Schneider
red flush complete illum pushbutton Ø16 latching 1NC 12...24V

Not for sale
Schneider XB6AF4B2B, red flush complete illum pushbutton Ø16 latching 1NC 12...24V. Category: Harmony XB6. Not for sale; no price or quote is offered for this product.
- Reference:XB6AF4B2B
- Manufacturer / Brand:Schneider
Key Specifications
- Range Of Product
- Harmony XB6
- Product Or Component Type
- Complete illuminated push-button
- Device Short Name
- XB6
- Bezel Material
- Plastic
Product Description
Red Flush Complete Pushbutton Ø16 Latching 1NC 12...24V
Technical Specifications
Main15
| Range Of Product | Harmony XB6 |
|---|---|
| Product Or Component Type | Complete illuminated push-button |
| Device Short Name | XB6 |
| Bezel Material | Plastic |
| Mounting Diameter | 16 mm |
| Sale Per Indivisible Quantity | 1 |
| Shape Of Signaling Unit Head | Round |
| Type Of Operator | latching |
| Operator Profile | Red flush, unmarked |
| Contacts Type And Composition | 1 NC |
| Contact Operation | Slow-break |
| Connections - Terminals | Faston connectors, connection size: 2.8 x 0.5 mm |
| Light Source | LED |
| Bulb Base | Integral LED |
| [Us] Rated Supply Voltage | 12...24 V AC/DC |
Complementary20
| Height | 18 mm |
|---|---|
| Width | 18 mm |
| Depth | 57 mm |
| Terminals Description ISO N°1 | (21-22)NC |
| Net Weight | 0.022 kg |
| Operating Position | Any position |
| Positive Opening | With conforming to EN/IEC 60947-5-1 appendix K |
| Operating Travel | 2 mm (NC changing electrical state); 3.5 mm (total travel) |
| Operating Force | 4.5 N NC changing electrical state |
| Contacts Material | Silver alloy (Ag/Ni) |
| Short-circuit Protection | 6 A cartridge fuse type gG |
| [Ui] Rated Insulation Voltage | 250 V (pollution degree 3) conforming to EN/IEC 60947-1 |
| [Uimp] Rated Impulse Withstand Voltage | 4 kV conforming to EN/IEC 60947-1 |
| [Ie] Rated Operational Current | 3 A at 120 V, AC-15, B300 conforming to EN/IEC 60947-5-1; 1.5 A at 240 V, AC-15, B300 conforming to EN/IEC 60947-5-1; 0.1 A at 250 V, DC-13, R300 conforming to EN/IEC 60947-5-1; 0.22 A at 125 V, DC-13, R300 conforming to EN/IEC 60947-5-1 |
| Electrical Durability | 1000000 cycles, AC-15 at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C; 1000000 cycles, DC-13 at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C |
| Electrical Reliability | Λ = 10exp(-8) at 5 V and 1 mA with confidence level of 90 % conforming to IEC 60947-5-4 |
| Signalling Type | Steady |
| Supply Voltage Limits | 6…30 V AC/DC |
| Current Consumption | 15 mA |
| Surge Withstand | 1 kV direct contact conforming to IEC 61000-4-5; 2 kV in free air conforming to IEC 61000-4-5 |
Environment14
| Protective Treatment | TC |
|---|---|
| Ambient Air Temperature For Storage | -40…70 °C |
| Ambient Air Temperature For Operation | -25…70 °C |
| Electrical Shock Protection Class | Class II conforming to IEC 61140 |
| IP Degree Of Protection | IP65 conforming to IEC 60529 |
| NEMA Degree Of Protection | NEMA 13 conforming to UL 50; NEMA 4 conforming to UL 50; NEMA 4X conforming to UL 50; NEMA 13 conforming to CSA C22.2 No 94; NEMA 4 conforming to CSA C22.2 No 94; NEMA 4X conforming to CSA C22.2 No 94 |
| Standards | EN/IEC 60947-1; EN/IEC 60947-5-1; CSA C22.2 No 14; JIS C 852; JIS C 4520; UL 508; EN/IEC 60947-5-5 |
| Product Certifications | CSA; GOST; CCC; UL |
| Vibration Resistance | +/- 3 mm (f= 2…500 Hz) conforming to IEC 60068-2-6; 5 gn (f= 2…500 Hz) conforming to IEC 60068-2-6 |
| Shock Resistance | 30 gn (duration = 18 ms) for half sine wave acceleration conforming to IEC 60068-2-27; 50 gn (duration = 11 ms) for half sine wave acceleration conforming to IEC 60068-2-27 |
| Resistance To Fast Transients | 2 kV conforming to IEC 61000-4-4 |
| Resistance To Electromagnetic Fields | 10 V/m conforming to IEC 61000-4-3 |
| Resistance To Electrostatic Discharge | 6 kV on contact (on metal parts) conforming to IEC 61000-4-2; 8 kV in free air (in insulating parts) conforming to IEC 61000-4-2 |
| Electromagnetic Emission | Class B conforming to IEC 55011 |
Packing Units18
| Unit Type Of Package 1 | PCE |
|---|---|
| Number Of Units In Package 1 | 1 |
| Package 1 Height | 3.0 cm |
| Package 1 Width | 10.0 cm |
| Package 1 Length | 8.0 cm |
| Package 1 Weight | 14.0 g |
| Unit Type Of Package 2 | S01 |
| Number Of Units In Package 2 | 60 |
| Package 2 Height | 15 cm |
| Package 2 Width | 15 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 1.065 kg |
| Unit Type Of Package 3 | S01 |
| Number Of Units In Package 3 | 60 |
| Package 3 Height | 15 cm |
| Package 3 Width | 15 cm |
| Package 3 Length | 40 cm |
| Package 3 Weight | 1.065 kg |
Logistical informations1
| Country Of Origin | FR |
|---|
Contractual warranty1
| Warranty (in Months) | 18 |
|---|