Schneider BMXMSP0200 - 2-channel pulse output module PTO
Schneider

BMXMSP0200 - 2-channel pulse output module PTO

Schneider BMXMSP0200, 2-channel pulse output module PTO. Category: Modicon X80 I/Os. Request a quote for price and lead time.

Key Specifications

Range Of Product
Modicon X80
Product Or Component Type
PTO module
Number Of Channels
2
Number Of Inputs
4

Product Description

This product is part of the Modicon X80 range, a common platform of modules for Modicon M580 and M340 Programmable Automation Controllers (PAC). This PTO module has 2 channels, 4 inputs with sink (positive) discrete logic. It is a PTO module with an input/output voltage 24V DC, an output current of 50mA and a maximum current consumption of 200mA at 3.3V DC. This product is robust, high quality and based on the latest innovative technology. It is furnished with two 28-way connectors for electrical connection. There is no insulation between channels. It is suitable for medium to large process applications. It meets EN 61131-2, EN 61000-6-4, EN 61000-6-2 and EN 61010-2-201 standards. This output compatible with signal converter (USIC), RS422, 7mA input and source input, 5V to 24V. Input compatible with 2-wire/3-wire proximity sensor 19.2V to 30V conforming to IEC 947-5-2. Modicon X80 consists in a compatible modules common platform that reduce maintenance and training costs with same spare parts in stock, and unique training for different Programmable Automation Controllers (PAC).

Key Features

  • Common PTO module for Modicon M580 and M340 platforms
  • Two independent PTO channels
  • For controlling variable speed drives or Lexium 32C/32M servo drives with integrated pulse control interface
  • Robust build for industrial environments

Technical Specifications

Main8
Range Of ProductModicon X80
Product Or Component TypePTO module
Number Of Channels2
Number Of Inputs4
Discrete Input TypeCurrent sink yes origin input conforming to IEC 61131-2 type 3; Current sink yes proximity input and limit switch input conforming to IEC 61131-2 type 3; Current sink or source counter in position input conforming to IEC 61131-2 type 3; Current sink or source drive ready, emergency input conforming to IEC 61131-2 type 3
Input Compatibility2-wire/3-wire proximity sensor 19.2…30 V conforming to IEC 947-5-2
Output CompatibilitySignal converter (USIC); RS422, 7 mA input; Source input, 5 V to 24 V
Output Frequency200 kHz <0.5 m with USIC and VW3M8210R05; 100 kHz <5 m with the normal source input circuit; 200 kHz <10 m with the RS422 compatible circuits
Complementary29
Operating Threshold> 12 V no error supply voltage; > 8 V error supply voltage
Input Voltage24 V DC
Input Current4.3 mA
Voltage State 1 Guaranteed>= 11 V
Current Consumption35 mA at 24 V DC preactuator; 150 mA at 3.3 V DC typical; 200 mA at 3.3 V DC maximum
Current State 1 Guaranteed>= 2 mA
Voltage State 0 Guaranteed5 V
Current State 0 Guaranteed<= 1.5 mA
Response Time< 200 µs for position completed input and drive ready input; < 60 µs for origin input and proximity input
Number Of Outputs1 pulse output; 2 auxiliary output
Preactuator Voltage Detection Threshold< 8 V error preactuator voltage auxiliary output; < 8 V no error preactuator voltage auxiliary output; > 14 V error preactuator voltage pulse output; > 14 V no error preactuator voltage pulse output
Output Voltage24 V DC
Output Voltage Limits19...30 V
Discrete Output Current50 mA
Current Per Channel0.4 A
Maximum Leakage Current0.05 mA at state 0
[Ures] Residual Voltage0.15 V at state 1
Response Time On Output1.2...1.5 ms on appearance; 1.2...1.5 ms on disappearance
Load Impedance Ohmic15000 Ohm
Output Overload ProtectionBy current limiter and electronic circuit breaker
Output Short-circuit ProtectionBy current limiter and electronic circuit breaker
Reverse Polarity ProtectionBy reverse mounting diode on output; Integrated on input
Insulation Between ChannelsNo insulated
Insul Btwn Prim And Second1500 Vrms
Insulation Resistance> 10 MOhm
Local Signalling1 LED (green) for module operating (RUN); 1 LED (red) for external fault (I/O); 1 LED (red) for internal fault, module failure (ERR); 1 LED (green) for download (DL); 8 LEDs (green) for channel status (CH00); 8 LEDs (green) for channel status (CH01)
Electrical Connection2 connectors with 28 pins
Module FormatStandard
Product CertificationsCE; UL; CSA; RCM; EAC; Merchant Navy; ATEX zone 2/22; IECEx zone 2/22
Environment5
Ambient Air Temperature For Operation-25…70 °C
Derating FactorWithout
Directives2014/35/EU - low voltage directive; 2014/30/EU - electromagnetic compatibility; 2014/34/EU - ATEX directive
StandardsIEC 61131-2; IEC 61010-2-201; UL 61010-2-201; CSA C22.2 No 61010-2-201; IACS E10; IEC 61000-6-5, interface type 1 and type 2; IEC 61850-3, location G; IEC 60079-0
Environmental CharacteristicHazardous location class I division 2
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height5.400 cm
Package 1 Width11.500 cm
Package 1 Length11.700 cm
Package 1 Weight147.000 g
Unit Type Of Package 2S02
Number Of Units In Package 215
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight2.527 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents4

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support