Schneider LV481010 - VigiPact Type B RHB - Earth Leakage Protection Relay
Schneider

LV481010 - VigiPact Type B RHB - Earth Leakage Protection Relay

Schneider LV481010, VigiPact Type B RHB - Earth Leakage Protection Relay. Category: Vigirex RH10MP-RH21MP-RH99MP-RH197-RHU. Request a quote for price and lead time.

Key Specifications

Range
VigiPacT
Device Short Name
RHB
Product Or Component Type
Residual current protection relay
Relay Application
Protection relay

Product Description

VigiPacT RHB is a DIN rail mounting residual current protection and monitoring relay. It protects against people direct or indirect contact, property fire hazards and motors. It measures the earth leakage current in an electrical installation via its associated toroid. It trips the associated circuit breaker when the set residual operation current is overrun. It can activate an alarm and a pre-alarm. The operational supply voltage is 100/250VAC 50/400Hz or 100/250VDC. It is a type B earth-leakage protection class. The current sensitivity is adjustable from 30mA to 3A on the keypad. The time delay is adjustable on the keypad from instantaneous to 10s. The monitored distribution system voltage is up to 800 VAC 50/60/400 Hz. It is installed on a DIN-rail inside a switchboard and the protection degree is IP40. It must be associated with a compatible Schneider Electric type B toroid.

Key Features

  • "VigiPacT relays ensure coordination with ComPacT circuit breakers (switch off within 40ms)"
  • "Continuous monitoring of the power supply, the relay/toroid link and internal electronics"
  • "Reinforced insulation of VigiPacT relays (overvoltage category IV)"
  • "Access to settings protected by a lead-sealable cover or password"
  • RoHS and REACH compliant

Technical Specifications

Main20
RangeVigiPacT
Device Short NameRHB
Product Or Component TypeResidual current protection relay
Relay ApplicationProtection relay
Mounting SupportDIN rail
Earth-leakage Protection ClassType B
Type Of SettingKeypad
Residual Earth-leakage Sensitity Adjustment TypeAdjustable
Earth-leakage Sensitivity0.03…0.1 A, adjustable in step of 0.001 A; 0.1…1 A, adjustable in step of 0.01 A; 1…3 A, adjustable in step of 0.1 A
Earth-leakage Time DelayInstantaneous for 0.03 A; Adjustable 0…1 s for 0.03…3 A adjustable in step of 10 ms; Adjustable 1…10 s for 0.03…3 A adjustable in step of 100 ms
Threshold Setting0.015...1 A adjustable in step of 0.001 A alarm; 1...3 A adjustable in step of 0.1 A alarm
Current Sensors CompatibilityVigiPacT TB35 earth leakage current sensor; VigiPacT TB60 earth leakage current sensor; VigiPacT TB120 earth leakage current sensor; VigiPacT TB210 earth leakage current sensor; VigiPacT TB35P earth leakage current sensor; VigiPacT TB60P earth leakage current sensor
[Ithe] Conventional Enclosed Thermal Current5 A
Minimum Load1 mA at 10 V
[Us] Rated Supply Voltage100...250 V AC 50...400 Hz 70...120 %; 100...250 V DC
Power Consumption In VA6.5 VA
Monitored Distribution System800 V - AC at 0...2000 Hz (maximum)
Earthing SystemTT; TN-S
[Uimp] Rated Impulse Withstand Voltage4 kV
ResetRemote reset
Complementary17
Test FunctionRemote test; Local
MonitoringElectronics (watchdog); Power supply (continuous); Relay/sensor link (continuous)
Signal Contacts Composition1 NO/NC alarm fail-safe; 1 NO pre-alarm fail-safe
Type Of MeasurementEarth fault current internal measurement, range: 80...100 %
Tamperproof Of SettingsProtected by access code
Connections - TerminalsTerminal block 1 cable(s) 0.2…2.5 mm² flexible 24 AWG...12 AWG; Terminal block 1 cable(s) 0.2…2.5 mm² rigid 24 AWG...12 AWG; Terminal block 2 cable(s) 0.2…1.5 mm² flexible 24 AWG...12 AWG; Terminal block 2 cable(s) 0.2…1.5 mm² rigid 24 AWG...12 AWG
Wire Stripping Length8 mm; 9 mm
Tightening Torque0.5…0.6 N.m
9 Mm Pitches4
StandardsEN/IEC 60947-2 Annex M; EN/IEC 60755
Width36 mm
Height90 mm
Depth70.5 mm
Net Weight0.15 kg
IP Degree Of ProtectionIP40 on front face: conforming to EN/IEC 60529; IP30 on side parts: conforming to EN/IEC 60529; IP20 on connection terminals: conforming to EN/IEC 60529
IK Degree Of ProtectionIK07 conforming to EN 50102
Mechanical RobustnessFire resistance conforming to IEC 60695-2-1; IK protection 2 joules: IK07 conforming to EN 50102; Vibrations 13.2...100 Hz: 0.7 g; Vibrations 2...13.2 Hz: +/- 1 mm
Environment8
Environmental CharacteristicExposure to damp heat not in service conforming to IEC 60068-2-30; Exposure to damp heat in service conforming to IEC 60068-2-56; Salt mist conforming to IEC 60068-2-52
Overvoltage CategoryIII
Electrical Shock Protection ClassClass II
Electromagnetic CompatibilityConducted and radiated emissions: , B, conforming to CISPR 11; Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6; Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2; High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5; Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4; Radiated susceptibility: , 3, conforming to IE
Relative Humidity95 % at 55 °C
Pollution Degree2 conforming to IEC 60664-1
Ambient Air Temperature For Operation-25…55 °C
Ambient Air Temperature For Storage-40…85 °C
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height5.300 cm
Package 1 Width12.000 cm
Package 1 Length16.000 cm
Package 1 Weight242.000 g
Unit Type Of Package 2S04
Number Of Units In Package 240
Package 2 Height30.000 cm
Package 2 Width40.000 cm
Package 2 Length60.000 cm
Package 2 Weight10.380 kg
Logistical informations1
Country Of OriginDE
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents2

Tags

See products with the same tag in the catalogue.