| Number Of Step Output Contacts | 12 |
|---|
| [Us] Rated Supply Voltage | 90...550 V AC; <= 999 kV AC with external VT |
|---|
| Measurement Current | 0…5 A |
|---|
| Measurement Voltage | 90…550 V AC 50/60 Hz |
|---|
| Operating Mode | Manual or automatic |
|---|
| Number Of Quadrant Operation For Generator Application | 4 |
|---|
| Device Connection | Communication protocol: Modbus interface: RS485 |
|---|
| Input Function | Switch: 1 x dry contact |
|---|
| Colour Code | Front: dark grey RAL 7016 |
|---|
| Display Type | Backlit LCD |
|---|
| Display Size | 56 x 25 mm |
|---|
| Function Available | Manual programming; Automatic initialisation; Automatic detection; Advanced programming (expert); Any step sequence |
|---|
| Metering Type | Power factor and displacement PF (signed, four quadrant); Total current harmonic distortion THD (I); Power factor average over lifetime; Temperature maximum; Phase current I1, I2, I3 RMS on load; Active power P, P1, P2, P3 on load; Reactive power Q, Q1, Q2, Q3 on load; Apparent power S, S1, S2, S3 on load; Voltage U21, U32, U13, V1, V2, V3 on load |
|---|
| Type Of Measurement | Capacitor current overload Irms/I1; Individual voltage harmonic; Power factor; Operating time; Cos φ; Ambient temperature inside the cubicle; Tan φ |
|---|
| Information Displayed | Number of switching cycles per step; Individual step size in kVAr; Remaining step capacity in % |
|---|
| Type Of Alarms | Step power loss (< 75 %) / Action: message and alarm contact + step blocked; Step faulty / Action: message and alarm contact + step blocked; High current (> 6 A CT) / Action: message and alarm contact; Hunting (unstable regulation) / Action: message and alarm contact + step blocked; Low current (< 15 mA CT) / Action: message and alarm contact; Overcompensation / Action: message and alarm contact; |
|---|
| Data Recording | 5 alarms |
|---|
| Operational Hours Alarm | 100000 h without maintenance |
|---|
| Operational Counter Alarm | 65000 cycles without maintenance |
|---|
| Input Type | Phase to phase; Phase to neutral; Insensitive to CT polarity; Insensitive to phase rotation polarity; Current input CT...X/5 A and X/1 A |
|---|
| Output Type | Control relay: 0.2 A 110 V DC; Control relay: 1 A 48 V DC; Control relay: 2 A 400 V AC 50/60 Hz; Control relay: 1 A 24 V DC; Control relay: 5 A 250 V AC 50/60 Hz; Control relay: 5 A 120 V AC 50/60 Hz; Fan: 5 A 250 V AC 50/60 Hz; Fan: 1 A 48 V DC; Alarm relay: 5 A 250 V AC 50/60 Hz; Alarm relay: 1 A 48 V DC |
|---|
| Maximum At The Common Terminal | 10 A |
|---|
| Settings Operating Mode | Automatic; Manual |
|---|
| Type Of Setting | Choice of stepping programs: auto; Choice of stepping programs: LIFO; Choice of stepping programs: linear; Delay between 2 successive switch on the same step: 5...1200 s; Step configuration programming: auto; Step configuration programming: off; Step configuration programming: fixed; Target cos phi: 0.7 inductive...0.7 capacitive; Target cos phi: dual cos φ |
|---|
| Measurement Accuracy | Voltage +/- 1 %; Current +/- 1 %; Frequency +/- 1 %; Energy (P,Q,S) +/- 2 %; Cos φ +/- 2 %; Total voltage harmonic distortion THD (U) +/- 2 %; Individual voltage harmonic +/- 3 %; Temperature +/- 3 °C |
|---|
| Time Delay Range | 1...6500 s (on reconnection); 1...6500 s (on response) |
|---|
| Provided Equipment | User manual |
|---|
| Mounting Mode | Flush-mounted |
|---|
| Mounting Support | Panel - thickness: 1…3 mm |
|---|
| Mounting Location | In cabinet |
|---|
| Cut-out Dimensions | 138 x 138 mm |
|---|
| Height | 144 mm |
|---|
| Width | 144 mm |
|---|
| Depth | 58 mm |
|---|
| Net Weight | 0.6 kg |
|---|
| Compatibility Code | VPL 12 |
|---|