Schneider TPRST009 - TeSys Island Starter 9A/4kW
Schneider

TPRST009 - TeSys Island Starter 9A/4kW

Schneider TPRST009, TeSys Island Starter 9A/4kW. Category: TeSys island. Request a quote for price and lead time.

Key Specifications

Range
TeSys
Product Name
TeSys island
Device Short Name
TPRST
Product Or Component Type
Motor starter

Product Description

TeSys island direct starter, 3 poles, 9A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 9A and motors up to 4kW@400V / 5hp@480V. It provides motor protection functions including thermal overload (setting 0.18-9A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of switching cycles, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC).

Key Features

  • Upstream voltage presence detection
  • Power and energy monitoring when connected with TPRVM voltage module
  • Manages motors and other electrical loads up to 80 A (AC-3) / 37 kW/40 hp
  • All adjustments and setting are digitized, no mechanical dials or dip switches
  • Embedded Cybersecurity (Achilles Level 2)

Technical Specifications

Main29
RangeTeSys
Product NameTeSys island
Device Short NameTPRST
Product Or Component TypeMotor starter
Motor Starter TypeDirect on line
Device PresentationDirect starter connected to an automation controller through a bus coupler; Operational only when connected to a bus coupler
Function AvailableUpstream voltage presence detection; Electrical line and load protection; Power and energy monitoring when connected with TPRVM voltage module
Product CompatibilityTPRBC bus coupler; TPRVM voltage interface module
Poles Description3P (3 NO)
Utilisation CategoryAC-1; AC-2; AC-3; AC-4; AC-3e
Motor Power KW2.2 kW at 230 V 50 Hz (AC-3); 4 kW at 380...415 V 50 Hz (AC-3); 4 kW at 440 V 50 Hz (AC-3); 5.5 kW at 500 V 50 Hz (AC-3); 5.5 kW at 690 V 50 Hz (AC-3)
Motor Power HP (UL / CSA)0.33 hp at 120 V AC 60 Hz for 1 phase motors; 1 hp at 240 V AC 60 Hz for 1 phase motors; 2 hp at 208 V AC 60 Hz for 3 phases motors; 2 hp at 240 V AC 60 Hz for 3 phases motors; 5 hp at 480 V AC 60 Hz for 3 phases motors; 7.5 hp at 600 V AC 60 Hz for 3 phases motors
[Ue] Rated Operational Voltage<= 690 V AC 47...63 Hz
[Ie] Rated Operational Current9 A (at <50 °C) at <= 440 V AC-3; 15 A (at <50 °C) at <= 440 V AC-1
[Ith] Conventional Free Air Thermal Current15 A (at 50 °C)
[Ui] Rated Insulation Voltage690 V conforming to IEC 60947-4-1; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] Rated Impulse Withstand Voltage6 kV conforming to IEC 60947-1
Overvoltage CategoryIII
Thermal Protection Adjustment Range0.18…9 A
Thermal Overload ClassClass 5…30
ResetRemotely or automatically
Irms Rated Making Capacity250 A at 440 V conforming to IEC 60947
Rated Breaking Capacity250 A at 440 V conforming to IEC 60947
[Icw] Rated Short-time Withstand Current210 A 40 °C - 1 s; 105 A 40 °C - 10 s; 61 A 40 °C - 1 min; 30 A 40 °C - 10 min
Average Impedance2.5 mOhm - Ith 15 A 50 Hz
Power Dissipation Per Pole0.2 W AC-3 - Ith 9 A; 0.56 W AC-1 - Ith 15 A
[Uc] Control Circuit Voltage24 V DC supplied by the bus coupler
Current Consumption160 mA contactor sealed; 160 mA contactor closing
Power Dissipation In W3.5 W at Ie AC-3
Complementary17
Mechanical Durability30 Mcycles
Electrical Durability2 Mcycles 9 A AC-3 at Ue 440 V; 1.2 Mcycles 15 A AC-1 at Ue 440 V
Maximum Operating Rate3600 cyc/mn AC-3
Operating Time< 100 ms closing; < 30 ms opening
Safety Performance LevelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Protection TypeThermal overload protection; Motor overheat; Overcurrent; Undercurrent; Jam; Long start; Stall; Rapid cycle lockout; Phase sequence; Rapid restart lockout; Phase reversal; Phase loss; Phase unbalance; Ground current
Monitoring TypeTime device ON; Time device switch ON; Number of faults; Number of switching cycles; Number of device power cycles; Average current Iavg; Average voltage Vavg; Max current Imax; Max voltage Vmax; Active and reactive power with voltage module; Active and reactive energy with voltage module; True power factor with voltage module
Local Signalling1 LED (green/red) for DS (device status); 1 LED (green/red) for LS (load status)
StandardsEN/IEC 60947-1; EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1
Product CertificationsEAC; CSA; CCC; UL
Mounting ModeHorizontal and vertical (35 mm symmetrical DIN rail)
Connections - TerminalsScrew-clamp terminals 1 cable(s) 1…4 mm² (16 AWG...12 AWG) rigid; Screw-clamp terminals 2 cable(s) 1…4 mm² (16 AWG...12 AWG) rigid; Screw-clamp terminals 1 cable(s) 1.5…4 mm² (16 AWG...12 AWG) flexible without cable end; Screw-clamp terminals 2 cable(s) 1.5…4 mm² (16 AWG...12 AWG) flexible without cable end; Screw-clamp terminals 1 cable(s) 1…4 mm² (16 AWG...12 AWG) flexible with cable end; Screw-
Tightening Torque1.7 N.m - with screwdriver flat Ø 6 mm; 1.7 N.m - with screwdriver Philips No 2
Width45 mm
Height116 mm
Depth115 mm
Net Weight0.656 kg
Environment11
Ambient Air Temperature For Storage-25…70 °C
Ambient Air Temperature For Operation-10…50 °C without derating; 50…60 °C with current derating
Relative Humidity5…95 %
Operating Altitude0...2000 m without derating
IP Degree Of ProtectionIP20
Pollution Degree2
Protective TreatmentTC
Fire Resistance960 °C conforming to UL 94; 850 °C conforming to IEC 60695-2-1; 650 °C conforming to IEC 60695-2-12
Shock Resistance15 gn (duration = 11 ms) conforming to IEC 60068-2-27
Vibration Resistance1.5 mm peak to peak (f= 3…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Electromagnetic CompatibilityElectrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2; Radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3; Fast transient immunity test, level 4, 4 kV, conforming to EN/IEC 61000-4-4; Surge immunity test (differential mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5; Surge immunity test (common mode), level 4, 4 kV,
Packing Units12
Unit Type Of Package 1PCE
Number Of Units In Package 11
Package 1 Height5.000 cm
Package 1 Width12.500 cm
Package 1 Length13.000 cm
Package 1 Weight711.000 g
Unit Type Of Package 2S02
Number Of Units In Package 214
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight10.252 kg
Logistical informations1
Country Of OriginFR
Contractual warranty1
Warranty (in Months)18

Documents and Downloads

Documents are published by the manufacturer and open in a new tab.

Other Documents2

Tags

See products with the same tag in the catalogue.

WhatsApp Direct Support