Schneider 56163 - RH21M 220/240 V AC 50/60/400 Hz WITH MANUAL FAULT RESET
Schneider

56163 - RH21M 220/240 V AC 50/60/400 Hz WITH MANUAL FAULT RESET

Schneider 56163, RH21M 220/240 V AC 50/60/400 Hz WITH MANUAL FAULT RESET. Category: Vigirex RH10MP-RH21MP-RH99MP-RH197-RHU. Request a quote for price and lead time.

Key Specifications

Range
VigiPacT
Device Short Name
RH21M
Product Or Component Type
Residual current protection relay
Relay Application
Protection relay

Product Description

VigiPacT RH21M is a DIN rail mounting residual current protection relay. It protects against people direct or indirect contact, property fire hazards and motors. It measures the earth leakage current in an electrical installation via its associated toroid. It trips the associated circuit breaker when the set residual operation current is overrun. The operational supply voltage is 220/240VAC 50/60Hz. The current sensitivity is selectable with 2 thresholds 30 mA and 300 mA. The time delay is instantaneous 0.06s. It requires a local manual reset after a fault clearance. The monitored distribution system voltage is up to 1000 VAC 50/60/400 Hz. It is installed on a DIN-rail inside a switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type A toroid or rectangular sensor.

Key Features

  • "VigiPacT relays ensure coordination with ComPacT circuit breakers (switch off within 40ms)"
  • "Continuous monitoring of the power supply, the relay/toroid link and internal electronics"
  • "Reinforced insulation of VigiPacT relays (overvoltage category IV)"
  • "Access to settings protected by a lead-sealable cover or password"
  • RoHS and REACH compliant

Technical Specifications

Main19
RangeVigiPacT
Device Short NameRH21M
Product Or Component TypeResidual current protection relay
Relay ApplicationProtection relay
Mounting SupportDIN rail
Earth-leakage Protection ClassType A
Type Of SettingSelector
Residual Earth-leakage Sensitity Adjustment TypeAdjustable 2 settings
Earth-leakage Sensitivity0.03 A; 0.3 A
Earth-leakage Time DelayInstantaneous for 0.03 A; Instantaneous for 0.3 A; Fixed 0.06 s for 0.3 A
Current Sensors CompatibilityVigiPacT TOA earth leakage current sensor; VigiPacT A earth leakage current sensor; VigiPacT L earth leakage current sensor
[Ithe] Conventional Enclosed Thermal Current8 A
Minimum Load10 mA at 12 V
[Us] Rated Supply Voltage220...240 V AC 50/60 Hz 55...110 %
Power Consumption In VA4 VA
Monitored Distribution System1000 V - AC at 50/60 Hz (maximum); 1000 V - AC at 400 Hz (maximum)
Earthing SystemIT; TT; TN-S
[Uimp] Rated Impulse Withstand Voltage8 kV
ResetManual reset
Complementary16
Test FunctionLocal; Remote test
MonitoringElectronics (continuous); Power supply (continuous); Relay/sensor link (continuous)
Type Of MeasurementEarth fault current internal measurement, range: 80...100 %
Tamperproof Of SettingsProtected by sealable cover
Connections - TerminalsAuxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible 24 AWG...12 AWG; Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid 24 AWG...12 AWG; Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible 24 AWG...12 AWG; Fault: screw terminal cable(s) 0.2…2.5 mm² flexible 24 AWG...12 AWG; Fault: screw terminal cable(s) 0.2…4 mm² rigid 24 AWG...12 AWG; Fault: scre
Wire Stripping LengthAuxiliary power supply: 7 mm for top connection; Fault: 8 mm for bottom connection; Relay test and fault reset: 5 mm for bottom connection; Sensor: 5 mm for top connection; Voltage presence: 8 mm for bottom connection
Tightening TorqueAuxiliary power supply: 0.6 N.m top; Fault: 0.6 N.m bottom; Relay test and fault reset: 0.25 N.m bottom; Sensor: 0.25 N.m top; Voltage presence: 0.6 N.m bottom
9 Mm Pitches6
StandardsEN/IEC 60947-2 Annex M; EN/IEC 60755; UL 1053; CAN/CSA C22.2 No. 144
Width54 mm
Height81 mm
Depth74 mm
Net Weight0.3 kg
IP Degree Of ProtectionIP40 on front face: conforming to EN/IEC 60529; IP30 on side parts: conforming to EN/IEC 60529; IP20 on connection terminals: conforming to EN/IEC 60529
IK Degree Of ProtectionIK07 conforming to EN 50102
Mechanical RobustnessFire resistance conforming to IEC 60695-2-1; IK protection 2 joules: IK07 conforming to EN 50102; Vibrations 13.2...100 Hz: 0.7 g; Vibrations 2...13.2 Hz: +/- 1 mm
Environment7
Overvoltage CategoryIV
Electrical Shock Protection ClassClass II
Electromagnetic CompatibilityConducted and radiated emissions: , B, conforming to CISPR 11; Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6; Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2; High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5; Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4; Radiated susceptibility: , 3, conforming to IE
Relative Humidity95 % at 55 °C
Pollution Degree3 conforming to IEC 60664-1
Ambient Air Temperature For Operation-35…70 °C
Ambient Air Temperature For Storage-55…85 °C
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height8.8 cm
Package 1 Width7.8 cm
Package 1 Length9.3 cm
Package 1 Weight311.0 g
Unit Type Of Package 2S03
Number Of Units In Package 236
Package 2 Height30.0 cm
Package 2 Width30.0 cm
Package 2 Length40.0 cm
Package 2 Weight11.683 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads