Schneider LC3D09AM7 - TeSys D - star delta starter - 3 x 3P (3 NO) - 9 A - 220 V AC coil
Schneider

TeSys D - star delta starter - 3 x 3P (3 NO) - 9 A - 220 V AC coil

Nicht im Verkauf

Schneider LC3D09AM7, TeSys D - star delta starter - 3 x 3P (3 NO) - 9 A - 220 V AC coil. Kategorie: Niederspannungsprodukte. Nicht im Verkauf; für dieses Produkt gibt es keinen Preis und kein Angebot.

Wichtige Eigenschaften

Range
TeSys
Produktname
TeSys D
Product Or Component Type
Star delta starter
Device Short Name
LC3D

Produktbeschreibung

Montaj Plakasında Yıldız Delta Yolverici Tesys Lc3-d - Bobin 220 V Ac

Technische Daten

Haupteigenschaften24
RangeTeSys
ProduktnameTeSys D
Product Or Component TypeStar delta starter
Device Short NameLC3D
Contactor ApplicationMotor control
Utilisation CategoryAC-3
Device PresentationPre-wired
Poles Description3 x 3P
Power Pole Contact Composition3 x 3 NO
[Ue] Rated Operational VoltagePower circuit: <= 690 V AC 25...400 Hz
[Ie] Rated Operational Current9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Motor Power KW4 kW at 220/230 V AC 50/60 Hz; 7.5 kW at 380/400 V AC 50/60 Hz; 7.5 kW at 415 V AC 50/60 Hz; 7.5 kW at 440 V AC 50/60 Hz
Control Circuit TypeAC at 50/60 Hz
[Uc] Control Circuit Voltage220 V AC 50/60 Hz
Auxiliary Contact Composition1 NC for KM1 star contactor
[Uimp] Rated Impulse Withstand Voltage6 kV conforming to IEC 60947
Overvoltage CategoryIII
[Ui] Rated Insulation VoltagePower circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified
Electrical Durability2 Mcycles 9 A AC-3 at Ue <= 440 V
Safety CoverProtective cover
Interlocking TypeMechanical
Mounting SupportPlate
StandardsCSA C22.2 No 14; EN 60947-5-1; EN 60947-4-1; IEC 60947-4-1; IEC 60947-5-1; UL 508
Product CertificationsDNV; GOST; RINA; UL; LROS (Lloyds register of shipping); CSA; BV; CCC; GL
Ergänzende Eigenschaften19
Connections - TerminalsPower circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp t
Tightening TorquePower circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2
Mechanical Durability15 Mcycles
Maximum Operating Rate30 cyc/h 60 °C
Starting Time30 s
Coil TechnologyWithout built-in suppressor module
Control Circuit Voltage LimitsDrop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C); Operational: 0.8...1.1 Uc at 50 Hz (at <60 °C); Operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
Inrush Power In VA70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in Power Consumption In VA7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat Dissipation2…3 W at 50/60 Hz
Auxiliary Contacts TypeMechanically linked conforming to IEC 60947-5-1 3 x 1 NO + 1 NC; Mirror contact conforming to IEC 60947-4-1 3 x 1 NC
Signalling Circuit Frequency25...400 Hz
Minimum Switching Current5 mA for signalling circuit
Minimum Switching Voltage17 V for signalling circuit
Non-overlap Time1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
Width143 mm
Height124 mm
Depth143 mm
Net Weight1.53 kg
Umgebungsbedingungen11
Insulation Resistance> 10 MOhm for signalling circuit
IP Degree Of ProtectionIP2X front face conforming to IEC 60529
Climatic Withstandconforming to IACS E10; conforming to IEC 60947-1 Annex Q category D
Protective TreatmentTH conforming to IEC 60068-2-30
Pollution Degree3
Ambient Air Temperature For Storage-60…80 °C
Ambient Air Temperature For Operation-40…70 °C at Uc
Operating Altitude3000 m without derating
Fire Resistance850 °C conforming to IEC 60695-2-1
Flame RetardanceV1 conforming to UL 94
Mechanical RobustnessVibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor open: 10 Gn for 11 ms; Shocks contactor closed: 15 Gn for 11 ms
Verpackungseinheiten6
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height18 cm
Package 1 Width16 cm
Package 1 Length23.5 cm
Package 1 Weight1.53 kg
Logistical informations1
Country Of OriginFR

Schlagwörter

Produkte mit demselben Schlagwort im Katalog ansehen.