injected thermoplastic (ASA PC)."
  • "Comes with a filter, outlet grille, and protective grilles for safety."
  • "Can operate in temperatures from -10 to 70°C."
  • "Provides a free flow rate of 262 m3/h."

Technical Specifications

Main8
RangeClimaSys
Product NameClimaSys CV
Product Or Component TypeFan
Type Of FilterStandard
Flow RateFree flow rate with standard filter: 262 m3/h
[Us] Rated Supply Voltage12...30 V
Input Voltage24 V DC
CertificationCSA
Complementary18
Absorbed Power13 W
[In] Rated Current0.53 A
Noise Level < At53…57 dB
Bearing TypeBall
HeightExternal: 268 mm
WidthExternal: 248 mm
DepthExternal : 103.4 mm
Cut-out Dimensions223 x 223 mm
Net Weight1.1 kg
MaterialOutlet grille: injected thermoplastic (ASA PC)
ColourOutlet grille: grey (RAL 7035)
Ambient Air Temperature For Operation-10…70 °C
Ambient Air Temperature For Storage-40…70 °C
Maximum Pressure158 Pa flow rate 0 m³/h
Connections - TerminalsCable
IP Degree Of ProtectionIP54
Device Composition1 axial motor; 2 protective grille: on the front and rear surfaces; 1 filter: front of axial motor; 1 outlet grille: front; 1 cut-out template; 1 power cord
Condition Of UseOverfrequent filter replacement should be avoided; Outside temperature must be 5 °C lower than inside temperature; Flow rates depends on the work point, see ProClima software; Filter must be cleaned and replaced regularly; Surrounding environment must be relatively clean
Packing Units18
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height18.500 cm
Package 1 Width25.000 cm
Package 1 Length27.500 cm
Package 1 Weight1.360 kg
Unit Type Of Package 2CAR
Number Of Units In Package 24
Package 2 Height28.000 cm
Package 2 Width41.000 cm
Package 2 Length59.000 cm
Package 2 Weight6.460 kg
Unit Type Of Package 3P12
Number Of Units In Package 364
Package 3 Height125.000 cm
Package 3 Width80.000 cm
Package 3 Length120.000 cm
Package 3 Weight114.000 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents3

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support