Schneider TM3SAC5R - Safety module, switch monitoring, CAT3, 1 function
Schneider

TM3SAC5R - Safety module, switch monitoring, CAT3, 1 function

Schneider TM3SAC5R, Safety module, switch monitoring, CAT3, 1 function. Category: Modicon TM3. Request a quote for price and lead time.

Key Specifications

Range Of Product
Modicon TM3 Safety
Product Or Component Type
Safety module
Device Short Name
TM3SAC
Safety Module Application
For emergency stop and switch monitoring

Product Description

This TM3 safety expansion module monitors emergency shutdown pushbuttons and limit switches to conform to PLd / Category 3. It meets the requirements of PL d/Category 3 conforming to EN/ISO 13849-1 and SILCL 2 conforming to EN/IEC 62061. It has a module locking latch, 2 TM3 bus connectors designed to provide continuity of the link between connected modules, a symmetrical rail locking clip, display block for the module channels and diagnostics. It completes your Modicon M221, M241 or M251 PLC configuration with a dedicated safety I/O, without the need to use a complete safety controller. It has removable terminals for easier and better control wires tightening, thus improving installation reliability.

Key Features

  • "Make any Modicon M2xx PLC as safety controller using a functional safety I/O modules"
  • "Modularity and easness of installation"
  • "Large choice of I/O system to enhance the capabilities of Modicon M2xx plc"
  • "Removable terminal BLOCKS for better control wires tightening"
  • "Modicon TM3 is an EcoStruxure Machine I/O system"

Technical Specifications

Main6
Range Of ProductModicon TM3 Safety
Product Or Component TypeSafety module
Device Short NameTM3SAC
Safety Module ApplicationFor emergency stop and switch monitoring
Function Of ModuleEmergency stop monitoring 1-channel wiring; Emergency stop monitoring 2-channel wiring; Monitoring of a movable guard with 2 switches and automatic start
Safety LevelCan reach PL d/category 3 conforming to ISO 13849-1: 2008; Can reach PL d/category 3 conforming to ISO 13849-2: 2012; Can reach SILCL 2 conforming to IEC 62061: 2005; Can reach SIL 2 conforming to IEC 61508: 2010
Complementary32
Safety Reliability DataDC = 95 % conforming to ISO 13849-1; PFHd = 5E-9 1/h conforming to IEC 61508-1 1 operation/hour DC-13 24 V DC, <4 A; PFHd = 30E-9 1/h conforming to IEC 61508-1 60 operations/hour DC-13 24 V DC, <1 A; MTTFd = 500 years conforming to ISO 13849-1 1 operation/hour DC-13 24 V DC, <4 A; MTTFd = 85 years conforming to ISO 13849-1 60 operations/hour DC-13 24 V DC, <1 A; SFF = 95 % conforming to IEC 61508-
Synchronisation Time Between InputsUnlimited
Connections - TerminalsCaptive screw clamp terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34; Captive screw clamp terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34; Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34; Captive screw c
Output TypeRelay instantaneous opening, 3 NO circuit(s), potential free
Number Of Safety Circuits3 NO for relay instantaneous opening
Maximum Switching Voltage230 V utilisation category AC-15 at 50 Hz (relay instantaneous opening); 24 V utilisation category DC-13 (relay instantaneous opening)
[Us] Rated Supply Voltage24 V - 15...20 % DC
Power Consumption In W0.2 W at 5 V DC; 3.6 W at 24 V DC
Input Protection TypeInternal, electronic
[Uc] Control Circuit Voltage24 V DC
Maximum Cable Distance Between Devices30 m
Breaking Capacity360 VA holding AC-15 B300 relay output; 3600 VA inrush AC-15 B300 relay output
Output Thermal Current6 A per relay for relay output
[Ith] Conventional Free Air Thermal Current18 A
Associated Fuse Rating4 A gG or gL for relay output conforming to IEC 60947-5-1; 6 A fast blow for relay output conforming to IEC 60947-5-1
Minimum Output Current10 mA for relay output
Output Voltage10 V relay output
Maximum Response Time On Input Open40 ms
[Ui] Rated Insulation Voltage300 V (pollution degree 2) conforming to IEC 60647-5-1
[Uimp] Rated Impulse Withstand Voltage4 kV overvoltage category III conforming to IEC 60647-5-1
Current Consumption100 mA at 24 V DC external supply (at state on)
Local Signalling6 LEDs (green/red) for user
Electrical ConnectionScrew terminal
StandardsISO 13849-1:2008; ISO 13849-2:2012; IEC 62061:2005; IEC 61508:2010; IEC 60947-5-1:2010; IEC 61131-2:2007; IEC 60204-1:2005; IEC 60204-1:2009/A1; IEC 61010-1:2010; EN 50581:2012
Product CertificationsTÜV; CSA 61010-2-201 (pending); CSA Haz Loc Class 1 Division 2 (pending); RCM; ANSI Haz Loc Class 1 Division 2 (pending); EAC; UL 61010-2-201
MarkingEFUP 10; RCM; CSA; UL; TÜV; CE; EAC
Electromagnetic CompatibilityElectrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2; Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2; Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to IEC 61000-4-3; Susceptibility to electromagnetic fields - test level: 3 V/m (1.4 GHz...2 GHz) conf
Mounting SupportTop hat type TH35-7.5 rail conforming to IEC 60715; Top hat type TH35-15 rail conforming to IEC 60715; wall mount using attached fasteners
Height94 mm
Depth73 mm
Width43.7 mm
Net Weight0.19 kg
Environment18
StandardsEN 1088/ISO 14119; ISO 13850; IEC 60947-1; IEC 60204-1; IEC 60947-5-1
Resistance To Electrostatic Discharge8 kV in air conforming to IEC 61000-4-2; 6 kV on contact conforming to IEC 61000-4-2
Resistance To Electromagnetic Fields10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3; 3 V/m 1.4 GHz...2 GHz conforming to IEC 61000-4-3; 1 V/m 2 GHz...3 GHz conforming to IEC 61000-4-3
Resistance To Magnetic Fields30 A/m 50/60 Hz conforming to IEC 61000-4-8
Resistance To Fast Transients3 kV for power lines (DC) (DC) conforming to IEC 61000-4-4; 2 kV for I/O lines conforming to IEC 61000-4-4
Surge Withstand1 kV power lines (DC) differential mode conforming to IEC 61000-4-5 DC; 1 kV power lines (DC) common mode conforming to IEC 61000-4-5 DC
Resistance To Conducted Disturbances10 V 0.15...80 MHz conforming to IEC 61000-4-6
Electromagnetic EmissionRadiated emissions - test level: 50 dBµV/m class A ( 24 V DC) at 30…230 Hz conforming to IEC 61131-3; Radiated emissions - test level: 57 dBµV/m class A ( 24 V DC) at 230…1000 Hz conforming to IEC 61131-3
Ambient Air Temperature For Operation-10…55 °C horizontal installation
Ambient Air Temperature For Storage-25…70 °C
Relative Humidity10…95 %, without condensation (in operation); 10…95 %, without condensation (in storage)
IP Degree Of ProtectionIP20 (terminals) conforming to IEC 60529
Pollution Degree2
Operating Altitude0...2000 m
Storage Altitude0…3000 m
Vibration Resistance+/- 3.5 mm (f= 5…150 Hz) conforming to IEC 60068-2-6
Shock Resistance15 gn for 11 ms conforming to IEC 60068-2-27
Mechanical RobustnessBumps 6 ms 300 shocks (25 gn) conforming to IEC 60068-2-27
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height7.500 cm
Package 1 Width10.600 cm
Package 1 Length12.500 cm
Package 1 Weight283.000 g
Unit Type Of Package 2S03
Number Of Units In Package 218
Package 2 Height30.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight5.522 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents3

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support