Schneider NSYCVF85M230PF - Fan + Filter 85m3/h 230V IP54 - 125x125
Schneider

NSYCVF85M230PF - Fan + Filter 85m3/h 230V IP54 - 125x125

Schneider NSYCVF85M230PF, Fan + Filter 85m3/h 230V IP54 - 125x125. Category: ClimaSys CV. Request a quote for price and lead time.

Key Specifications

Range
ClimaSys
Product Name
ClimaSys CV
Product Or Component Type
Fan
Type Of Filter
Standard

Product Description

ClimaSys CV Axial motor ventilator. 230V 50Hz or 60Hz. 17 W 50 Hz, 15 W 60 Hz. Free flow rate with standard filter of 85 m3/h at 50 Hz and 98 m3/h at 60 Hz. 170 x 150 x 62 mm. Cut-out dimensions of 125 x 125 mm. Outlet grille injected thermoplastic (ASA PC), Grey RAL 7035. Connections terminals by cable. 2 protective grille on the front and rear surfaces. Protection IP54.

Key Features

  • "Free flow rate with standard filter of 85 m3/h at 50 Hz and 98 m3/h at 60 Hz."
  • "17 W 50 Hz, 15 W 60 Hz."
  • "Connections terminals by cable."
  • "Cut-out dimensions of 125 x 125 mm."
  • "Ext Dimensions : 170 x 150 x 62 mm."

Technical Specifications

Main8
RangeClimaSys
Product NameClimaSys CV
Product Or Component TypeFan
Type Of FilterStandard
Flow RateFree flow rate with standard filter: 85 m3/h at 50 Hz; Free flow rate with standard filter: 98 m3/h at 60 Hz
[Us] Rated Supply Voltage175...253 V
Input Voltage230 V 50/60 Hz
CertificationCSA
Complementary18
Absorbed Power15 W 60 Hz; 17 W 50 Hz
[In] Rated Current0.121 A 50 Hz; 0.097 A 60 Hz
Noise Level < At46…49 dB
Bearing TypeBall
HeightExternal: 170 mm
WidthExternal: 150 mm
DepthExternal : 62 mm
Cut-out Dimensions125 x 125 mm
Net Weight0.78 kg
MaterialOutlet grille: injected thermoplastic (ASA PC)
ColourOutlet grille: grey (RAL 7035)
Ambient Air Temperature For Operation-20…60 °C
Ambient Air Temperature For Storage-40…70 °C
Maximum Pressure50 Pa flow rate 0 m³/h
Connections - TerminalsFaston connector
IP Degree Of ProtectionIP54
Device Composition1 axial motor; 2 protective grille: on the front and rear surfaces; 1 filter: front of axial motor; 1 outlet grille: front; 1 cut-out template; 1 power cord
Condition Of UseFlow rates depends on the work point, see ProClima software; Surrounding environment must be relatively clean; Filter must be cleaned and replaced regularly; Overfrequent filter replacement should be avoided; Outside temperature must be 5 °C lower than inside temperature
Packing Units18
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height8.000 cm
Package 1 Width15.500 cm
Package 1 Length18.000 cm
Package 1 Weight930.000 g
Unit Type Of Package 2CAR
Number Of Units In Package 210
Package 2 Height21.000 cm
Package 2 Width33.000 cm
Package 2 Length43.000 cm
Package 2 Weight9.526 kg
Unit Type Of Package 3P12
Number Of Units In Package 3240
Package 3 Height95.000 cm
Package 3 Width80.000 cm
Package 3 Length120.000 cm
Package 3 Weight241.000 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents4

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support