Schneider 16332 - Plug-in type LV surge arrester, PRD1 25r 3P+N
Schneider

16332 - Plug-in type LV surge arrester, PRD1 25r 3P+N

Schneider 16332, Plug-in type LV surge arrester, PRD1 25r 3P+N. Category: Modular Surge Arrester: iPRF1 12,5r & PRD1. Request a quote for price and lead time.

Key Specifications

Range Of Product
PRD1
Range Of Product
Acti9
Product Name
Acti9 PRD1
Product Or Component Type
Surge arrester with pluggable cartridge

Product Description

This Acti9 PRD1 product is a surge arrester with pluggable cartridge. It has 3P+N pole. The maximum continuous operating voltage is 350V (L-N or N-PE). It is available for TT or TN-S earthing system. It is a type 1 and type 2 surge arrester. It protects electrical installations against direct lightning strikes by finely clipping the lightning wave overvoltages. It is fitted with easy-to-replace withdrawable cartridges. The device has an end-of-life indication (white for correct operation, red at end of life) with remote signalling. The nominal discharge current (impulse 8-20 µs) is 25kA with a maximum of 40kA. The Uc maximum continuous operating voltage in differential mode (between phase and neutral) is 350VAC. The Uc maximum continuous operating voltage in common mode (between neutral and earth) is 350VAC. The maximum lightning current Iimp (impulse current 10-350 µs) is 25kA between L-N and 100kA between N-PE. The rated voltage network is 230VAC or 400VAC. The voltage protection level goes up to 1.5kV. The degree of protection is IK05 and IP20 on its terminals becoming IP40 once in modular enclosure. It can be mounted on DIN rail for modular installation. Its width is 16 modules of 9mm. This product complies with IEC/EN 61643-11 standard.

Key Features

  • Protection of electrical installations against direct lightning strikes
  • Combined surge arrester type 1+2 25kA according to IEC 61643-11:2011 and EN 61643-11:2012 standards
  • Suitable for TT and TN-S networks with high prospective short-circuit fault currents
  • Easy to replace withdrawable cartridges, and pluggable with anti-vibration lock
  • Can be installed with any upstream disconnection devices, such as a fuse or circuit breaker

Technical Specifications

Main14
Range Of ProductPRD1
Range Of ProductActi9
Product NameActi9 PRD1
Product Or Component TypeSurge arrester with pluggable cartridge
Device Short NamePRD1 25r
Device ApplicationDistribution
StandardsEN 61643-11:2012; IEC 61643-11:2011
Product CertificationsCE
Quality LabelsKEMA-KEUR
Poles Description3P + N
Remote SignallingWith
Signal Contacts Composition1 SD (1 C/O)
Surge Arrester TypeElectrical distribution network
Earthing SystemTN-S; TT
Complementary25
Surge Arrester Class TypeType 1 + 2
Surge Arrester TechnologySpark gap; MOV
[Ue] Rated Operational Voltage230/400 V AC (+/- 10 %) at 50/60 Hz
Nominal Discharge CurrentCommon mode: 100 kA (N/PE); Differential mode: 25 kA (L/N)
Maximum Discharge CurrentDifferential mode: 40 kA L/N
[Iimp] Impulse CurrentCommon mode: 100 kA N/PE 50 A.s; Differential mode: 25 kA L/N 12.5 A.s
[Uc] Maximum Continuous Operating VoltageDifferential mode: 350 V L/N; Common mode: 350 V N/PE
Maximum [Up] Voltage Protection LevelCommon mode 1.5 kV type 2 N/PE; Differential mode 1.5 kV type 2 L/N
[Ifi] Follow Current25 kA differential mode L/N; 0.1 kA common mode N/PE
Short-circuit Withstand25 kA
Disconnector Device TypeAssociated fuse gG 315 A up to Isc = 25 kA; Associated circuit breaker NSXm 100E TM-D up to Isc = 16 kA; Associated circuit breaker NSXm 100B TM-D up to Isc = 25 kA; Associated circuit breaker Compact NSX100B TM-D up to Isc = 25 kA
Signalling Circuit Voltage1 A/250 V AC 50/60 Hz
Mounting ModeClip-on (DIN rail)
9 Mm Pitches16
Height90 mm
Width142.8 mm
Depth70 mm
Net Weight1.43 kg
ColourAnthracite grey (RAL 7016)
MaterialPBT (polybutylene terephthalate)
Connections - TerminalsTunnel type terminal (downside) 2.5…35 mm²; Tunnel type terminal (upside) 2.5…35 mm²
Tightening Torque4.5 N.m
Impulse Current25 kA
Compatibility CodePRD1_25r
Market SegmentSmall commercial
Environment5
IK Degree Of ProtectionIK05 conforming to IEC 62262
Relative Humidity5…90 %
Operating Altitude2000 m
Ambient Air Temperature For Operation-25…60 °C
Ambient Air Temperature For Storage-40…80 °C
Packing Units18
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height9 cm
Package 1 Width14 cm
Package 1 Length18.8 cm
Package 1 Weight1.282 kg
Unit Type Of Package 2S03
Number Of Units In Package 27
Package 2 Height30 cm
Package 2 Width30 cm
Package 2 Length40 cm
Package 2 Weight9.555 kg
Unit Type Of Package 3P12
Number Of Units In Package 356
Package 3 Height45 cm
Package 3 Width80 cm
Package 3 Length120 cm
Package 3 Weight87.44 kg
Logistical informations1
Country Of OriginDE
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents2

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support