Schneider LV432896 - Circuit breaker ComPact NSX630H, 70kA at 415VAC, MicroLogic 2.3 trip unit 630A, 4 poles 4d
Schneider

Circuit breaker ComPact NSX630H, 70kA at 415VAC, MicroLogic 2.3 trip unit 630A, 4 poles 4d

Not for sale

Schneider LV432896, Circuit breaker ComPact NSX630H, 70kA at 415VAC, MicroLogic 2.3 trip unit 630A, 4 poles 4d. Category: ComPact NSX <630A. Not for sale; no price or quote is offered for this product.

Key Specifications

Range
ComPact
Product Name
ComPact NSX
Range Of Product
ComPact NSX400...630
Device Short Name
NSX630H

Product Description

This Compact NSX630H is a complete 4P 4d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 70kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic Micrologic 2.3 trip unit, with 630A rating. Micrologic 2.3 trip unit provides adjustable long time and short time protections, and a fixed instantaneous protection. This 4 poles version (185mm x 255mm x 110mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX630H is part of Schneider Electric EcoStruxure Power architecture.

Technical Specifications

Main22
RangeComPact
Product NameComPact NSX
Range Of ProductComPact NSX400...630
Device Short NameNSX630H
Product Or Component TypeCircuit breaker
Device ApplicationDistribution
Number Of Poles4P
Protected Poles Description3t; 4t; 3t + N/2
Neutral PositionLeft
[In] Rated Current630 A at 40 °C
[Ue] Rated Operational Voltage690 V AC 50/60 Hz
Network TypeAC
Network Frequency50/60 Hz
Suitability For IsolationYes conforming to EN/IEC 60947-2
Utilisation CategoryCategory A
[Icu] Rated Ultimate Short-circuit Breaking Capacity85 kA at 240 V AC 50/60 Hz conforming to UL 508; 65 kA at 480 V AC 50/60 Hz conforming to UL 508; 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 20
Performance LevelH 70 kA 415 V AC
Trip Unit NameMicroLogic 2.3
Trip Unit TechnologyElectronic
Trip Unit Protection FunctionsLSoI
Control TypeToggle
Circuit Breaker Mounting ModeFixed
Complementary30
[Ui] Rated Insulation Voltage800 V AC 50/60 Hz
[Uimp] Rated Impulse Withstand Voltage8 kV
[Ics] Rated Service Short-circuit Breaking Capacity11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical Durability15000 cycles
Electrical Durability2000 cycles at 690 V In; 6000 cycles at 690 V In/2; 4000 cycles at 440 V In; 8000 cycles at 440 V In/2
Mounting SupportBackplate
Upside ConnectionFront
Downside ConnectionFront
Connection Pitch45 mm
Protection TypeL : for overload protection (long time); So : for short time short-circuit protection with fixed delay; I : for instantaneous short-circuit protection
Trip Unit Rating630 A at 40 °C
Long-time Pick-up Adjustment Type Ir (thermal Protection)Adjustable 9 settings
[Ir] Long-time Protection Pick-up Adjustment Range250...630 A
Long-time Protection Delay Adjustment Type TrFixed
[tr] Long-time Protection Delay Adjustment Range16 s at 6 x Ir
Thermal Memory20 minutes before and after tripping
Short-time Protection Pick-up Adjustment Type IsdAdjustable 9 settings
[Isd] Short-time Protection Pick-up Adjustment Range1.5...10 x Ir
Short-time Protection Delay Adjustment Type TsdFixed
Instantaneous Protection Pick-up Adjustment Type IiFixed
[Ii] Instantaneous Protection Pick-up Adjustment Range6900 A
Earth-leakage ProtectionWithout
Neutral Protection Settings0.5 x Ir (3t + N/2); 1 x Ir (4t); No protection (3t)
Zone Selective Interlocking ZSIWithout
Number Of Slots For Electrical Auxiliaries6 slot(s)
Local SignallingFlashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
Width (W)185 mm
Height (H)255 mm
Depth (D)110 mm
Net Weight8.13 kg
Environment11
StandardsEN/IEC 60947
Product CertificationsCCC; EAC; Marine
Overvoltage CategoryClass II
Electrical Shock Protection ClassClass II
Pollution Degree3 conforming to IEC 60664-1
IP Degree Of ProtectionIP40 conforming to IEC 60529
IK Degree Of ProtectionIK07 conforming to IEC 62262
Ambient Air Temperature For Operation-25…70 °C
Ambient Air Temperature For Storage-50…85 °C
Relative Humidity0…95 %
Operating Altitude0...2000 m without derating; 2000 m...5000 m with derating
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height15.0 cm
Package 1 Width20.4 cm
Package 1 Length29.0 cm
Package 1 Weight7.542 kg
Unit Type Of Package 2S04
Number Of Units In Package 23
Package 2 Height30.0 cm
Package 2 Width40.0 cm
Package 2 Length60.0 cm
Package 2 Weight23.17 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads