Schneider A9C15924 - Acti9 iACT - 24V DC control and auxiliary contact 1 NO with Ti24 PLC interface
Schneider

Acti9 iACT - 24V DC control and auxiliary contact 1 NO with Ti24 PLC interface

Schneider A9C15924, Acti9 iACT - 24V DC control and auxiliary contact 1 NO with Ti24 PLC interface. Category: iCT. Request a quote for price and lead time.

Key Specifications

Range
Acti9
Product Or Component Type
Control and indication auxiliary
Device Short Name
iACT24
Signal Contacts Composition
1 NO

Product Description

This Acti9 iACT24 is reliable control and indication auxiliary. It has 1 normally open signal contact. Control voltage is 24VDC and 230V AC. Mounting is performed on the left of Acti9 iCT contactors with operational current less than or equal to 25A. The degree of protection is IP20 and IP40 in an enclosure. It is DIN rail mountable. Mechanical endurance goes up to 250000 cycles. This product is compliant with IEC/EN 60947-5-1.

Key Features

  • Provides a status indication of the contactor
  • Easy integration with PLCs with the i24 interface

Technical Specifications

Main8
RangeActi9
Product Or Component TypeControl and indication auxiliary
Device Short NameiACT24
Signal Contacts Composition1 NO
Signalling Circuit Voltage24 V DC: - 20...20 % 0.002...0.1 A
[Uc] Control Circuit Voltage230 V AC 50/60 Hz maintained >= 200 ms; 24 V DC falling edge; 24 V DC rising edge
Control TypeRemote control
[Us] Rated Supply Voltage230 V AC at 50/60 Hz
Complementary22
Mounting ModeFixed, on the left of CT
Mounting SupportDIN rail
Comb Busbar And Distribution Block CompatibilityBottom: YES; Top: NO
9 Mm Pitches2
Height81 mm
Width18 mm
Depth68 mm
ColourWhite
Overvoltage CategoryIII
[Uimp] Rated Impulse Withstand Voltage4 kV
[Ui] Rated Insulation Voltage440 V
Immunity To Microbreaks10 ms
Undervoltage BehaviourNo opening if loss of 24 V DC
StandardsIEC 60947-1 annex S
Quality LabelsCE
Electrical Durability250000 cycles conforming to IEC 60947-5-1
Connections - TerminalsControl circuit: tunnel type terminals 2 cable(s) 2.5 mm² flexible; Control circuit: tunnel type terminals 2 cable(s) 1.5 mm² rigid; Auxiliary supply: tunnel type terminals 2 cable(s) 2.5 mm² flexible; Auxiliary supply: tunnel type terminals 2 cable(s) 1.5 mm² rigid; Control circuit: spring-loaded terminal Ti24 2 cable(s) 0.25…0.75 mm² flexible; Control circuit: spring-loaded terminal Ti24 1 cable
Wire Stripping LengthControl circuit: 10 mm for bottom connection; Auxiliary supply: 10 mm for bottom connection; Control circuit: 10 mm for top connection
Tightening TorqueControl circuit: 1 N.m bottom; Auxiliary supply: 1 N.m bottom
Product CompatibilityICT 230/240 V 50 Hz; With PLC; ICT 220 V 50 Hz; Acti 9 Smartlink; ICT 220/240 V 50 Hz
Market SegmentResidential; Small commercial
Compatibility CodeIACT24
Environment6
IP Degree Of ProtectionIP20 conforming to IEC 60529; IP40 (modular enclosure) conforming to IEC 60529
Pollution Degree3 conforming to IEC 60439-1
Tropicalisation2 conforming to IEC 60947-5-1
Relative Humidity93 % at 40 °C conforming to IEC 60068-2
Ambient Air Temperature For Operation-25…60 °C
Ambient Air Temperature For Storage-40…80 °C
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height2.700 cm
Package 1 Width7.600 cm
Package 1 Length8.600 cm
Package 1 Weight84.000 g
Unit Type Of Package 2S03
Number Of Units In Package 2108
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight9.546 kg
Logistical informations1
Country Of OriginES
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents3

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support