Schneider LR9F7375 - TeSys LRF - electronic thermal overload relay - 200...330 A - class 10
Schneider

TeSys LRF - electronic thermal overload relay - 200...330 A - class 10

Not for sale

Schneider LR9F7375, TeSys LRF - electronic thermal overload relay - 200...330 A - class 10. Category: TeSys LR9. Not for sale; no price or quote is offered for this product.

Key Specifications

Range
TeSys
Product Name
TeSys LRF
Device Short Name
LR9F
Product Or Component Type
Electronic thermal overload relay

Product Description

TeSys LR9F electronic overload relay, thermal setting range 200-330A, class 10, for protection of motors 132-160kW@400V. to be mounted directly below a TeSys F 3-pole contactor LC1 F225, F265, F330, F400, F500, use of a support mounting plate LA7F902 is mandatory (to be ordered separately). Motor protection includes thermal overload of 1-phase and 3-phase motors, phase failure, phase unbalance, prolonged starting times, stalled rotor conditions. On the front of the relay, it provides a thermal adjustement dial, buttons for test, stop & reset, a trip indicator, trip auxiliary contacts 1NO+1NC. Multi standards certified (IEC, UL, CSA, CCC, Marine), Green Premium compliant (RoHs/Reach).

Technical Specifications

Main9
RangeTeSys
Product NameTeSys LRF
Device Short NameLR9F
Product Or Component TypeElectronic thermal overload relay
Relay ApplicationMotor protection
Product CompatibilityLC1F225...LC1F500
Network TypeAC
Thermal Overload ClassClass 10 conforming to IEC 60947-4
Thermal Protection Adjustment Range200…330 A
Complementary23
Network Frequency50/60 Hz
Mounting SupportDirect on contactor; Plate
Tripping Threshold1.12 +/- 0.06 In tripping conforming to IEC 60947-4-1
Surge Withstand4 kV conforming to IEC 61000-4-5
Contacts Type And Composition1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current5 A for control circuit
[Ue] Rated Operational Voltage1000 V AC 50/60 Hz for power circuit conforming to VDE 0110 group C
[Ui] Rated Insulation VoltagePower circuit: 1000 V AC conforming to IEC 60947-4
[Uimp] Rated Impulse Withstand Voltage8 kV conforming to IEC 60947-1
Phase Failure SensitivityTripping in 4 s +/- 20 % conforming to IEC 60947-4-1
ResetManual reset on front relay
Control TypeDial white full-load current adjustment; Test button red; Push-button red reset; Push-button stop
Local SignallingTrip indicator
Temperature Compensation-20…70 °C
Current Consumption<= 5 mA no-load
Switching Capacity For Alarm0...150 mA
Maximum Voltage Drop<2.5 V closed state
Connections - TerminalsControl circuit: screw clamp terminals 1 cable 0.75…2.5 mm² - cable stiffness: flexible - with cable end; Control circuit: screw clamp terminals 1 cable 0.75…2.5 mm² - cable stiffness: solid; Control circuit: screw clamp terminals 1 cable 0.75…4 mm² - cable stiffness: flexible - without cable end; Control circuit: screw clamp terminals 2 cable 1…1.5 mm² - cable stiffness: flexible - with cable end
Tightening TorqueControl circuit: 1.2 N.m on screw clamp terminals; Power circuit: 35 N.m on screw clamp terminals
Height136.8 mm
Width150 mm
Depth127.6 mm
Net Weight2.32 kg
Environment11
StandardsVDE 0660; IEC 60947-4-1; EN 60947-4-1; IEC 60255-17; IEC 60255-8
Product CertificationsUL; CSA; UKCA
Protective TreatmentTH
IP Degree Of ProtectionIP20 conforming to IEC 60529; IP20 conforming to VDE 0106
Ambient Air Temperature For Operation-20…55 °C conforming to IEC 60255-8
Ambient Air Temperature For Storage-40…85 °C
Operating Altitude<= 2000 m without derating
Fire Resistance850 °C conforming to IEC 60695-2-1
Mechanical RobustnessShocks: 13 Gn for 11 ms conforming to IEC 60068-2-7; Vibrations 5...300 Hz: 2 GN conforming to IEC 60068-2-6
Dielectric Strength6 kV 50 Hz conforming to IEC 255-5
Electromagnetic CompatibilityResistance to electrostatic discharge: 6 kV in indirect mode conforming to IEC 61000-4-2; Resistance to electrostatic discharge: 8 kV in air conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test: 10 V/m conforming to IEC 61000-4-3; Fast transients immunity test: 2 kV conforming to IEC 61000-4-4
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height18.000 cm
Package 1 Width20.000 cm
Package 1 Length19.500 cm
Package 1 Weight1.882 kg
Unit Type Of Package 2P06
Number Of Units In Package 236
Package 2 Height75.000 cm
Package 2 Width60.000 cm
Package 2 Length80.000 cm
Package 2 Weight79.896 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents2

Tags

See products with the same tag in the catalogue.