Circuit breaker ComPact NSX630H, 70kA at 415VAC, MicroLogic 2.3 trip unit 630A, 4 poles 4d

Schneider LV432896, Circuit breaker ComPact NSX630H, 70kA at 415VAC, MicroLogic 2.3 trip unit 630A, 4 poles 4d. Category: ComPact NSX <630A. Not for sale; no price or quote is offered for this product.
- Reference:LV432896
- Manufacturer / Brand:Schneider
Key Specifications
- Range
- ComPact
- Product Name
- ComPact NSX
- Range Of Product
- ComPact NSX400...630
- Device Short Name
- NSX630H
Product Description
This Compact NSX630H is a complete 4P 4d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 70kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic Micrologic 2.3 trip unit, with 630A rating. Micrologic 2.3 trip unit provides adjustable long time and short time protections, and a fixed instantaneous protection. This 4 poles version (185mm x 255mm x 110mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX630H is part of Schneider Electric EcoStruxure Power architecture.
Technical Specifications
Main22
| Range | ComPact |
|---|---|
| Product Name | ComPact NSX |
| Range Of Product | ComPact NSX400...630 |
| Device Short Name | NSX630H |
| Product Or Component Type | Circuit breaker |
| Device Application | Distribution |
| Number Of Poles | 4P |
| Protected Poles Description | 3t; 4t; 3t + N/2 |
| Neutral Position | Left |
| [In] Rated Current | 630 A at 40 °C |
| [Ue] Rated Operational Voltage | 690 V AC 50/60 Hz |
| Network Type | AC |
| Network Frequency | 50/60 Hz |
| Suitability For Isolation | Yes conforming to EN/IEC 60947-2 |
| Utilisation Category | Category A |
| [Icu] Rated Ultimate Short-circuit Breaking Capacity | 85 kA at 240 V AC 50/60 Hz conforming to UL 508; 65 kA at 480 V AC 50/60 Hz conforming to UL 508; 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 20 |
| Performance Level | H 70 kA 415 V AC |
| Trip Unit Name | MicroLogic 2.3 |
| Trip Unit Technology | Electronic |
| Trip Unit Protection Functions | LSoI |
| Control Type | Toggle |
| Circuit Breaker Mounting Mode | Fixed |
Complementary30
| [Ui] Rated Insulation Voltage | 800 V AC 50/60 Hz |
|---|---|
| [Uimp] Rated Impulse Withstand Voltage | 8 kV |
| [Ics] Rated Service Short-circuit Breaking Capacity | 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 |
| Mechanical Durability | 15000 cycles |
| Electrical Durability | 2000 cycles at 690 V In; 6000 cycles at 690 V In/2; 4000 cycles at 440 V In; 8000 cycles at 440 V In/2 |
| Mounting Support | Backplate |
| Upside Connection | Front |
| Downside Connection | Front |
| Connection Pitch | 45 mm |
| Protection Type | L : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection |
| Trip Unit Rating | 630 A at 40 °C |
| Long-time Pick-up Adjustment Type Ir (thermal Protection) | Adjustable 9 settings |
| [Ir] Long-time Protection Pick-up Adjustment Range | 250...630 A |
| Long-time Protection Delay Adjustment Type Tr | Fixed |
| [tr] Long-time Protection Delay Adjustment Range | 16 s at 6 x Ir |
| Thermal Memory | 20 minutes before and after tripping |
| Short-time Protection Pick-up Adjustment Type Isd | Adjustable 9 settings |
| [Isd] Short-time Protection Pick-up Adjustment Range | 1.5...10 x Ir |
| Short-time Protection Delay Adjustment Type Tsd | Fixed |
| Instantaneous Protection Pick-up Adjustment Type Ii | Fixed |
| [Ii] Instantaneous Protection Pick-up Adjustment Range | 6900 A |
| Earth-leakage Protection | Without |
| Neutral Protection Settings | 0.5 x Ir (3t + N/2); 1 x Ir (4t); No protection (3t) |
| Zone Selective Interlocking ZSI | Without |
| Number Of Slots For Electrical Auxiliaries | 6 slot(s) |
| Local Signalling | Flashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload |
| Width (W) | 185 mm |
| Height (H) | 255 mm |
| Depth (D) | 110 mm |
| Net Weight | 8.13 kg |
Environment11
| Standards | EN/IEC 60947 |
|---|---|
| Product Certifications | CCC; EAC; Marine |
| Overvoltage Category | Class II |
| Electrical Shock Protection Class | Class II |
| Pollution Degree | 3 conforming to IEC 60664-1 |
| IP Degree Of Protection | IP40 conforming to IEC 60529 |
| IK Degree Of Protection | IK07 conforming to IEC 62262 |
| Ambient Air Temperature For Operation | -25…70 °C |
| Ambient Air Temperature For Storage | -50…85 °C |
| Relative Humidity | 0…95 % |
| Operating Altitude | 0...2000 m without derating; 2000 m...5000 m with derating |
Packing Units12
| Unit Type Of Package 1 | PCE |
|---|---|
| Number Of Units In Package 1 | 1 |
| Package 1 Height | 15.0 cm |
| Package 1 Width | 20.4 cm |
| Package 1 Length | 29.0 cm |
| Package 1 Weight | 7.542 kg |
| Unit Type Of Package 2 | S04 |
| Number Of Units In Package 2 | 3 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 40.0 cm |
| Package 2 Length | 60.0 cm |
| Package 2 Weight | 23.17 kg |
Logistical informations1
| Country Of Origin | FR |
|---|
Contractual warranty1
| Warranty (in Months) | 18 |
|---|
Documents and Downloads
Documents are published by the manufacturer and open in a new tab.