Schneider NSYCVF38M230PF - Fan + Filter 38m3/h 230V IP54 - 92x92
Schneider

NSYCVF38M230PF - Fan + Filter 38m3/h 230V IP54 - 92x92

Schneider NSYCVF38M230PF, Fan + Filter 38m3/h 230V IP54 - 92x92. Category: ClimaSys CV. Request a quote for price and lead time.

Key Specifications

Range
ClimaSys
Product Name
ClimaSys CV
Product Or Component Type
Fan
Type Of Filter
Standard

Product Description

  • This product is a forced air ventilation fan that is designed to provide reliable and efficient cooling
  • It is made of injected thermoplastic (ASA PC) and is available in grey (RAL 7035) color
  • The fan has a ball bearing type and a maximum pressure of 29 Pa
  • It has a power range of 4,5 W 50 Hz and 4,8 W 60 Hz, and a free flow rate of 38 m3/h at 50 Hz and 39 m3/h at 60 Hz
  • It can be used in ambient air temperatures ranging from -10 to 70°C
  • It has a power cable and comes with a filter, an outlet grille, and two protective grilles on the front and rear surfaces
  • It has an IP54 degree of protection and a noise level of 40-41 dB
  • The cut-out dimensions of the fan are 92 x 92 mm
  • This fan also comes with an anti-insect filter included
  • Protection IP54.

Key Features

  • Free flow rate with standard filter of 38 m3/h at 50 Hz and 39 m3/h at 60 Hz.
  • 4.5 W 50 Hz, 4.8 W 60 Hz.
  • Connections terminals by cable.
  • Cut-out dimensions of 92 x 92 mm.
  • Ext Dimensions : 137 x 117 x 49 mm.

Technical Specifications

Main7
RangeClimaSys
Product NameClimaSys CV
Product Or Component TypeFan
Type Of FilterStandard
Flow RateFree flow rate with standard filter: 38 m3/h at 50 Hz; Free flow rate with standard filter: 39 m3/h at 60 Hz
[Us] Rated Supply Voltage150...250 V
Input Voltage230 V 50/60 Hz
Complementary18
Absorbed Power4.5 W 50 Hz; 4.8 W 60 Hz
[In] Rated Current0.16 A 50 Hz; 0.17 A 60 Hz
Noise Level < At40…41 dB
Bearing TypeBall
HeightExternal: 137 mm
WidthExternal: 117 mm
DepthExternal : 49 mm
Cut-out Dimensions92 x 92 mm
Net Weight0.22 kg
MaterialOutlet grille: injected thermoplastic (ASA PC)
ColourOutlet grille: grey (RAL 7035)
Ambient Air Temperature For Operation-10…70 °C
Ambient Air Temperature For Storage-40…70 °C
Maximum Pressure29 Pa flow rate 0 m³/h
Connections - TerminalsCable
IP Degree Of ProtectionIP54
Device Composition1 axial motor; 2 protective grille: on the front and rear surfaces; 1 filter: front of axial motor; 1 outlet grille: front; 1 cut-out template
Condition Of UseOutside temperature must be 5 °C lower than inside temperature; Flow rates depends on the work point, see ProClima software; Surrounding environment must be relatively clean; Filter must be cleaned and replaced regularly; Overfrequent filter replacement should be avoided
Packing Units18
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height7.000 cm
Package 1 Width12.000 cm
Package 1 Length14.500 cm
Package 1 Weight280.000 g
Unit Type Of Package 2CAR
Number Of Units In Package 234
Package 2 Height60.000 cm
Package 2 Width40.000 cm
Package 2 Length28.000 cm
Package 2 Weight10.940 kg
Unit Type Of Package 3P12
Number Of Units In Package 3272
Package 3 Height68.000 cm
Package 3 Width80.000 cm
Package 3 Length120.000 cm
Package 3 Weight100.000 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents4

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support