ABLU3A24400 - POWER SUPPLY, 380...500 V AC, 3 phase, 24V, 40A
Schneider ABLU3A24400, POWER SUPPLY, 380...500 V AC, 3 phase, 24V, 40A. Category: Power supplies for industrial use, rail mounting. Request a quote for price and lead time.
- Reference:ABLU3A24400
- Manufacturer / Brand:Schneider
- Availability:On Request / Inquire Stock
- Price:1,150.00 EUR (Request a quote)
Key Specifications
- Range Of Product
- Modicon Power Supply
- Product Or Component Type
- Power supply
- Power Supply Type
- Regulated switch mode
- Variant Option
- Universal
Product Description
This product is part of the Modicon ABL range, an offer of power supplies for industrial use. It is a regulated switch mode power supply. It has a rated input of 380V to 500V AC, a rated output current of 40A at 24V DC and a rated power output of 960W. It supplies direct current voltage and ensures a protection against overloads and short-circuits with automatic or manual restart. It operates from minus 25 to plus 55degrees celcius and plus 55 to 70degrees celcius with a current derating of 3.3%, at an altitude of less than 2000meters. It measures 124mm high, 110mm wide, and 128.7mm deep. It weighs 2.29kg. It is a power supply for industrial use. It meets CE, CB Scheme, cULus Listed, UL HazLoc Class1Div2, cURus Recognized, RCM, EAC, UKCA, KC. To IEC/EN-UL/CSA 62368-1, IEC/EN-UL/CSA 61010-1/2 standards. GV2ME07 or GV2RT06 circuit breakers are recommanded for its protection. It installs on 35mm DIN rail. It brings energy to your automated systems. Designed with extreme compactness for simple machines and applications.
Key Features
- One of the most compact on the market
- Up to +70°C ambiant temperature
- Manual or Automatic reset in case of output overload or short circuit
- Power reserve allowing to deliver a current of 150% its nominal rating for a short time
- Conformal coating in order to resist to common dust and humidity
Technical Specifications
Main10
| Range Of Product | Modicon Power Supply |
|---|---|
| Product Or Component Type | Power supply |
| Power Supply Type | Regulated switch mode |
| Variant Option | Universal |
| Enclosure Material | Metal |
| Nominal Input Voltage | 380...500 V AC three phase |
| Rated Power In W | 960 W |
| Output Voltage | 24 V DC |
| Power Supply Output Current | 40 A |
| Permissible Temporary Current Boost | 1.5 x In (for 5 seconds) |
Complementary32
| Input Voltage Limits | 320...575 V AC 3 phases |
|---|---|
| Nominal Network Frequency | 50…60 Hz |
| Network System Compatibility | TN; TT; IT |
| Maximum Leakage Current | 2 mA 500 V AC |
| Input Protection Type | Integrated fuse (not interchangeable) 3.15 A; External protection (recommended) |
| Inrush Current | 35 A at 380 V; 35 A at 500 V |
| Power Factor | 0.90 at 380 V AC; 0.90 at 500 V AC |
| Efficiency | 95 % at 380 V AC; 95 % at 500 V AC |
| Output Voltage Adjustment | 24...28 V |
| Power Dissipation In W | 49 W |
| Current Consumption | < 1.9 A 380 V AC; < 1.7 A 500 V AC |
| Turn-on Time | < 2 s |
| Holding Time | > 20 ms 380 V AC; > 20 ms 500 V AC |
| Startup With Capacitive Loads | 200000 µF |
| Residual Ripple | < 200 mV |
| Meantime Between Failure [MTBF] | 595400 h at 25 °C, full load conforming to SR 332; 308300 h at 55 °C, 80 % load conforming to SR 332 |
| Output Protection Type | Against overload and short-circuits, protection technology: manual or automatic reset by switch; Against over temperature, protection technology: automatic reset; Against overvoltage, protection technology: manual reset |
| Connections - Terminals | Screw connection: 6...16 mm², (10 AWG...6 AWG) without wire end ferrule for output; Screw connection: 6...10 mm², (10 AWG...8 AWG) with wire end ferrule for output; Screw connection: 0.75…6 mm², (18 AWG...10 AWG) without wire end ferrule for input; Screw connection: 0.75...4 mm², (18 AWG...12 AWG) with wire end ferrule for input; Cage clamp: 0.2...1.5 mm², (22 AWG...16 AWG) without wire end ferrul |
| Line And Load Regulation | < 0.17 % at 100 % load in line at 25 °C; < 0.6 % +/- 0.5 % at 150 % load at 25 °C |
| Status LED | 1 LED (green and red) product status |
| Depth | 128.7 mm |
| Height | 124 mm |
| Width | 110 mm |
| Net Weight | 2.29 kg |
| Output Coupling | Parallel |
| Marking | CE; UKCA |
| Mounting Support | Top hat type TH35-15 rail conforming to IEC 60715; Top hat type TH35-7.5 rail conforming to IEC 60715; Double-profile DIN rail |
| Supply | SELV conforming to IEC 60950-1; SELV conforming to IEC 60204-1; SELV conforming to IEC 60364-4-41 |
| Dielectric Strength | 4000 V AC with input to output; 2000 V AC with input to ground; 1500 V AC with output to ground; 4000 V AC with input to diagnostic relay; 500 V AC with output to diagnostic relay; 1500 V AC with diagnostic relay to ground; with shutdown input not isolated from output |
| Diagnostic Relay | Electromechanical relay 1000.0 mA 30 V |
| Service Life | 10 year(s) 40 °C 80 % load |
| Overvoltage Category | III; II |
Environment11
| Standards | IEC 62368-1; EN/IEC 61204-3; IEC 61000-6-1; IEC 61000-6-2; IEC 61000-6-3; IEC 61000-6-4; IEC 61000-3-2; EN 61000-3-3; UL 62368-1; CSA C22.2 No 62368-1; CSA C22.2 No 107.1 |
|---|---|
| Product Certifications | CE; CUL listed; CUL recognized; RCM; CB Scheme; EAC; KC; UKCA; CURus |
| Operating Altitude | < 5000 m overvoltage category III; overvoltage category II |
| Shock Resistance | 150 m/s² for 11 ms |
| IP Degree Of Protection | IP20 |
| Ambient Air Temperature For Operation | -25…55 °C without current derating mounting position A < 2000 m; 55…70 °C with current derating of 3.3 % per °C mounting position A < 2000 m |
| Electrical Shock Protection Class | Class I |
| Pollution Degree | 2 |
| Vibration Resistance | 3.5 mm (f= 3…11.9 Hz) conforming to IEC 60068-2-6; 20 m/s² (f= 11.9…150 Hz) conforming to IEC 60068-2-6 |
| Electromagnetic Immunity | Immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2; Immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2; Immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3; Immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC |
| Electromagnetic Emission | Conducted emissions conforming to IEC 61000-6-3; Radiated emissions conforming to IEC 61000-6-4 |
Packing Units18
| Unit Type Of Package 1 | PCE |
|---|---|
| Number Of Units In Package 1 | 1 |
| Package 1 Height | 15.500 cm |
| Package 1 Width | 21.500 cm |
| Package 1 Length | 22.000 cm |
| Package 1 Weight | 2.872 kg |
| Unit Type Of Package 2 | S03 |
| Number Of Units In Package 2 | 2 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.344 kg |
| Unit Type Of Package 3 | P12 |
| Number Of Units In Package 3 | 48 |
| Package 3 Height | 105.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 120.000 cm |
| Package 3 Weight | 160.250 kg |
Logistical informations1
| Country Of Origin | IN |
|---|
Contractual warranty1
| Warranty (in Months) | 18 |
|---|
Documents and Downloads