Schneider TPRST065, TeSys Island Starter 65A/30kW. Category: TeSys island. Request a quote for price and lead time.
- Reference:TPRST065
- Manufacturer / Brand:Schneider
- Availability:On Request / Inquire Stock
- Price:652.86 EUR (Request a quote)
Key Specifications
- Range
- TeSys
- Product Name
- TeSys island
- Device Short Name
- TPRST
- Product Or Component Type
- Motor starter
Product Description
TeSys island direct starter, 3 poles, 65A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 65A and motors up to 30kW@400V / 40hp@480V. It provides motor protection functions including thermal overload (setting 3.35-65A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of switching cycles, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC).
Key Features
- Upstream voltage presence detection
- Power and energy monitoring when connected with TPRVM voltage module
- Manages motors and other electrical loads up to 80 A (AC-3) / 37 kW/40 hp
- All adjustments and setting are digitized, no mechanical dials or dip switches
- Embedded Cybersecurity (Achilles Level 2)
Technical Specifications
Main29
| Range | TeSys |
|---|---|
| Product Name | TeSys island |
| Device Short Name | TPRST |
| Product Or Component Type | Motor starter |
| Motor Starter Type | Direct on line |
| Device Presentation | Direct starter connected to an automation controller through a bus coupler; Operational only when connected to a bus coupler |
| Function Available | Upstream voltage presence detection; Electrical line and load protection; Power and energy monitoring when connected with TPRVM voltage module |
| Product Compatibility | TPRBC bus coupler; TPRVM voltage interface module |
| Poles Description | 3P (3 NO) |
| Utilisation Category | AC-1; AC-2; AC-3; AC-4; AC-3e |
| Motor Power KW | 18.5 kW at 230 V 50 Hz (AC-3); 30 kW at 380...415 V 50 Hz (AC-3); 30 kW at 440 V 50 Hz (AC-3); 37 kW at 500 V 50 Hz (AC-3); 37 kW at 690 V 50 Hz (AC-3) |
| Motor Power HP (UL / CSA) | 5 hp at 120 V AC 60 Hz for 1 phase motors; 10 hp at 240 V AC 60 Hz for 1 phase motors; 20 hp at 208 V AC 60 Hz for 3 phases motors; 20 hp at 240 V AC 60 Hz for 3 phases motors; 40 hp at 480 V AC 60 Hz for 3 phases motors; 50 hp at 600 V AC 60 Hz for 3 phases motors |
| [Ue] Rated Operational Voltage | <= 690 V AC 47...63 Hz |
| [Ie] Rated Operational Current | 65 A (at <50 °C) at <= 440 V AC-3; 80 A (at <50 °C) at <= 440 V AC-1 |
| [Ith] Conventional Free Air Thermal Current | 80 A (at 50 °C) |
| [Ui] Rated Insulation Voltage | 690 V conforming to IEC 60947-4-1; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1 |
| [Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947-1 |
| Overvoltage Category | III |
| Thermal Protection Adjustment Range | 3.35…65 A |
| Thermal Overload Class | Class 5…30 |
| Reset | Remotely or automatically |
| Irms Rated Making Capacity | 1000 A at 440 V conforming to IEC 60947 |
| Rated Breaking Capacity | 1000 A at 440 V conforming to IEC 60947 |
| [Icw] Rated Short-time Withstand Current | 900 A 40 °C - 1 s; 520 A 40 °C - 10 s; 260 A 40 °C - 1 min; 110 A 40 °C - 10 min |
| Average Impedance | 1.5 mOhm - Ith 80 A 50 Hz |
| Power Dissipation Per Pole | 6.3 W AC-3 - Ith 65 A; 9.6 W AC-1 - Ith 80 A |
| [Uc] Control Circuit Voltage | 24 V DC supplied by the bus coupler |
| Current Consumption | 80 mA contactor sealed; 500 mA contactor closing |
| Power Dissipation In W | 20.8 W at Ie AC-3 |
Complementary17
| Mechanical Durability | 6 Mcycles |
|---|---|
| Electrical Durability | 1.4 Mcycles 65 A AC-3 at Ue 440 V; 0.5 Mcycles 80 A AC-1 at Ue 440 V |
| Maximum Operating Rate | 3600 cyc/mn AC-3 |
| Operating Time | < 80 ms closing; < 80 ms opening |
| Safety Performance Level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Protection Type | Thermal overload protection; Motor overheat; Overcurrent; Undercurrent; Jam; Long start; Stall; Rapid cycle lockout; Phase sequence; Rapid restart lockout; Phase reversal; Phase loss; Phase unbalance; Ground current |
| Monitoring Type | Time device ON; Time device switch ON; Number of faults; Number of switching cycles; Number of device power cycles; Average current Iavg; Average voltage Vavg; Max current Imax; Max voltage Vmax; Active and reactive power with voltage module; Active and reactive energy with voltage module; True power factor with voltage module |
| Local Signalling | 1 LED (green/red) for DS (device status); 1 LED (green/red) for LS (load status) |
| Standards | EN/IEC 60947-1; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1 |
| Product Certifications | CSA; UL; EAC; CCC |
| Mounting Mode | Horizontal and vertical (35 mm symmetrical DIN rail) |
| Connections - Terminals | EverLink BTR screw connectors 1 cable(s) 1…35 mm² (16 AWG...2 AWG) rigid; EverLink BTR screw connectors 2 cable(s) 1…25 mm² (16 AWG...4 AWG) rigid; EverLink BTR screw connectors 1 cable(s) 1…35 mm² (16 AWG...2 AWG) flexible without cable end; EverLink BTR screw connectors 2 cable(s) 1…25 mm² (16 AWG...4 AWG) flexible without cable end; EverLink BTR screw connectors 1 cable(s) 1…35 mm² (16 AWG...2 |
| Tightening Torque | 5 N.m - cable 1…25 mm² hexagonal 4 mm; 8 N.m - cable 25…35 mm² hexagonal 4 mm |
| Width | 55 mm |
| Height | 167 mm |
| Depth | 125 mm |
| Net Weight | 1.248 kg |
Environment11
| Ambient Air Temperature For Storage | -25…70 °C |
|---|---|
| Ambient Air Temperature For Operation | -10…50 °C without derating; 50…60 °C with current derating |
| Relative Humidity | 5…95 % |
| Operating Altitude | 0...2000 m without derating |
| IP Degree Of Protection | IP20 |
| Pollution Degree | 2 |
| Protective Treatment | TC |
| Fire Resistance | 960 °C conforming to UL 94; 850 °C conforming to IEC 60695-2-1; 650 °C conforming to IEC 60695-2-12 |
| Shock Resistance | 15 gn (duration = 11 ms) conforming to IEC 60068-2-27 |
| Vibration Resistance | 1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 |
| Electromagnetic Compatibility | Electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2; Radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3; Fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4; Surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5; Surge immunity test (common mode), level 4, 4 kV, |
Packing Units12
| Unit Type Of Package 1 | PCE |
|---|---|
| Number Of Units In Package 1 | 1 |
| Package 1 Height | 8.000 cm |
| Package 1 Width | 15.000 cm |
| Package 1 Length | 19.500 cm |
| Package 1 Weight | 1.354 kg |
| Unit Type Of Package 2 | S03 |
| Number Of Units In Package 2 | 8 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 11.311 kg |
Logistical informations1
| Country Of Origin | FR |
|---|
Contractual warranty1
| Warranty (in Months) | 18 |
|---|