Schneider
NSYCVF560M230PF - Fan + Filter 560m3/h 230V IP54 - 291x291
Schneider NSYCVF560M230PF, Fan + Filter 560m3/h 230V IP54 - 291x291. Category: ClimaSys CV. Request a quote for price and lead time.
- Reference:NSYCVF560M230PF
- Manufacturer / Brand:Schneider
- Availability:On Request / Inquire Stock
- Price:437.00 EUR (Request a quote)
Key Specifications
- Range
- ClimaSys
- Product Name
- ClimaSys CV
- Product Or Component Type
- Fan
- Range Compatibility
- Prisma P; Prisma G
Product Description
ClimaSys CV Axial motor ventilator. 230V 50Hz or 60Hz. 68 W 50 Hz, 85 W 60 Hz. Free flow rate of 550 m3/h at 50 Hz and 60 Hz. 336 x 316 x 161 mm. Cut-out dimensions of 291 x 291 mm. Outlet grille injected thermoplastic (ASA PC), Grey RAL 7035. Connections terminals by cable. 2 protective grille on the front and rear surfaces. Protection IP54.
Key Features
- "Free flow rate with standard filter of 560 m3/h at 50 Hz and 586 m3/h at 60 Hz."
- "68 W 50 Hz, 85 W 60 Hz."
- "Connections terminals by cable."
- "Cut-out dimensions of 291 x 291 mm."
- "Ext Dimensions : 336 x 316 x 162 mm."
Technical Specifications
Main9
| Range | ClimaSys |
|---|---|
| Product Name | ClimaSys CV |
| Product Or Component Type | Fan |
| Range Compatibility | Prisma P; Prisma G |
| Type Of Filter | Standard |
| Flow Rate | Free flow rate with standard filter: 562 m3/h at 50 Hz; Free flow rate with standard filter: 586 m3/h at 60 Hz |
| [Us] Rated Supply Voltage | 207...244 V |
| Input Voltage | 230 V 50/60 Hz |
| Certification | CSA |
Complementary18
| Absorbed Power | 64 W 50 Hz; 80 W 60 Hz |
|---|---|
| [In] Rated Current | 0.29 A 50 Hz; 0.35 A 60 Hz |
| Noise Level < At | 59 dB |
| Bearing Type | Ball |
| Height | External: 336 mm |
| Width | External: 316 mm |
| Depth | External : 161 mm |
| Cut-out Dimensions | 291 x 291 mm |
| Net Weight | 3.2 kg |
| Material | Outlet grille: injected thermoplastic (ASA PC) |
| Colour | Outlet grille: grey (RAL 7035) |
| Ambient Air Temperature For Operation | -15…60 °C |
| Ambient Air Temperature For Storage | -40…70 °C |
| Maximum Pressure | 140 Pa flow rate 0 m³/h |
| Connections - Terminals | Terminal block |
| IP Degree Of Protection | IP54 |
| Device Composition | 1 axial motor; 2 protective grille: on the front and rear surfaces; 1 filter: front of axial motor; 1 outlet grille: front; 1 cut-out template |
| Condition Of Use | Filter must be cleaned and replaced regularly; Surrounding environment must be relatively clean; Outside temperature must be 5 °C lower than inside temperature; Overfrequent filter replacement should be avoided; Flow rates depends on the work point, see ProClima software |
Packing Units12
| Unit Type Of Package 1 | PCE |
|---|---|
| Number Of Units In Package 1 | 1 |
| Package 1 Height | 23.000 cm |
| Package 1 Width | 32.000 cm |
| Package 1 Length | 34.000 cm |
| Package 1 Weight | 3.554 kg |
| Unit Type Of Package 2 | P12 |
| Number Of Units In Package 2 | 24 |
| Package 2 Height | 119.000 cm |
| Package 2 Width | 80.000 cm |
| Package 2 Length | 120.000 cm |
| Package 2 Weight | 94.000 kg |
Logistical informations1
| Country Of Origin | FR |
|---|
Contractual warranty1
| Warranty (in Months) | 18 |
|---|
Documents and Downloads