safety controller XPS-MC - 24 V DC - 16 input - 32 LEDs signalling

Schneider XPSMC16ZC, safety controller XPS-MC - 24 V DC - 16 input - 32 LEDs signalling. Category: Modicon MCM. Not for sale; no price or quote is offered for this product.
- Reference:XPSMC16ZC
- Manufacturer / Brand:Schneider
Key Specifications
- Range Of Product
- Preventa Safety automation
- Product Or Component Type
- Configurable safety controller
- Safety Module Name
- XPSMC
- Type Of Start
- Configurable
Product Description
This product is part of the Preventa XPS MP, XPS MC, XPS MCM range, an offer of safety controllers. This safety controller provides 16 inputs and 32 LEDs for signalling. It is a safety controller with a power consumption of 12W, control circuit voltage of 28.8V and a rated supply voltage of 24V DC. Supported communication port protocols are Modbus with RJ45 port, CANopen with 9-way SUB-D male port. It is an IP20 rated product. Its dimensions are 74mm (Width) x 153mm (Depth) x 151.5mm (Height). It weighs 0.82kg. It is designed to provide a solution for safety applications requiring conformity to Performance Level PL e/Category 4 EN/ISO 13849-1 and SIL3 EN/IEC 61508. This product is certified by UL, CSA and TUV. It meets EN 574/ISO 13851, EN 1760-1/ISO 13856-1, EN/IEC 61496-1, EN/IEC 60204-1, EN/IEC 60947-5-1, EN 954-1/EN/ISO 13849-1 and IEC 61508 standards. Simple, it features redundancy principle micro-processor based technology to provide advanced functions, flexibility regarding the choice of safety function and more precise diagnostics are just some of its advantages. Safety controller XPS MC is configured with a simple software environment where functions are mapped to the various controller outputs according to the application requirements.
Technical Specifications
Main11
| Range Of Product | Preventa Safety automation |
|---|---|
| Product Or Component Type | Configurable safety controller |
| Safety Module Name | XPSMC |
| Safety Use Category | Category 4 maximum conforming to EN 954-1/EN/ISO 13849-1; PLE maximum conforming to ISO 13849-1; SIL 3 maximum conforming to IEC 61508 |
| Type Of Start | Configurable |
| Standards | IEC 61496-1; EN 574/ISO 13851; EN 1760-1/ISO 13856-1; IEC 61508; EN 954-1/EN/ISO 13849-1; IEC 60947-5-1; IEC 60204-1 |
| Product Certifications | UL; TÜV; CSA |
| [Us] Rated Supply Voltage | 24 V DC - 20...20 % |
| Number Of Inputs | 16 |
| Communication Port Protocol | CANopen with 1 SUB-D 9-pin male port(s), serial link, transmission rate: 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 800 kbps or 1 Mbps; Modbus with 1 RJ45 port(s), serial link, transmission rate: 1200 bps, 2400 bps, 4800 bps, 9600 bps or 19200 bps |
| Safety Level | Can reach PL e/category 4 conforming to EN 954-1/EN/ISO 13849-1; Can reach SIL 3 conforming to IEC 61508 |
Complementary28
| Function Of Module | Emergency stop monitoring, with or without time delay, 1 or 2-channel wiring; Enabling switch monitoring, 2 or 3 contacts; Foot switch monitoring; Guard monitoring with 1 or 2 limit switches; Magnetic switch monitoring category 4 conforming to EN/IEC 61496; Muting function of light curtains; Position selector; Safety mat monitoring; Safety time delays; Shaft/chain breaking monitor; Zero speed dete |
|---|---|
| Synchronisation Time Between Inputs | Depending on configuration selected |
| Power Consumption In W | 12 W |
| Input Protection Type | External fuse 16 A |
| [Uc] Control Circuit Voltage | 28.8 V |
| Maximum Line Resistance | 100 Ohm <2000 m |
| Output Type | 2 relays, 2 NO contacts (4 NO total) circuit(s); Solid state, 6 circuit(s), volt-free |
| Breaking Capacity | 180 VA holding AC-15 C300 relay output; 1800 VA inrush AC-15 C300 relay output |
| Output Thermal Current | 4 A for both outputs simultaneously; 6 A for 1 output and 2 A for the other for relay output |
| [Ith] Conventional Free Air Thermal Current | 16 A for relay output; 6.5 A for static output circuit |
| Associated Fuse Rating | 16 A gL for power supply; 4 A gL for relay output; 6 A fast blow for relay output |
| Minimum Output Current | 10 mA for relay output |
| Minimum Output Voltage | 17 V for relay output |
| Response Time | Configurable : 20 ms or 30 ms with software XPSMCWIN |
| [Ui] Rated Insulation Voltage | 300 V (pollution degree 2) conforming to IEC 60647-5-1, DIN VDE 0110 part 1 |
| [Uimp] Rated Impulse Withstand Voltage | 4 kV overvoltage category III conforming to IEC 60647-5-1, DIN VDE 0110 part 1 |
| Method Of Access | Slave |
| Exchange Size | 14 words |
| Number Of Addresses | 1…127 for CANopen; 1…247 for Modbus |
| Parity | Even for Modbus; No for Modbus; Odd for Modbus |
| Data Format | 1 start bit/8 data bits; 1 stop bit even or odd; 2 stop bits without parity; RTU (Remote Terminal Unit) mode |
| Supported Modbus Function | 01: 8-bit output data/32-bit input data; 02: 32-bit input data/8-bit output data; 03: information and errors |
| Local Signalling | 32 LEDs |
| Mounting Support | Mounting plate |
| Depth | 153 mm |
| Height | 151.5 mm |
| Width | 74 mm |
| Net Weight | 0.82 kg |
Environment3
| IP Degree Of Protection | IP20 conforming to IEC 60529 |
|---|---|
| Ambient Air Temperature For Operation | -10…55 °C |
| Ambient Air Temperature For Storage | -25…85 °C |
Packing Units12
| Unit Type Of Package 1 | PCE |
|---|---|
| Number Of Units In Package 1 | 1 |
| Package 1 Height | 9.500 cm |
| Package 1 Width | 18.000 cm |
| Package 1 Length | 26.000 cm |
| Package 1 Weight | 1.265 kg |
| Unit Type Of Package 2 | S04 |
| Number Of Units In Package 2 | 6 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 40.000 cm |
| Package 2 Length | 60.000 cm |
| Package 2 Weight | 8.459 kg |
Logistical informations1
| Country Of Origin | FR |
|---|
Contractual warranty1
| Warranty (in Months) | 18 |
|---|
Documents and Downloads