Schneider LR97D25M7 - TeSys LR97D Electronic Thermal Overload Relay 5-25A 220VAC
Schneider

LR97D25M7 - TeSys LR97D Electronic Thermal Overload Relay 5-25A 220VAC

Schneider LR97D25M7, TeSys LR97D Electronic Thermal Overload Relay 5-25A 220VAC. Category: TeSys Deca electronic relays. Request a quote for price and lead time.

Key Specifications

Range
TeSys
Product Name
TeSys D
Device Short Name
LR97
Product Or Component Type
Electronic overcurrent relay

Product Description

TeSys LR97D electronic overcurrent relay, 25A/690V, to be supplied with 200-240V AC, for protection of motors with a rated current 5-21A. It provides 3 dials to adjust the protection, LOAD (5-25A) for the overcurrent level, O-TIME (0.3-10sec) for the acceptable duration of the overcurrent, D-TIME (0.5-30sec) for the starting duration. In addition, the device trips when the current is higher than 3 x LOAD during more than 0.5sec in steady state and if there is a missing phase during more than 3sec. Settings also include selectors for 1-phase/3-phase motors and manual/automatic reset, the device has a reset button, a test/stop button, 2 LED indicators (Run/Trip), 2 auxiliary contacts 1NO/NC for fault signaling. Settings can be locked by sealing the transparent cover. For direct attachment to the bottom terminals of a 3-phase contactor LC1D09-D38, with screw clamp terminals on bottom, the separate mounting from the contactor is possible using the terminal block LAD7B106 (to be ordered separately). Multi-standards certified (IEC, UL, CSA, CCC, EAC), compliant RoHs/Reach.

Key Features

  • "Settings can be locked by sealing the transparent cover"
  • "It provides 3 dials to adjust the protection"
  • "Compact (45 mm wide) for easy integration into motor starter functions"
  • "Reduces production loss and associated downtime"
  • "Simple setting and signaling features"

Technical Specifications

Main11
RangeTeSys
Product NameTeSys D
Device Short NameLR97
Product Or Component TypeElectronic overcurrent relay
Relay ApplicationOverload Imax > Isetting; Locked rotor, mechanical jamming I > 3 x Isetting; Sensitivity to phase failure
Product CompatibilityLC1D09...D38
Network TypeAC
[Us] Rated Supply Voltage200...240 V AC
Thermal Protection Adjustment Range5…25 A
[Ue] Rated Operational Voltage600 V AC 50/60 Hz for power circuit conforming to CSA; 600 V AC 50/60 Hz for power circuit conforming to UL; 690 V AC 50/60 Hz for power circuit conforming to IEC 60947-4-1
Quantity Per SetSet of 10
Complementary20
Network Frequency50...60 Hz
Mounting SupportDirect on contactor; Rail
Tripping Threshold5...21 A
Surge Withstand6 kV conforming to IEC 61000-4-5
Contacts Type And Composition1 C/O
[Ith] Conventional Free Air Thermal Current3 A for control circuit
Protection TypeBS fuse 3 A - for control circuit; GB2 circuit breaker 3 A - for control circuit; GG fuse 3 A - for control circuit
Maximum Power28 W at 110 V DC conforming to IEC 60947; 28 W at 220 V DC conforming to IEC 60947; 55 W at 24 V DC conforming to IEC 60947; 55 W at 48 V DC conforming to IEC 60947; 140 VA at 48 V AC conforming to IEC 60947; 360 VA at 110 V AC conforming to IEC 60947; 360 VA at 220 V AC conforming to IEC 60947; 70 VA at 24 V AC conforming to IEC 60947
[Ui] Rated Insulation VoltagePower circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL; Power circuit: 690 V conforming to IEC 60947-4-1
[Uimp] Rated Impulse Withstand Voltage6 kV
Phase Failure Sensitivity< 3 s
ResetAutomatic reset 120 s fixed; Electrical by interruption of power supply for minimum 0.1 s; Manual reset
Time Range0.2...10 s - O-time knob; 0.3...10 s - O-time knob; 0.5..30 s - D-time knob
Signalling Function2 LEDs
Connections - TerminalsControl circuit: cable 1 x 1…25 mm²flexible with cable end; Control circuit: cable 1 x 1…25 mm²flexible without cable end; Power circuit: cable 1 x 1…4 mm²flexible with cable end; Power circuit: cable 1 x 1.5…10 mm²flexible without cable end; Power circuit: lug-clamp 1 x 1…4 mm²flexible with cable end; Power circuit: lug-clamp 1 x 1.5…10 mm²flexible without cable end; Control circuit: cable 2 x 1…
Tightening TorqueControl circuit: 0.6...1.2 N.m on lug-clamp; Power circuit: 2 N.m on cable
Height67.5 mm
Width45 mm
Depth67.5 mm
Net Weight0.172 kg
Environment15
StandardsIEC 60255-6; IEC 60947
Product CertificationsCSA; UL; GOST
Protective TreatmentTH conforming to IEC 60068
IP Degree Of ProtectionIP20 conforming to IEC 60529
Ambient Air Temperature For Operation-25…60 °C conforming to IEC 60947-4-1
Ambient Air Temperature For Storage-30…80 °C
Operating Altitude2000 m
Fire Resistance850 °C conforming to IEC 60695-2-1
Shock Resistance15 gn 11 ms conforming to IEC 60068-2-7
Vibration Resistance4 gn conforming to IEC 60068-2-6
Dielectric Strength2 V 50 Hz conforming to IEC 60255-5
Resistance To Electrostatic Discharge6 kV in indirect mode; 8 kV in air
Resistance To Radiated Fields10 V/m level 3
Resistance To Fast Transients2 kV
Disturbance Radiated/conducted10 V conforming to EN 61000-4-6; Class A conforming to EN 55011
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height5.500 cm
Package 1 Width7.200 cm
Package 1 Length7.700 cm
Package 1 Weight183.000 g
Unit Type Of Package 2S02
Number Of Units In Package 224
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight4.804 kg
Logistical informations1
Country Of OriginKR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents2

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support